A robust method for transmission line sequence parameter estimation using synchronized phasor measurements

被引:0
|
作者
Goklani, Hemantkumar [1 ]
Gajjar, Gopal [1 ]
Soman, S. A. [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Mumbai, India
关键词
Line parameter estimation; Percentage unbalance; Phasor measurement units (PMUs); INSTRUMENT TRANSFORMERS; CALIBRATION;
D O I
10.1016/j.epsr.2023.109616
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
We present a positive and zero sequence line parameter estimation method, that is robust to systematic errors in the instrument transformers, especially when they are within the specified tolerance as per standards. Using Monte Carlo simulations, it is shown that the proposed approach is robust and accurate for all operating conditions, specifically for short length and lightly loaded transmission lines. We also validate the proposed approach on 400 kV and 765 kV transmission lines using actual field phasor measurement unit (PMU) data. Further, estimation of zero sequence line parameter values is somewhat tricky because not enough unbalance exists during the normal operation of the power grid. Therefore, we quantify the minimum percentage unbalance needed in currents to determine zero sequence line parameter values within 1% tolerance. We also present the line length and line loading effects in estimating zero sequence line parameter values using simulations. Simulation and field PMU data results on 765 kV and 400 kV lines of different lengths and loading levels show that the proposed method estimates accurate positive and zero sequence line parameter values.
引用
收藏
页数:7
相关论文
共 50 条
  • [41] Instrument Transformer Calibration and Robust Estimation of Transmission Line Parameters Using PMU Measurements
    Goklani, Hemantkumar
    Gajjar, Gopal
    Soman, S. A.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2021, 36 (03) : 1761 - 1770
  • [42] Observability, Redundancy and Gross Error Processing in State Estimation Using SCADA and Synchronized Phasor Measurements
    Fantin, C. A.
    Massignan, J. A. D.
    Castillo, M. R.
    London, J. B. A., Jr.
    2015 IEEE EINDHOVEN POWERTECH, 2015,
  • [43] Real-time estimation of security from voltage collapse using synchronized phasor measurements
    Khatib, AR
    Nuqui, RF
    Ingram, MR
    Phadke, AG
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 582 - 588
  • [44] Strategic Use of Synchronized Phasor Measurements to Improve Network Parameter Error Detection
    Lin, Yuzhang
    Abur, Ali
    IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (05) : 5281 - 5290
  • [45] Correction of Phasor Measurements Independent of Transmission Line Parameters
    Xue, Ancheng
    Xu, Feiyang
    Xu, Jingsong
    Chow, Joe H.
    You, Hongyu
    Bi, Tianshu
    IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (01) : 346 - 356
  • [46] Transmission line parameter identification using PMU measurements
    Shi, Di
    Tylavsky, Daniel J.
    Koellner, Kristian M.
    Logic, Naim
    Wheeler, David E.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2011, 21 (04): : 1574 - 1588
  • [47] Novel Fault Location Algorithm for Transmission Line using Synchronized Measurements
    Hinge, Trupti P.
    Dambhare, Sanjay S.
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,
  • [48] Estimation of transmission loss components from phasor measurements
    Tuttelberg, Kaur
    Kilter, Jako
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 98 : 62 - 71
  • [49] Implementation of an Adaptive Voting Scheme using Synchronized Phasor Measurements
    Quint, Ryan D.
    Thomas, M. Kyle
    2012 PROCEEDINGS OF IEEE SOUTHEASTCON, 2012,
  • [50] Detection of Electromechanical Wave Propagation Using Synchronized Phasor Measurements
    Suryawanshi, Prakash
    Dambhare, Sanjay
    Pramanik, Ashutosh
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2014, 15 (01): : 69 - 75