Performance Study of Booster-Driven Hybrid Cooling Units for Free Cooling in Data Centers

被引:2
|
作者
Zhuang, Rong [1 ,2 ]
Zhou, Feng [3 ]
Tian, Xuwen [3 ]
Xu, Buqing [3 ]
Li, Shaocong [3 ]
Ma, Guoyuan [3 ]
机构
[1] State Key Lab Air Conditioning Equipment & Syst En, Zhuhai 519070, Peoples R China
[2] Gree Elect Appliances Inc Zhuhai, Zhuhai 519000, Peoples R China
[3] Beijing Univ Technol, Dept Refrigerat & Cryogen Engn, Beijing 100124, Peoples R China
关键词
data center; booster; free cooling; thermal performance; LOOP;
D O I
10.3390/su151914558
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the data center, using ambient energy cooling technology can effectively reduce the average power use efficiency, and the heat pipe as an effective use of ambient energy device has attracted much attention. For the dynamic heat pipe, reducing the power consumption of the pump effectively is the key to improving the efficiency. In this paper, the rotary booster is selected as the gas phase booster device of the heat pipe unit, the standard unit of the rotary booster is improved, and three types of boosters are obtained, including two improved boosters and one standard unit. Comparative test studies are conducted on three different types of boosters, and the power of the booster shows a downward trend with the increase in indoor and outdoor temperature differences (outdoor temperature decreases). With the increase in indoor and outdoor temperature differences, the cooling capacity increases first and then decreases. When the indoor and outdoor temperature difference is greater than 20 degrees C, the suction pressure of the booster is greater than the saturated condensing pressure force under outdoor ambient temperature, and the work of the booster decreases. Among the three types of boosters, the medium pressure ratio booster energy efficiency ratio (EER) is the largest. After throttling the standard unit, results show that its cooling capacity unit increases, but the booster power also increases, and the EER is still smaller than that of the improved unit.
引用
收藏
页数:19
相关论文
共 50 条
  • [1] Cooling performance of a pump-driven two phase cooling system for free cooling in data centers
    Ma, Yuezheng
    Ma, Guoyuan
    Zhang, Shuang
    Zhou, Feng
    APPLIED THERMAL ENGINEERING, 2016, 95 : 143 - 149
  • [2] Experimental study on direct evaporative cooling for free cooling of data centers
    Li, Chao
    Mao, Ruiyong
    Wang, Yong
    Zhang, Jun
    Lan, Jiang
    Zhang, Zujing
    ENERGY, 2024, 288
  • [3] Experimental study on free cooling performance of an integrated cooling system based on loop thermosyphon for data centers
    Wang, Jing
    Cao, Xiaoling
    Yuan, Yanping
    Yu, Nanyang
    Zhou, Xu
    Li, Jinwei
    Wu, Lang
    ENERGY, 2025, 322
  • [4] Study on Free Cooling Systems for Data Centers in Japan
    Udagawa, Yosuke
    Waragai, Shisei
    Yanagi, Masahide
    Fukumitsu, Wataru
    32ND INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE (INTELEC), 2010,
  • [5] Free cooling of data centers: A review
    Zhang, Hainan
    Shao, Shuangquan
    Xu, Hongbo
    Zou, Huiming
    Tian, Changqing
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 35 : 171 - 182
  • [6] Research on Free Cooling of Data Centers by Using Indirect Cooling of Open Cooling Tower
    Dong, Kaijun
    Li, Pingjie
    Huang, Zhilin
    Su, Lin
    Sun, Qin
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2831 - 2838
  • [7] Performance Investigation on the Thermosyphon with Evaporative Condenser for Free Cooling of Data Centers
    Liu, Haichao
    Shao, Shuangquan
    Zhang, Hainan
    Tian, Changqing
    JOINT INTERNATIONAL CONFERENCE ON ENERGY, ECOLOGY AND ENVIRONMENT ICEEE 2018 AND ELECTRIC AND INTELLIGENT VEHICLES ICEIV 2018, 2018,
  • [8] DYNAMIC ANALYSIS OF HYBRID COOLING DATA CENTERS SUBJECTS TO THE FAILURE OF CRAC UNITS.
    Gao, Tianyi
    Samadiani, Emad
    Schmidt, Roger
    Sammakia, Bahgat
    PROCEEDINGS OF THE ASME INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, 2013, VOL 2, 2014,
  • [9] Parametric study of hybrid cooling solution for thermal management of data centers
    Mulay, Veerendra
    Karajgikar, Saket
    Agonafer, Dereje
    Schmidt, Roger
    Iyengar, Madhusudan
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION 2007, VOL 8, PTS A AND B: HEAT TRANSFER, FLUID FLOWS, AND THERMAL SYSTEMS, 2008, : 519 - 526
  • [10] Computational study of hybrid cooling solution for thermal management of data centers
    Mulay, Veerendra
    Karajgikar, Saket
    Agonafer, Dereje
    Schmidt, Roger
    Iyengar, Madhusudan
    Nigen, Jay
    IPACK 2007: PROCEEDINGS OF THE ASME INTERPACK CONFERENCE 2007, VOL 1, 2007, : 723 - 731