A sensitive single-end DC line fault detection method for MMC-HVDC grids using reactor voltage ratio

被引:7
|
作者
Yu, Senlin [1 ]
Wang, Xiaoru [1 ]
Zhang, Xiao-Ping [2 ]
机构
[1] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 610031, Sichuan, Peoples R China
[2] Univ Birmingham, Dept Elect Elect & Syst Engn, Birmingham B15 2TT, England
关键词
MMC-HVDC grid; Line -mode voltage; Transient voltage; Mathematical morphology; High -resistance faults; NONUNIT PROTECTION; TRANSMISSION-LINES; SYSTEMS; IDENTIFICATION; SCHEME; WAVE;
D O I
10.1016/j.ijepes.2023.108953
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The fast, sensitive, and reliable primary protection method can ensure the continuous and reliable operation of the modular multilevel converter (MMC)-based HVDC grid during dc faults. This paper proposes a fault detection method based on the ratio of voltage integrals to improve the single-end method sensitivity to high-resistance faults. First, the reactor line-mode transient voltage caused by the initial traveling wave (TW) is analyzed in the fault component network. The exponential term of the voltage is independent of the fault resistance and can be reflected by the proposed voltage integral ratio. Next, the influence of subsequent TWs on the integral is analyzed. The partition time, selected by the mathematical morphology, is proposed to divide the voltage sampling data into two parts. Finally, the criterion using the ratio of the two-part voltage integral is proposed to detect internal faults. The +/- 500 kV bipolar MMC-HVDC grid built on PSCAD/EMTDC validates that the pro-posed method can fast identify internal faults, and the protected zone covers the whole line length. Smulation cases analyze the influence of the reactor and sampling frequencies on the proposed method. Moreover, the method is sensitive to high-resistance faults and can work under white noise and different wiring modes.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Single pole-to-ground fault location method for MMC-HVDC system using active pulse
    Bi, Tianshu
    Wang, Shuai
    Jia, Ke
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (02) : 272 - 278
  • [32] HVDC Line Protection Based on DC Filter Multifrequency Single-end Electric Parameters
    Dai Z.
    Zhao Z.
    Wang X.
    Guo Y.
    Qin H.
    Qiu H.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (02): : 702 - 713
  • [33] MMC-HVDC AC side line protection based on positive sequence fault component current ratio
    Huang, Hanqing
    Wang, Zengping
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (19) : 4375 - 4385
  • [34] Single Pole-to-Ground Fault Location Method for MMC-HVDC System Using Wavelet Decomposition and DBN
    Ye, Xinjie
    Lan, Sheng
    Xiao, Si-jie
    Yuan, Yongbin
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2021, 16 (02) : 238 - 247
  • [35] Single-ended Fault Location of Hybrid MMC-HVDC System Based on Active Detection
    Song G.
    Hou J.
    Guo B.
    Dianwang Jishu/Power System Technology, 2021, 45 (02): : 730 - 740
  • [36] Dc fault current calculation method in MMC-HVDC grid considering current-limiting devices
    Xu, Jianzhong
    Zhu, Sicheng
    Li, Chengyu
    Zhao, Chengyong
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 3188 - 3195
  • [37] Single-End Based Fault Location Method for VSC-HVDC Transmission Systems
    Elgamasy, Mahmoud M.
    Izzularab, Mohamed A.
    Zhang, Xiao-Ping
    IEEE ACCESS, 2022, 10 : 43129 - 43142
  • [38] Fault Current Calculation Method in Complex Frequency Domain of MMC-HVDC Grid Using Equivalent Model of Transmission Line
    Yu Y.
    Lyu Y.
    Deng W.
    Xu J.
    Zhao C.
    1600, Chinese Society for Electrical Engineering (40): : 7530 - 7538
  • [39] Single-end protection scheme for HVDC transmission line based on fault current propagation characteristics
    Dai W.
    Zhang H.
    Mou D.
    Liu L.
    Lin S.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (09): : 67 - 73and87
  • [40] Symmetrical Multi-pole MMC-HVDC with DC Fault Ride Through Capability Using HBSM
    Yadav, Ankit
    Singh, S. N.
    Das, S. P.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2023, 51 (10) : 991 - 1008