Cost-optimal control for a small energy community heated with dual source heat pump and district heating

被引:0
|
作者
Wang, Yangmin [1 ]
Zhang, Ruqian [1 ,2 ]
Merilainen, Altti [3 ]
Kosonen, Antti [3 ]
Jokisalo, Juha [1 ]
Kosonen, Risto [1 ,4 ]
机构
[1] Aalto Univ, Dept Mech Engn, Espoo, Finland
[2] Eindhoven Univ Technol, Dept Built Environm, Eindhoven, Netherlands
[3] Lappeenranta Lahti Univ Technol LUT, Dept Elect Engn, Lappeenranta, Finland
[4] Nanjing Tech Univ, Coll Urban Construct, Nanjing, Peoples R China
关键词
District heating; Dual source heat pump; Energy community; Hydrogen production waste heat; Smart control; SYSTEMS;
D O I
10.1016/j.enbuild.2025.115622
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Control strategies are crucial for reducing energy costs in hybrid heating systems using multiple energy carriers. The study analyzed the impact of three control strategies on energy usage and costs in a small energy community heated with a hybrid heating system. The system comprises a low-temperature heating network powered by a dual source heat pump and a district heating network. The control strategies included a low-temperature heatingprioritized and two cost-effective control strategies based on different electricity and district heating prices. The analysis was implemented by dynamic simulations based on the customized heating network model for the years 2022 and 2023. The cost-effective control strategy based on hourly electricity prices and the estimated cost of district heating produced by utilizing waste heat from hydrogen production resulted in the lowest annual costs. It reduced the annual costs by 25 % in 2022 and by 5 % in 2023 compared to the low-temperature heatingprioritized control strategy. The major difference between the two years was the variations in energy prices and the structure of the district heating power fees. As price differences between electricity and district heating in 2023 were less than those in 2022, the drop in energy costs upon adopting the cost-effective control strategy was smaller in 2023. Different power fee charging policies resulted in an increased power fee cost in 2023 even if the maximum district heating power slightly decreased. The increased power fee cost weakened the positive impact of energy cost saving brought by the cost-effective control strategies in the total costs.
引用
收藏
页数:14
相关论文
共 50 条
  • [41] A household dishwasher heated by a heat pump system using an energy storage unit with water as the heat source
    Bengtsson, Peder
    Berghel, Jonas
    Renstrom, Roger
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 49 : 19 - 27
  • [42] Energy evaluation of heating and cooling source use for surface water source heat pump system
    Long, Ji-Bo
    Li, Nian-Ping
    Ruan, Fang
    Huang, Si-Yi
    Huang, Ya-Bo
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2014, 41 (02): : 47 - 51
  • [43] Heating performance characteristics of a dual source heat pump using air and waste heat in electric vehicles
    Ahn, Jae Hwan
    Kang, Hoon
    Lee, Ho Seong
    Jung, Hae Won
    Baek, Changhyun
    Kim, Yongchan
    APPLIED ENERGY, 2014, 119 : 1 - 9
  • [44] Energy saving potentials of a photovoltaic assisted heat pump for hybrid building heating system via optimal control
    Zanetti, Ettore
    Aprile, Marcello
    Kum, Dongsuk
    Scoccia, Rossano
    Motta, Mario
    JOURNAL OF BUILDING ENGINEERING, 2020, 27
  • [45] Optimal supply water temperature control of water source heat pump
    Palahanska-Mavrov, M.
    Wang, G.
    Liu, M.
    Solar Engineering 2005, 2006, : 317 - 323
  • [46] A model predictive control strategy of global optimal dispatch for a combined solar and air source heat pump heating system
    Zhao, Jing
    Li, Yawen
    Qin, Yabing
    Liu, Dehan
    Wu, Xia
    Zhang, Xinyu
    Cheng, Xiangping
    Wu, Yanyuan
    APPLIED THERMAL ENGINEERING, 2025, 258
  • [47] Quasi-dynamic energy-saving judgment of electric-driven seawater source heat pump district heating system over boiler house district heating system
    Haiwen, Shu
    Duanmu, Lin
    Xiangli, Li
    Yingxin, Zhu
    ENERGY AND BUILDINGS, 2010, 42 (12) : 2424 - 2430
  • [48] Factor Analysis for Evaluating Energy-Saving Potential of Electric-Driven Seawater Source Heat Pump District Heating System Over Boiler House District Heating System
    Shu, Haiwen
    Wang, Hongbin
    Lin Duanmu
    Li, Xiangli
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 2: HVAC&R COMPONENT AND ENERGY SYSTEM, 2014, 262 : 93 - 100
  • [49] Heating New Housing Areas with District Heat from Central Heat Pump Heating Plants Using Single or Dual Agent Heat Pumps.
    Mucic, Vinko
    Fernwarme international, 1984, 13 (04): : 219 - 221
  • [50] A comprehensive assessment of cost-optimal heat supply to new low-energy building areas in Sweden
    Sandvall, Akram
    Romanchenko, Dmytro
    Karlsson, Kenneth
    ENERGY REPORTS, 2023, 10 : 202 - 212