Impact of Adding Fast Switching Fault Current Limiter (FSFCL) to the Neutral Point of 220 kV Transformer

被引:0
|
作者
Dai, Lujian [1 ]
Zhao, Jun [1 ]
Guo, Meng [1 ]
Gao, Shuguo [1 ]
Xiang, Chenmeng [1 ]
Wei, Bin [2 ]
Qin, Weiqi [2 ]
Ma, Guoming [2 ]
Tian, Yuan [1 ]
机构
[1] State Grid Hebei Elect Power Co, Elect Power Res Inst, Shijiazhuang 050000, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
关键词
asymmetrical short-circuit fault; transformer neutral point; fast switching fault current limiter; neutral point overvoltage; relay protection; short-circuit current calculation;
D O I
10.3390/en17194862
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In recent years, as the power grid continues to expand, the issue of asymmetrical short-circuit currents exceeding limits on the 220 kV medium-voltage side has become increasingly severe, and traditional current-limiting methods have certain limitations. Therefore, this paper explores the potential benefits and feasibility of installing a Fast Switching Fault Current Limiter (FSFCL) at the neutral point of a 220 kV transformer to effectively limit asymmetrical short-circuit currents on the medium-voltage side. The paper first analyzes the current-limiting performance of the FSFCL under different installation configurations, transformer operating conditions, and fault conditions through theoretical calculations. Subsequently, through simulation studies, the impact of different limiting reactance values on the overvoltage effect at the neutral point is discussed. The results show that the installation of the FSFCL has a significant effect on suppressing the asymmetrical short-circuit current on the medium-voltage side of the transformer, but this measure has also led to an increase in the voltage at the grounded neutral point. Finally, taking the No. 2 main transformer of a certain 220 kV substation as an example, to achieve the expected current-limiting effect, the limiting reactance value of the FSFCL needs to be at least 4 ohms. At this reactance value, the overvoltage level at the neutral point remains well below the withstand limit of its insulating material. Additionally, given the existing overvoltage protection devices at the neutral point, no further overvoltage protection measures are required.
引用
收藏
页数:14
相关论文
共 26 条
  • [1] Tank-type Fast Switching of 500 kV Fast-switching Fault Current Limiter
    Wang W.
    Zhao Y.
    Xu Y.
    Lü W.
    Yang B.
    Fang T.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (02): : 803 - 811
  • [2] Development of a 220 kV/300 MVA superconductive fault current limiter
    Xin, Y.
    Gong, W. Z.
    Hong, H.
    Gao, Y. Q.
    Niu, X. Y.
    Zhang, J. Y.
    Sun, Y. W.
    Ren, A. L.
    Wang, H. Z.
    Zhang, L. F.
    Li, Q.
    Wei, Z. Q.
    Wang, L. Z.
    Cui, J. B.
    Niu, G. J.
    Xiong, Z. Q.
    SUPERCONDUCTOR SCIENCE & TECHNOLOGY, 2012, 25 (10):
  • [3] The effects of a fast switching fault current limiter on distance protection
    Henry, S
    Baldwin, T
    Steurer, M
    PROCEEDINGS OF THE 35TH SOUTHEASTERN SYMPOSIUM ON SYSTEM THEORY, 2003, : 264 - 268
  • [4] Research on Fault Current Limiter Based on Fast Switching Technology
    Jiang, Huating
    Qin, Lijun
    2018 3RD INTERNATIONAL CONFERENCE ON CONTROL AND ROBOTICS ENGINEERING (ICCRE), 2018, : 196 - 200
  • [5] Dynamics modeling of fast transformer type fault current limiter loaded with HTSC
    Konin, Aleksandr M.
    Kiprijanovic, Oleg L.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2007, 17 (04) : 3853 - 3856
  • [6] Overvoltage of 110kV, 220kV Transformer Neutral Point and Its Protection Analysis
    Li Yining
    Liu Junyi
    Kuang Shi
    Xie Wenbing
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [7] Limiting characteristics of the superconducting fault current limiter applied to the neutral line of conventional transformer
    Im, I. G.
    Choi, H. S.
    Jung, B. I.
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2013, 494 : 339 - 343
  • [8] First Russian 220 kV Superconducting Fault Current Limiter (SFCL) For Application in City Grid
    Moyzykh, Mikhail
    Gorbunova, Daria
    Ustyuzhanin, Petr
    Sotnikov, Dmitry
    Baburin, Kirill
    Maklakov, Alexander
    Magommedov, Eldar
    Shumkov, Alexey
    Telnova, Anastasia
    Shcherbakov, Vladimir
    Kumarov, Damir
    Sabirov, Lenar
    Medovik, Maria
    Kadyrbaev, Artem
    Alexandrov, Sergey
    Mikoyan, Ivan
    Samoilenkov, Sergey
    Vavilov, Andrey
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (05)
  • [9] Development and test of a 220 kV/1.5 kA resistive type superconducting fault current limiter
    Dai, Shaotao
    Ma, Tao
    Xue, Chi
    Zhao, Lianqi
    Huang, Yong
    Hu, Lei
    Wang, Bangzhu
    Zhang, Teng
    Xu, Xiaofei
    Cai, Lingling
    Chen, Hao
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2019, 565
  • [10] Fast-switching High Voltage Fault Current Limiter with Multiple Breakers
    Lyu W.
    Liu Y.
    Zhou Q.
    Fang T.
    Wang Z.
    Zhang G.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (23): : 234 - 239