Novel configuration of dual-temperature condensation and dual-temperature evaporation high-temperature heat pump system: Carbon footprint, energy consumption, and financial assessment

被引:33
|
作者
Dai, Baomin [1 ]
Wang, Qi [1 ]
Liu, Shengchun [1 ]
Wang, Dabiao [2 ]
Yu, Liqi [1 ]
Li, Xinhai [1 ]
Wang, Yuanyuan [1 ]
机构
[1] Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin 300134, Peoples R China
[2] Fuzhou Univ, Natl Engn Res Ctr Chem Fertilizer Catalyst NERC CF, Sch Chem Engn, Fujian 350002, Peoples R China
关键词
High-temperature heat pump; Ejector; Dual-temperature condensation; Dual-temperature evaporation; Temperature matching; Waste heat recovery; CO2 REFRIGERATION CYCLE; LOW-GWP REFRIGERANTS; PERFORMANCE ANALYSIS; WORKING; R1234ZE(Z);
D O I
10.1016/j.enconman.2023.117360
中图分类号
O414.1 [热力学];
学科分类号
摘要
To achieve the goal of carbon neutrality for the application of industrial heating by recovery waste heat, the concept of dual-temperature condensation and dual-temperature evaporation is proposed for the hightemperature heat pump (HTHP) by introducing the techniques of ejector and two-stage compression. The energy, exergy, emission, and economic models are developed and optimized for the two new proposed systems. Then, the energy consumption, CO2 emissions and cost (LCC) during the whole life cycle are compared with five existing heat pumps and four traditional boilers. The highest coefficient of performance (COP) of heat pump (HP) can be got when intermediate water temperature on the heat sink side is optimum. The new proposed systems have better performances than the other five HTHPs. During the rated working condition, discharge temperature decreases by the use of dual-temperature condensation and dual-temperature evaporation HP with an ejector (EjDCDE). The optimal COP of Ej-DCDE-2 is 4.25, which is 11.55% and 1.43% higher than dual-temperature condensation and single-temperature evaporation HP and Ej-DCDE-1, respectively. The exergy destruction of Ej-DCDE-2 is reduced by 27.88% compared with basic heat pump (Base). Moreover, Ej-DCDE-2 has the lowest primary energy consumption of 14.62 ktoe, 22.19% and 25.09% lower than Base and oil-fired boiler during the total working period, respectively. In general, HTHPs have lower carbon dioxide, gaseous and particular pollutant emissions compared with boilers, especially Ej-DCDE-2. Finally, Ej-DCDE-2 has the minimum LCC, which is 14.67% and 11.75% less than Base and coal-fired boiler. Ej-DCDE-2 shows the most potential advantages of all the heating solutions and is recommended to replace traditional boilers for industrial heating.
引用
收藏
页数:25
相关论文
共 50 条
  • [1] Carbon dioxide heat pump for dual-temperature drinking fountain
    Yang Da-zhang
    Lu, Jing
    He Zhe-bin
    Huang Xiu-zhi
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 188 - 192
  • [2] Carbon dioxide heat pump for dual-temperature drinking fountain
    杨大章
    吕静
    何哲彬
    黄秀芝
    Journal of Central South University, 2009, 16 (S1) : 188 - 192
  • [3] Carbon dioxide heat pump for dual-temperature drinking fountain
    杨大章
    吕静
    何哲彬
    黄秀芝
    JournalofCentralSouthUniversityofTechnology, 2009, 16(S1) (S1) : 188 - 192
  • [4] Dual-Temperature Evaluation of a High-Temperature Insulation System for Liquid-Immersed Transformer
    Zhang, Xiaojing
    Ren, Lu
    Yu, Haichuan
    Xu, Yang
    Lei, Qingquan
    Li, Xin
    Han, Baojia
    ENERGIES, 2018, 11 (08)
  • [5] Energetic assessment on a dual-temperature evaporation refrigeration system for hydrogen pre-cooling
    Wu, Yimei
    Guo, Yanhua
    Yu, Hongxin
    Chen, Jianye
    Shao, Shuangquan
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 159 : 264 - 275
  • [6] Analysis of a dual-temperature air source heat pump cycle with an ejector
    Wang, Min
    Cheng, Yue
    Yu, Jianlin
    APPLIED THERMAL ENGINEERING, 2021, 193
  • [7] Life cycle techno-enviro-economic assessment of dual-temperature evaporation transcritical CO2 high-temperature heat pump systems for industrial waste heat recovery
    Dai, Baomin
    Liu, Chen
    Liu, Shengchun
    Wang, Dabiao
    Wang, Qilong
    Zou, Tonghua
    Zhou, Xuan
    APPLIED THERMAL ENGINEERING, 2023, 219
  • [8] A novel dual-temperature ejector-compression heat pump cycle-exergetic and economic analyses
    Liu, Jian
    Lin, Zhang
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 126 : 155 - 167
  • [9] DUAL-TEMPERATURE CHILLED WATER ENHANCES ENERGY EFFICIENCY, COMFORT
    Elmtoft, Erik
    Nazeri, Saied
    Davallou, Tg
    Welsh, Amber P.E.
    ASHRAE Journal, 2023, 65 (11) : 57 - 59
  • [10] Thermodynamic analysis of a new tandem dual-temperature air source heat pump with ejector
    Gao, Yuefen
    Yang, Wenjie
    Zhang, Yiying
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 168 : 307 - 317