Interface Polarization Behaviors of Water Tree Aged XLPE Cable During PDC Measurement

被引:0
|
作者
Zhou, Kai [1 ]
Yuan, Hao [1 ]
Li, Yuan [1 ]
Li, Shiyu [2 ]
机构
[1] Sichuan Univ, Coll Elect Engn, Chengdu 610065, Peoples R China
[2] State Grid Leshan Power Supply Co, Leshan 614299, Peoples R China
基金
中国国家自然科学基金;
关键词
Trees; -; insulation; Aging; Dielectrics; Current measurement; Cables; Cable insulation; Polarization; Cross-linked polyethylene (XLPE) cable; interface polarization; polarization and depolarization current (PDC); water tree; SPACE-CHARGE DISTRIBUTION; DIELECTRIC-SPECTROSCOPY; TRANSFORMER INSULATION; ACTIVATION-ENERGY; FREQUENCY-DOMAIN; TIME;
D O I
10.1109/TDEI.2024.3453237
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Understanding the dielectric response of water tree aged cross-linked polyethylene (XLPE) has great significance in diagnosing the insulation failure of power cables. In this work, the polarization and depolarization current (PDC) characteristics of XLPE cables with different degrees of water tree aging are investigated. The conduction current, calculated as the difference between the PDCs, is analyzed. A novel phenomenon is that the conduction currents of aged samples increase first and then gradually decrease to a stable level over time. A model based on the nonlinear dielectric response theory of water trees is established to explain this behavior, attributing it to asymmetric charge accumulation and dissipation at the water tree-XLPE interface during the charging and discharging stages. Further analysis reveals the characteristics of the interface polarization current component during PDC measurement. During polarization, the interface polarization current first increases and then decreases, while the relaxation time constant first decreases and then increases. During depolarization, the interface polarization current gradually decreases with the increased relaxation time constant. To evaluate the degree of water tree aging in XLPE cables, the interfacial polarization coefficient K is defined. A K value greater than 1 indicates the presence of water trees in the cable. Moreover, the K value increases with the degree of water tree aging, and increasing the test voltage can enhance detection.
引用
收藏
页码:967 / 974
页数:8
相关论文
共 50 条
  • [1] Interface Polarization Characteristics of Water Tree Aged XLPE Cables Based on Polarization and Depolarization Current Method
    Yin Y.
    Zhou K.
    Li S.
    Chen Z.
    Zhang F.
    Zhou, Kai (zhoukai_scu@163.com), 1600, Chinese Machine Press (35): : 2643 - 2651
  • [2] Diagnosis and restoration of water tree aged XLPE cable materials
    Faremo, H
    Ildstad, E
    CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 596 - 599
  • [3] Polarization and Depolarization Current Measurement of Aged HVDC XLPE Model Cable
    Lee, Seung-Won
    Kim, Hae-Jong
    Park, Byung-Bae
    Ryu, Hee-Suk
    Oh, Sang-Soo
    Cho, Jeon-Wook
    Nam, Jin-Ho
    PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 85 - 88
  • [4] Investigation on water treeing behaviors of thermally aged XLPE cable insulation
    Kim, Chonung
    Jin, Zhijian
    Huang, Xingyi
    Jiang, Pingkai
    Ke, Qingquan
    POLYMER DEGRADATION AND STABILITY, 2007, 92 (04) : 537 - 544
  • [5] Diagnosing Method for Water Tree Aging on XLPE Cable Based on Continuous PDC Test Method
    Lin S.
    Zhou K.
    Yin Y.
    Li M.
    Gong W.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (20): : 6764 - 6772
  • [6] OXIDATION AND WATER TREE FORMATION IN SERVICE-AGED XLPE CABLE INSULATION
    GARTON, A
    BAMJI, S
    BULINSKI, A
    DENSLEY, J
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1987, 22 (04): : 405 - 412
  • [7] Insulation Status Diagnosis of XLPE Cable Based on Polarization and Depolarization Current (PDC)
    Zhao, Aixuan
    Wang, Yanbo
    Zhang, Xing
    Deng, Junbo
    Zhang, Guanjun
    Tao, Shiyan
    Wu, Linlin
    2015 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2015,
  • [8] Correlation between space charge distribution and water-tree location in aged XLPE cable
    Suzuki, K
    Tanaka, Y
    Takada, T
    Ohki, Y
    Takeya, C
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (01) : 78 - 81
  • [9] WATER TREE RETARDANT XLPE CABLE USING VLDPE
    ASANO, A
    TAKAHASHI, T
    MAEDA, K
    NIWA, T
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) : 553 - 558
  • [10] DEVELOPMENT OF NEW WATER TREE SUPPRESSIVE XLPE CABLE
    WATANABE, K
    YAGYU, H
    SEKII, Y
    MARUMO, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) : 27 - 33