Simulation research on cable-laying scheme of HIAF dipole power supply

被引:0
|
作者
Zhang, Runzu [1 ]
Feng, Anhui [1 ]
Liu, Ye [1 ]
Zhou, Zhongzu [1 ]
Zhang, Yongbo [1 ]
Liu, Pengfei [1 ]
Yang, Jiancheng [1 ]
Gao, Daqing [1 ]
Ruan, Shuang [1 ]
Shen, Guodong [1 ]
Liu, Hengmin [2 ]
机构
[1] Chinese Acad Sci, Inst Modern Phys, Lanzhou 730000, Peoples R China
[2] Tianshui Elect Drive Res Inst Grp Co Ltd, Tianshui 741020, Peoples R China
关键词
Cable; Pulse current; Laying scheme; Electrodynamic force; Vibration; FINITE-ELEMENT-ANALYSIS; CIRCUIT ELECTROMAGNETIC FORCE; MECHANICAL-STRESS;
D O I
10.1007/s41605-022-00371-z
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
BackgroundA strong electromagnetic force is the major cause of vibration in dipole power supply cables. Moreover, the long-term operation of cables under vibration conditions leads to structural fatigue failure. Purpose and methodsTo investigate the cable-laying scheme of a dipole power supply, a finite element model for the electromagnetic-structural coupling between cables and cleats was established. The electrodynamic forces were simulated for fixed-length cables in the horizontal, vertical, and bent models under pulse-current excitation. Subsequently, based on the optimized arrangement mode, the deformation of the cables and the stresses of the cleats were obtained.ResultsA small cable electrodynamic force was observed in the positive-negative interlace arrangement, and the cable deformation was caused by electrodynamic forces. The maximum cleat deformation occurred at the position with the largest electrodynamic force, where the cleats were reinforced. Moreover, the mechanical characteristics of the cables and cleats under pulse-current excitation are described intuitively and quantitatively, providing theoretical support for the cable-laying scheme of the dipole power supply.
引用
收藏
页码:149 / 158
页数:10
相关论文
共 48 条