Thermal management in legacy air-cooled data centers: An overview and perspectives

被引:13
|
作者
Isazadeh, Amin [1 ]
Ziviani, Davide [2 ]
Claridge, David E. [1 ]
机构
[1] Texas A&M Univ, Sch Mech Engn, Energy Syst Lab, College Stn, TX 77840 USA
[2] Purdue Univ, Sch Mech Engn, Ray W Herrick Labs, W Lafayette, IN 47907 USA
来源
关键词
Data center; Air-cooled systems; Hard-floor design; Raised-floor design; Cold/hot aisle configuration; Aisle containment; Exhaust chimney; Evaporative cooling; Desiccant wheel; Thermal energy storage; RAISED-FLOOR; PERFORMANCE; SYSTEMS; HEAT;
D O I
10.1016/j.rser.2023.113707
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Depletion of fossil fuel reservoirs, greenhouse gas emissions' impact on global warming, and rising energy costs are pushing the data center sector to reduce energy use. This paper reviews strategies for improving the energy performance of air-cooled systems in datacom facilities and enhancing temperature and flow distribution in white space by analyzing different airflow delivery architectures (hard floor and raised floor designs), eliminating cold and hot air mixing by incorporating cold/hot aisle containment or exhaust chimneys, and potential energy savings achievable by utilizing evaporative cooling systems. It was found that the optimal ventilation system is hard-floor architecture with locally-ducted supply and return air. Hard floor is less complicated than raised floor design, and overhead supply air can minimize hot spots at the top of racks. Airflow management strategies including cold and hot aisle formation, aisle containment, and exhaust chimneys can reduce annual cooling energy usage by 10-50% in conjunction with air-side and water-side economizers, minimize hot spots, and enhance thermal performance during cooling system failure. Hot-Aisle Containment or exhaust chimneys provide better thermal and energy performance than open and/or cold-aisle containment, but they require new ducting in traditional data centers. Depending on the climate and geographical location, evaporative cooling can reduce annual cooling energy usage by 20-70% and lead to Power Usage Effectiveness as low as 1.06. Evaporative coolers are more suitable for dry climates, but this limitation can be ameliorated by incorporating desiccant wheels and thermal energy storage.
引用
收藏
页数:18
相关论文
共 50 条
  • [1] Dynamic thermal management of air cooled data centers
    Bash, Cullen E.
    Patel, Chandrakant D.
    Sharma, Ratnesh K.
    2006 PROCEEDINGS 10TH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONICS SYSTEMS, VOLS 1 AND 2, 2006, : 445 - +
  • [2] Workload management for air-cooled data centers: An energy and exergy based approach
    Gupta, Rohit
    Moazamigoodarzi, Hosein
    MirhoseiniNejad, SeyedMorteza
    Down, Douglas G.
    Puri, Ishwar K.
    ENERGY, 2020, 209
  • [3] ENERGY MODELING OF AIR-COOLED DATA CENTERS: PART II THE EFFECT OF RECIRCULATION ON THE ENERGY OPTIMIZATION OF OPEN-AISLE, AIR-COOLED DATA CENTERS
    Demetriou, Dustin W.
    Khalifa, H. Ezzat
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 395 - 404
  • [4] THERMAL MANAGEMENT OF AIR-COOLED AND LIQUID-COOLED MULTICHIP MODULES
    BARCOHEN, A
    IEEE TRANSACTIONS ON COMPONENTS HYBRIDS AND MANUFACTURING TECHNOLOGY, 1987, 10 (02): : 159 - 175
  • [5] Evaluation of the cooling effectiveness of air-cooled data centers by energy diagram
    Li, Nan
    Li, Haowei
    Duan, Kaiwen
    Tao, Wen-Quan
    APPLIED ENERGY, 2025, 382
  • [6] Investigation of Exergy Destruction in CFD Modeling for a Legacy Air-Cooled Data Center
    Silva-Llanca, Luis
    Ortega, Alfonso
    Fouladi, Kamran
    del Valle, Marcelo
    Sundaralingam, Vikneshan
    2014 IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM), 2014, : 1366 - 1374
  • [7] Multi-scale collaborative modeling and deep learning-based thermal prediction for air-cooled data centers: An innovative insight for thermal management
    Wang, Ningbo
    Guo, Yanhua
    Huang, Congqi
    Tian, Bo
    Shao, Shuangquan
    APPLIED ENERGY, 2025, 377
  • [8] Cooling architecture selection for air-cooled Data Centers by minimizing exergy destruction
    Gupta, Rohit
    Asgari, Sahar
    Moazamigoodarzi, Hosein
    Pal, Souvik
    Puri, Ishwar K.
    ENERGY, 2020, 201
  • [9] Impacts of Increasing Temperature and Relative Humidity in Air-Cooled Tropical Data Centers
    Van Le, Duc
    Zhou, Jing
    Wang, Rongrong
    Tan, Rui
    Duan, Fei
    IEEE TRANSACTIONS ON SUSTAINABLE COMPUTING, 2024, 9 (05): : 790 - 802
  • [10] Development of an Outdoor Air Cooling-Type Air-Cooled Package Air Conditioner for Data Centers
    Udagawa, Yosuke
    Sekiguchi, Keisuke
    Yanagi, Masahide
    Uekusa, Tsuneo
    Naito, Yasuhiro
    ASHRAE TRANSACTIONS 2013, VOL 119, PT 1, 2013, 119 : 167 - 175