Impact of Adding Fast Switching Fault Current Limiter (FSFCL) to the Neutral Point of 220 kV Transformer

被引:0
|
作者
Dai, Lujian [1 ]
Zhao, Jun [1 ]
Guo, Meng [1 ]
Gao, Shuguo [1 ]
Xiang, Chenmeng [1 ]
Wei, Bin [2 ]
Qin, Weiqi [2 ]
Ma, Guoming [2 ]
Tian, Yuan [1 ]
机构
[1] State Grid Hebei Elect Power Co, Elect Power Res Inst, Shijiazhuang 050000, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
关键词
asymmetrical short-circuit fault; transformer neutral point; fast switching fault current limiter; neutral point overvoltage; relay protection; short-circuit current calculation;
D O I
10.3390/en17194862
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In recent years, as the power grid continues to expand, the issue of asymmetrical short-circuit currents exceeding limits on the 220 kV medium-voltage side has become increasingly severe, and traditional current-limiting methods have certain limitations. Therefore, this paper explores the potential benefits and feasibility of installing a Fast Switching Fault Current Limiter (FSFCL) at the neutral point of a 220 kV transformer to effectively limit asymmetrical short-circuit currents on the medium-voltage side. The paper first analyzes the current-limiting performance of the FSFCL under different installation configurations, transformer operating conditions, and fault conditions through theoretical calculations. Subsequently, through simulation studies, the impact of different limiting reactance values on the overvoltage effect at the neutral point is discussed. The results show that the installation of the FSFCL has a significant effect on suppressing the asymmetrical short-circuit current on the medium-voltage side of the transformer, but this measure has also led to an increase in the voltage at the grounded neutral point. Finally, taking the No. 2 main transformer of a certain 220 kV substation as an example, to achieve the expected current-limiting effect, the limiting reactance value of the FSFCL needs to be at least 4 ohms. At this reactance value, the overvoltage level at the neutral point remains well below the withstand limit of its insulating material. Additionally, given the existing overvoltage protection devices at the neutral point, no further overvoltage protection measures are required.
引用
收藏
页数:14
相关论文
共 26 条
  • [21] Discrimination between internal fault and magnetising inrush currents of power transformers in the presence of a superconducting fault current limiter applied to the neutral point
    Sahebi, Ali
    Samet, Haidar
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2016, 10 (05) : 537 - 544
  • [22] Design, Fabrication, and Operation of the Cryogenic System for a 220 kV/300 MVA Saturated Iron-Core Superconducting Fault Current Limiter
    Hong, H.
    Su, B.
    Niu, G. J.
    Cui, J. B.
    Tian, B.
    Li, Q.
    Wang, L. Z.
    Wang, Z. H.
    Zhang, K.
    Xin, Y.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2014, 24 (05)
  • [23] Simulation model of resistor-type superconducting fault current limiter and its impact on 10 kV distribution network
    Chen, Y. (merrycyj@163.com), 1600, Electric Power Automation Equipment Press (33):
  • [24] Design, Fabrication, and Operation of the Cryogenic System for a 220kV/300MVA Saturated Iron-Core Superconducting Fault Current Limiter
    Hong, Hui
    Niu, Guo Jun
    Cui, Ji Bin
    Tian, Bo
    Li, Qiang
    Wang, Li Zhong
    Xin, Ying
    Su, Bin
    Zhang, Zhi Hui
    Zhang, Kai
    2013 IEEE International Conference on Applied Superconductivity and Electromagnetic Devices (ASEMD), 2013, : 508 - 509
  • [25] Electrical distribution networks with isolated neutral point - the value of the capacitive earth-fault current and impact on the operation of these networks
    Nohacova, Lucie
    Vykuka, Roman
    Zak, Frantisek
    Kropacek, Vaclav
    PROCEEDINGS OF THE 8TH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRICAL POWER ENGINEERING (ELEKTROENERGETIKA 2015), 2015, : 77 - 80
  • [26] Direct Impact from The Through Fault Current of 150/20 kV Transformer to Its Dissolved Gas Analysis test in PT. PLN (Persero) TJBB APP Durikosambi
    Shaulagara, Shaga
    Ihsan, Muhammad
    Mustafa, Fajli
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 253 - 258