Splitting method for grounding grids corrosion diagnosis using a block dividing approach

被引:0
|
作者
Ni, Yun-Feng [1 ]
Liu, Jian [1 ,2 ]
Wang, Shu-Qi [1 ]
Li, Teng [1 ]
Li, Zhi-Zhong [2 ]
Wang, Sen [2 ]
机构
[1] School of Electrical Engineering, Xi'an University of Science and Technology, Xi'an 710054, China
[2] Shaanxi Electric Power Research Institute, Xi'an 710054, China
来源
关键词
Efficiency - Corrosion - Circuit theory;
D O I
暂无
中图分类号
学科分类号
摘要
To benefit the corrosion diagnosis, generally, the spiltting method of circuit theory is used which can divide the larger ground grid into several small scaled sub-grids to diagnosis by several touchable nodes. The testability for branches can be changed, by adopting the traditional splitting method, namely, along with the touchable nodes splitted. First, the influence of testability for braches is analyzed. The concepts of blocks and their prototypes, uncertain-branch groups and their prototypes, projection of blocks and part of touchable nodes are defined. Based on the mode of block, a new approach of grounding grids corrosion diagnosis by blocks is put forward. According to the desired corrosion diagnosis area, the blocks together with their projections and the parts of touchable nodes, which participate in the diagnosis are determined. According to the testing data of the corresponding parts, the resistances of intrinsic branches in a block can be determined by a linear least square method, thereby, the resistances of clear branches in the block can be worked out. The ranges of resistances of uncertain-branches in the block are also evaluated by a dichotomy algorithm. With the proposed approach, a grounding grid can be divided into several small scaled sub-grids. As a result, the efficiency is improved and the cross-interferences are reduced. An experimental grounding grid with thirty-eight branches is used as an example. The results of corrosion diagnosis show that the proposed approaches are feasible and only a few tests are needed to meet the requirements of diagnosing a certain part of the grounding grid, and the efficiency of corrosion diagnosis can be improved rapidly by the method.
引用
收藏
页码:2250 / 2260
相关论文
共 50 条
  • [21] Study on the evaluation method of substation soil to the corrosion performance of grounding grids
    Gao, Bing
    Wei, Minglei
    Zhou, Wenbo
    BASIC & CLINICAL PHARMACOLOGY & TOXICOLOGY, 2019, 125 : 111 - 112
  • [22] Grounding grids corrosion diagnosis automation test system and its key techniques
    Cheng, Hong-Li
    Yang, Yan-Na
    Liu, Jian
    Ni, Yun-Feng
    Wang, Sen
    Liu, Shu-Lin
    Li, Zhi-Zhong
    Cao, Di-Di
    Lu, Wei
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (12): : 2989 - 2994
  • [23] Influence of touchable nodes deviation on grounding grids corrosion diagnosis and its correction
    Liu, Jian
    Ni, Yun-Feng
    Lu, Wei
    Wang, Sen
    Li, Zhi-Zhong
    Gaodianya Jishu/High Voltage Engineering, 2008, 34 (11): : 2349 - 2354
  • [24] The Neural Network Method of Corrosion Diagnosis for Grounding Grid
    Hou, Zai-En
    Duan, Fu-Jian
    Zhang, Ke-Cun
    INTERNATIONAL ELECTRONIC CONFERENCE ON COMPUTER SCIENCE, 2008, 1060 : 353 - +
  • [25] Study on corrosion fracture diagnosis method of grounding wire of tower grounding device
    Zhang, Zhanlong
    Ye, Huarui
    Dan, Yihua
    Duanmu, Ziang
    Deng, Jun
    Gao, Chengfeng
    Gan, Pengfei
    MEASUREMENT, 2020, 166
  • [26] Design and application of testing magnetic field system for corrosion diagnosis of grounding grids in substation
    Liu, Yang
    Cui, Xiang
    Zhao, Zhibin
    Li, Lin
    Chen, Jianjun
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2009, 24 (01): : 176 - 182
  • [27] A new approach of testability evaluation for grounding grid corrosion diagnosis
    Liu Jian
    Wang Shuqi
    Ni Yunfeng
    Li Zhizhong
    Wang Sen
    2008 THIRD INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1-6, 2008, : 804 - 808
  • [28] Method for calculating the ground resistance of grounding grids using FEM
    Güemes, JA
    Hernando, FE
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 595 - 600
  • [29] New model of corrosion diagnosis for grounding grids based on constrained total least squares algorithm
    Zhang, Yingjiao
    Luo, Xianjue
    Niu, Tao
    Liu, Liqiang
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2010, 44 (10): : 110 - 115
  • [30] Computation method of magnetic field inverse problem on grounding grids fault diagnosis
    He, Wei
    Shi, Qingyan
    Yang, Fan
    Zhang, Ruiqiang
    Chongqing Daxue Xuebao/Journal of Chongqing University, 2012, 35 (09): : 80 - 85