Performance and Applicability Analysis of Indirect Evaporative Cooling Units in Data Centers Across Various Humidity Regions

被引:0
|
作者
Wei, Qian [1 ]
Lu, Jun [1 ]
Xia, Xiaoping [2 ]
Zhang, Bin [3 ]
Ying, Xiang [1 ]
Li, Leihong [1 ]
机构
[1] Chongqing Univ, Sch Civil Engn, Chongqing 400045, Peoples R China
[2] Southern Power Grid Integrated Energy Co, Guangzhou 510635, Peoples R China
[3] Yue Neng Bldg, 45-6 Tianhe Rd, Guangzhou 510075, Peoples R China
关键词
data center; fresh-air indirect heat transfer; coefficient of performance; indirect evaporative cooling; power-usage effectiveness;
D O I
10.3390/buildings14113623
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Indirect evaporative cooling (IEC), which utilizes natural cooling sources, is an advanced and promising technology to reduce the energy consumption of cooling systems in a data center (DC). This study presents a model of an IEC air-conditioning unit in a DC using TRNSYS simulation software validated using actual operational data to investigate the adaptability of IEC units in data centers located in regions with varying humidity levels, providing a reference for their application and promotion in DCs. Based on this premise, the authors analyzed the meteorological characteristics of Urumqi (a dry region), Beijing (a region with medium humidity), and Shanghai (a region with high humidity), which are representative cities in different humidity zones. The analysis identified the annual operating hours of the unit's three operation modes, including fresh-air indirect heat transfer (FAIHT), IEC, and hybrid. Simultaneously, the authors conducted a simulation of the unit's yearly energy consumption and determined time change curves for annual energy consumption, hourly coefficient of performance (COP) throughout the year, and mechanical cooling in various locations. The results indicate that IEC air-conditioning systems are highly effective in promoting the efficiency of data centers in various humidity regions. Dry locations demonstrate the greatest adaptability, followed by regions with medium humidity and, finally, regions with high humidity. The findings indicate that IEC units provide significant energy efficiency and cost-effectiveness when deployed in typical urban DCs across various humidity zones in China. The average annual power-usage effectiveness (PUE) of each city's DC utilizing the unit is less than 1.3, and the unit's annual operational cost savings exceed 30%.
引用
收藏
页数:25
相关论文
共 34 条
  • [21] DYNAMIC ANALYSIS OF HYBRID COOLING DATA CENTERS SUBJECTS TO THE FAILURE OF CRAC UNITS.
    Gao, Tianyi
    Samadiani, Emad
    Schmidt, Roger
    Sammakia, Bahgat
    PROCEEDINGS OF THE ASME INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, 2013, VOL 2, 2014,
  • [22] Analysis of indirect evaporative cooler performance under various heat and mass exchanger dimensions and flow parameters
    Adam, Abdalazeem
    Han, Dong
    He, Weifeng
    Amidpour, Majid
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 176
  • [23] Numerical study on performance of a hybrid indirect evaporative cooling heat recovery heat pump ventilator as applied in different climatic regions of China
    Wang, Jue
    Lu, Jun
    Li, Wuyan
    Zeng, Cheng
    Shi, Fenghao
    ENERGY, 2022, 239
  • [24] The performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit
    Huang, Xiang
    Wu, Sheng
    Fan, Li-juan
    Wang, Chao
    Wu, Jun-mei
    2010 4TH INTERNATIONAL CONFERENCE ON BIOINFORMATICS AND BIOMEDICAL ENGINEERING (ICBBE 2010), 2010,
  • [25] The performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit
    Huang, Xiang
    Wu, Sheng
    Fan, Li-juan
    Wang, Chao
    Wu, Jun-mei
    2010 4TH INTERNATIONAL CONFERENCE ON BIOINFORMATICS AND BIOMEDICAL ENGINEERING (ICBBE 2010), 2010,
  • [26] THE ENERGY AND EXERGY ANALYSIS ON THE PERFORMANCE OF COUNTER-FLOW HEAT AND MASS EXCHANGER FOR M-CYCLE INDIRECT EVAPORATIVE COOLING
    Wang, Lei
    Zhan, Chonghong
    Zhang, Jianli
    Zhao, Xudong
    THERMAL SCIENCE, 2019, 23 (02): : 613 - 623
  • [27] Matching analysis between the heating/cooling capacity of PVT heat pumps and the heating/cooling demand of residential buildings across various regions in China
    Lu, Shixiang
    Li, Yongkang
    Zhang, Jili
    Wang, Fang
    Yuan, Pengli
    JOURNAL OF BUILDING ENGINEERING, 2024, 98
  • [28] The Analysis of Modifications in Cooling Systems for High-Performance Data Centers. A Case Study
    Rusowicz, Artur
    Rucinski, Adam
    Laskowski, Rafal
    10TH INTERNATIONAL CONFERENCE ENVIRONMENTAL ENGINEERING (10TH ICEE), 2017,
  • [29] Analytical and experimental comparison of various in-row cooling systems for data centers: An exergy, exergoeconomic, and economic analysis
    Baghsheikhi, Mostafa
    Haftlangi, Pouria
    Mohammadi, Majid
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2025, 57
  • [30] Performance evaluation and financial analysis of applying hybrid renewable systems in cooling unit of data centers - A case study
    Jahangir, Mohammad Hossein
    Mokhtari, Reza
    Mousavi, Seyed Ali
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2021, 46