Numerical investigation on air-side heat transfer enhancement of wavy finned tube air cooler for underground tunnels

被引:0
|
作者
Wang, Yangjie [1 ]
Cai, Tianqi [1 ]
Niu, Pengxiang [2 ]
Fan, Wenbo [2 ]
Wang, Yijiang [1 ]
机构
[1] China Univ Min & Technol, Sch Mech & Civil Engn, State Key Lab Intelligent Construct & Hlth Operat, Xuzhou 221116, Peoples R China
[2] China Coal Construct Grp Corp Ltd, Beijing 102218, Peoples R China
基金
中国国家自然科学基金;
关键词
Wavy finned tube air cooler; Heat transfer enhancement; Vortex generator; Slit perforation; Thermal-hydraulic performance; THERMAL-HYDRAULIC PERFORMANCE; WINGLET VORTEX GENERATORS; FIELD SYNERGY PRINCIPLE; FRICTION CHARACTERISTICS; FLUID-FLOW; LONGITUDINAL VORTICES; DELTA WINGLETS; CROSS-FLOW; PLAIN FIN; EXCHANGERS;
D O I
10.1016/j.applthermaleng.2025.126061
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air coolers used in underground tunnels are traditionally bare tube units with limited thermal performance, negatively impacting refrigeration systems' energy efficiency. To enhance heat transfer efficiency, this study explores the application of finned-tube air coolers in underground tunnels or shafts with low dust concentrations during construction. The potential of wavy finned-tube air coolers to improve thermal performance under high wind speed conditions is investigated using numerical simulations. The RNG k-epsilon model was used to numerically investigate the effects of fin and finned tube design parameters, delta-wing vortex generator (VG-D) and slit configurations on the thermal-hydraulic performance of wavy finned tube air cooler. Key performance indicators, including the Nusselt number (Nu), friction factor (f), fin efficiency and composite performance factor (JF) are utilized to assess the enhancements. The results demonstrate that augmenting the height and thickness of wavy fins and the longitudinal tube pitch leads to improvements in both Nu and f. Reducing the transverse tube pitch enhances the Nu, fin efficiency and JF. Moreover, the integration of VG-D boosts Nu by 10.1% and JF by 7.3% compared to the base design. The addition of top-bottom slit perforations further augments the Nu and fin efficiency by 10.3%, 4.9%, and reduces the JF by 2.9%. Empirical correlations for the air-side performance of wavy finned-tube air coolers are also proposed, with deviation error less than 15%. These results can offer valuable insights for the design of high-efficiency wavy finned air coolers specifically suited for underground tunnel applications.
引用
收藏
页数:20
相关论文
共 50 条
  • [1] Numerical investigation of effect of tube shape on air-side heat transfer and pressure drop characteristics of a finned tube heat exchanger
    Min, JC
    Webb, RL
    Peng, XF
    HEAT TRANSFER SCIENCE AND TECHNOLOGY 2000, 2000, : 719 - 724
  • [2] Effects of biofouling on air-side heat transfer and pressure drop for finned tube heat exchangers
    Pu, Hui
    Ding, Guo-liang
    Ma, Xiao-kui
    Hu, Hai-tao
    Gao, Yi-feng
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05): : 1032 - 1040
  • [3] A numerical study on the air-side heat transfer of perforated finned-tube heat exchangers with large fin pitches
    Liu, Xiaoqin
    Yu, Jianlin
    Yan, Gang
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 100 : 199 - 207
  • [4] Experimental Heat Transfer Investigation of Tube Row Effects at Air-Side Heat Exchanger with Serrated Finned-Tubes
    Hofmann, Rene
    Frasz, Friedrich
    Ponweiser, Karl
    PROCEEDINGS OF THE 6TH IASME/WSEAS INTERNATIONAL CONFERENCE ON HEAT TRANSFER, THERMAL ENGINEERING AND ENVIRONMENT (HTE'08), PTS I AND II: NEW ASPECTS OF HEAT TRANSFER, THERMAL ENGINEERING AND ENVIRONMENT, 2008, : 193 - +
  • [5] Air-side performance of a wavy-finned-tube direct expansion cooling and dehumidifying air coil
    Huzayyin, A. S.
    Nada, S. A.
    Elattar, H. F.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02): : 230 - 244
  • [6] Experimental investigation on the air-side flow and heat transfer characteristics of 3-D finned tube bundle
    Chen, Zi-yong
    Cheng, Min
    Liao, Qiang
    Ding, Yu-dong
    Zhang, Jun-nan
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 131 : 506 - 516
  • [7] AN EXPERIMENTAL INVESTIGATION ON AIR-SIDE PERFORMANCES OF FINNED TUBE HEAT EXCHANGERS FOR INDIRECT AIR-COOLING TOWER
    Du, Xueping
    Yin, Yantao
    Zeng, Min
    Yu, Pengqing
    Wang, Qiuwang
    Dong, Zhaoyi
    Chen, Yitung
    THERMAL SCIENCE, 2014, 18 (03): : 863 - 874
  • [8] Air inlet angle influence on the air-side heat transfer and flow friction characteristics of a finned oval tube heat exchanger
    Tang, Linghong
    Du, Xueping
    Pan, Jie
    Sunden, Bengt
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 145
  • [9] Air-side flow and heat transfer characteristics of flat and slotted finned tube bundles with various tube pitches
    Kong, Y. Q.
    Yang, L. J.
    Du, X. Z.
    Yang, Y. P.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 99 : 357 - 371
  • [10] Experimental and Numerical Investigation of the Air Side Heat Transfer of a Finned Tubes Heat Exchanger
    Petrik, Mate
    Szepesi, Gabor
    PROCESSES, 2020, 8 (07)