EXPERIMENTAL STUDY ON HIGH TEMPERATURE HEAT PUMP SYSTEM WITH A DOUBLE HEAT SOURCE CASCADE

被引:1
|
作者
Bai, Jing [1 ]
Jia, Yifei [1 ]
Cui, Siqi [1 ]
Zhang, Chao [1 ]
Feng, Shiwei [1 ]
Xu, Chuang [1 ]
Fan, Huifang [1 ]
机构
[1] Zhongyuan Univ Technol, Sch Energy & Environm, Zhengzhou, Peoples R China
来源
THERMAL SCIENCE | 2023年 / 27卷 / 3A期
关键词
high temperature heat pump; dual heat sources; system performance; cascade type; SLIDING MODE CONTROL; OPTIMIZATION;
D O I
10.2298/TSCI2303845B
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to improve the thermal performance of a high temperature heat pump system, to realize the efficient heat recovery of industrial waste heat, and to make the combined utilization of low and medium temperature heat sources, a high temperature heat pump system with a double heat source cascade is proposed, which can absorb heat from industrial waste heat and the system is capable of heating water up to the required high temperature. The performance of the sys-tem is tested and analyzed. It is found that the inlet temperature of the medium temperature heat source has a significant impact on the performance of the heat pump system under working mode of the medium and low temperature heat sources. When the inlet temperature of the intermediate temperature heat source rises from 42 & DEG;C to 53 & DEG;C, the heating capacity of the cascade heat pump increas-es by 18.6%, and its performance coefficient increases by 8.9%. This paper pro-vides a reference for the high efficiency of the cascade high temperature heat pump technology.
引用
收藏
页码:1845 / 1853
页数:9
相关论文
共 50 条
  • [41] A semi-cascade heat pump system for different temperature lifts
    Kezier, Deliya
    Cheng, Jia-Hao
    Li, Xin-Yue
    Cao, Xiang
    Zhang, Chun-Lu
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [42] The effect of water temperature lift on the performance of cascade heat pump system
    Kim, Dong Ho
    Kim, Min Soo
    APPLIED THERMAL ENGINEERING, 2014, 67 (1-2) : 273 - 282
  • [43] Experimental study on temperature control optimization of ground source heat pump horizontal headers
    Tian, Xusong
    Mao, Ruiyong
    Pei, Peng
    Wu, Hongwei
    Ma, Hong
    Hu, Cheng
    Zhang, Zujing
    ENERGY AND BUILDINGS, 2022, 277
  • [44] Experimental and modeling analysis of a ground source heat pump system
    Montagud, Carla
    Miguel Corberan, Jose
    Ruiz-Calvo, Felix
    APPLIED ENERGY, 2013, 109 : 328 - 336
  • [45] EXPERIMENTAL STUDY ON A NEW HIGH TEMPERATURE AIR SOURCE HEAT PUMP IN HOT SUMMER AND COLD WINTER AREAS
    Sun J.
    Wu K.
    Wang Y.
    Huo C.
    Ge Z.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (06): : 186 - 192
  • [46] Experimental exergy assessment of ground source heat pump system
    Ahmad, Saif Nawaz
    Prakash, Om
    ADVANCES IN ENERGY RESEARCH, 2019, 6 (02): : 161 - 172
  • [47] Experimental study on a bifunctional heat utilization system of heat pump and power generation using low-grade heat source
    He, Zhonglu
    Zhang, Yufeng
    Wu, Zhangxiang
    Ma, Hongting
    Dong, Shengming
    APPLIED THERMAL ENGINEERING, 2017, 124 : 71 - 82
  • [48] Construction and experimental research on heat pump system based on heat-source tower
    Liang, Caihua
    Wen, Xiantai
    Zhang, Xiaosong
    Huagong Xuebao/CIESC Journal, 2010, 61 (SUPPL. 2): : 142 - 146
  • [49] Experimental study on solar assisted heat pump system for heat supply
    Kuang, YH
    Wang, RZ
    Yu, LQ
    ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (07) : 1089 - 1098
  • [50] Experimental study of solar assisted heat pump system for heat supply
    Kuang, Yuhui
    Wang, Ruzhu
    Yu, Liqiang
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2002, 23 (04): : 408 - 413