Interface Polarization Behaviors of Water Tree Aged XLPE Cable During PDC Measurement

被引:0
|
作者
Zhou, Kai [1 ]
Yuan, Hao [1 ]
Li, Yuan [1 ]
Li, Shiyu [2 ]
机构
[1] Sichuan Univ, Coll Elect Engn, Chengdu 610065, Peoples R China
[2] State Grid Leshan Power Supply Co, Leshan 614299, Peoples R China
基金
中国国家自然科学基金;
关键词
Trees; -; insulation; Aging; Dielectrics; Current measurement; Cables; Cable insulation; Polarization; Cross-linked polyethylene (XLPE) cable; interface polarization; polarization and depolarization current (PDC); water tree; SPACE-CHARGE DISTRIBUTION; DIELECTRIC-SPECTROSCOPY; TRANSFORMER INSULATION; ACTIVATION-ENERGY; FREQUENCY-DOMAIN; TIME;
D O I
10.1109/TDEI.2024.3453237
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Understanding the dielectric response of water tree aged cross-linked polyethylene (XLPE) has great significance in diagnosing the insulation failure of power cables. In this work, the polarization and depolarization current (PDC) characteristics of XLPE cables with different degrees of water tree aging are investigated. The conduction current, calculated as the difference between the PDCs, is analyzed. A novel phenomenon is that the conduction currents of aged samples increase first and then gradually decrease to a stable level over time. A model based on the nonlinear dielectric response theory of water trees is established to explain this behavior, attributing it to asymmetric charge accumulation and dissipation at the water tree-XLPE interface during the charging and discharging stages. Further analysis reveals the characteristics of the interface polarization current component during PDC measurement. During polarization, the interface polarization current first increases and then decreases, while the relaxation time constant first decreases and then increases. During depolarization, the interface polarization current gradually decreases with the increased relaxation time constant. To evaluate the degree of water tree aging in XLPE cables, the interfacial polarization coefficient K is defined. A K value greater than 1 indicates the presence of water trees in the cable. Moreover, the K value increases with the degree of water tree aging, and increasing the test voltage can enhance detection.
引用
收藏
页码:967 / 974
页数:8
相关论文
共 50 条
  • [41] Water Tree Deterioration Diagnosis for 10 kV XLPE cable based on Residual Charge Method
    Du, B. X.
    Huo, Z. X.
    Li, H. B.
    Gao, Y.
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 417 - 420
  • [42] DC voltage and AC voltage characteristics of current flowing in water tree degraded XLPE cable
    Kamohara H.
    Kudo Y.
    Ehara Y.
    IEEJ Transactions on Fundamentals and Materials, 2018, 138 (09) : 463 - 470
  • [43] Correlation between the AC breakdown strength and spacecharge distribution of water tree aged XLPE
    Lee, JH
    Cho, SM
    Song, IK
    1998 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 1998, : 657 - 660
  • [44] Location of water tree degraded point along XLPE cable line using DC voltage
    Suenaga, Kiyoka
    Uchida, Katsumi
    Hozumi, Naohiro
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1224 - +
  • [45] PDC Branch Parameter Characteristics of Water Tree Aged Cables Based on the Microstructural Characteristics of Water Trees
    Ma X.
    Li K.
    Zhou K.
    Li Y.
    Huang K.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (02): : 716 - 723
  • [46] Pulse response measurement aiming for locating water tree degradation in XLPE cables
    Hiei, Susumu
    Hozumi, Naohiro
    Kurihara, Takashi
    Okamoto, Tatsuki
    Uchida, Katsumi
    Tsuji, Taizo
    IEEJ Transactions on Fundamentals and Materials, 2011, 131 (06): : 439 - 444
  • [47] Investigation on the evolution of discharge behaviors at XLPE-SiR interface of 10 kV cable joints under moisture conditions
    Lu, Daiqiang
    Hu, Ran
    Zhao, Yifeng
    Zeng, Yanqi
    Liu, Gang
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 232
  • [49] Measurement of Residual Charge using Pulse Voltages for Water Tree Degraded XLPE Cables Diagnosis
    Kurihara, Takashi
    Okamoto, Tatsuki
    Kim, Myong Hwan
    Hozumi, Naohiro
    Tsuji, Taizo
    Uchida, Katsumi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 321 - 330
  • [50] Correlation between AC breakdown strength and low frequency dielectric loss of water tree aged XLPE cables
    Norwegian Univ of Science and, Technology , Trondheim, Norway
    IEEE Trans Power Delivery, 1 (40-45):