Fire Extinguishing Effect of Water Mist with Different Pressures on LFP Battery Module

被引:0
|
作者
Guo L. [1 ]
Wu J. [1 ]
Huang Z. [1 ]
Wang T. [1 ]
Lu H. [2 ]
Jin Y. [2 ]
机构
[1] State Grid Jiangsu Electric Power Company Economic Research Institute, Nanjing
[2] Research Center of Grid Energy Storage and Battery Application, School of Electrical Engineering, Zhengzhou University, Zhengzhou
来源
基金
中国国家自然科学基金;
关键词
Energy storage cabin; Fire extinguishing; LFP battery; Li-ion battery; Pressure; Thermal runaway; Water mist;
D O I
10.13336/j.1003-6520.hve.20200302009
中图分类号
学科分类号
摘要
The problem that fire needs to be extinguished quickly after batteries catch fire is urgently required to be solved in the large-scale application of electrochemical energy storage stations. At present, tests of extinguishing fire of lithium-ion battery with fine water mist are mostly focused on small-capacity single cells. The test platform is far from the actual environment of the energy storage cabin. Therefore, according to the extinguishing mechanism for verifying water mist fire-extinguishing effect, we designed a test plan according to the energy storage battery's actual operating conditions, and built a test platform reference to the actual energy storage cabin. A 344 Ah LFP battery module was adopted as a test object. Under the abuse of overcharge, the battery module would thermally run away and then burn. Four types of water mist with different pressures were used to extinguish and compare the fire extinguishing effects. The test proves that fine water mist with a sufficient pressure can effectively extinguish the fire of the LFP battery module. During the extinguishing process, there are cooling and heat insulation radiation mechanisms, and a fine water mist barrier phenomenon has been observed. It is found that the pressure of fine water mist below 10 MPa is inversely proportional to the fire extinguishing time. As the pressure increases, both the fire extinguishing rate and the cooling rate increase. The experimental results show that, for the fire protection design of large-capacity LFP battery modules, it is more economical and efficient to choose a fine water mist of 6 MPa or more as the fire extinguishing agent. The results of this study can provide test support for the fire protection measures of lithium iron phosphate energy storage power stations and the formulation of battery module fire-extinguishing specifications. © 2021, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:1002 / 1011
页数:9
相关论文
共 29 条
  • [11] DONG Zitong, Accidents frequently torture the safety of energy storage power stations, China Energy News
  • [12] LI Shuai, Restore energy storage, Energy, 9, pp. 16-21, (2018)
  • [13] WU Jingyun, HUANG Zheng, GUO Pengyu, Research progress on fire protection technology of LFP lithium-ion battery used in energy storage power station, Energy Storage Science and Technology, 8, 3, pp. 495-499, (2019)
  • [14] HUI Dong, GAO Fei, YANG Kai, Et al., Patent analysis of safety protection technology for lithium ion batteries, High Voltage Engineering, 44, 1, pp. 106-118, (2018)
  • [15] LIU Yujun, DUAN Qiangling, LI Ke, Et al., Experimental study on fire extinguishing of large-capacity lithium-ion batteries by various fire extinguishing agents, Energy Storage Science and Technology, 7, 6, pp. 1105-1112, (2018)
  • [16] ANDERSSON P, ARVIDSON M, EVEGREN F, Et al., Lion fire: extinguishment and mitigation of fires in Li-ion batteries at sea, 77, pp. 1-52, (2018)
  • [17] ZHOU Zheng, YANG Jianhua, ZHU Ping, Et al., Fire extinguishing test of power lithium ion battery by water mist with additive, Fire Science and Technology, 38, 4, pp. 512-516, (2019)
  • [18] LI Yi, YU Dongxing, ZHANG Shaoyu, Et al., On the fire extinguishing tests of typical lithium-ion battery, Journal of Safety and Environment, 15, 6, pp. 120-125, (2015)
  • [19] REN D, FENG X, LU L, Et al., Overcharge behaviors and failure mechanism of lithium-ion batteries under different test conditions, Applied Energy, 250, pp. 323-332, (2019)
  • [20] FERNANDES Y, BRY A, DE PERSIS S., Identification and quantification of gases emitted during abuse tests by overcharge of a commercial Li-ion battery, Journal of Power Sources, 389, pp. 106-119, (2018)