Dissolved gas analysis (DGA) of natural ester insulating fluids with different chemical compositions

被引:0
|
作者
机构
[1] Gémez, N.A.
[2] Wilhelm, H.M.
[3] Santos, C.C.
[4] Stocco, G.B.
来源
| 1600年 / Institute of Electrical and Electronics Engineers Inc., United States卷 / 21期
关键词
Chemical compositions - DGA interpretation - Dissolved gas analyses (DGA) - Dissolved gas analysis - Fault interpretation - Fault prediction - Insulating fluid - Transformer faults;
D O I
10.1109/TDEI.2014.6832250
中图分类号
学科分类号
摘要
This study presents experimental results of the application of the dissolved gas-inoil analysis (DGA) technique to natural ester insulating fluids. The investigations covered two common types of transformer faults, discharge and overheating, and four different commercial insulating oils, one mineral and three natural esters: Biovolt A (from corn oil), Biovolt HW (from sunflower oil with high oleic acid) and Envirotemp FR3 (from soya oil). The natural esters insulating fluids (NEIFs) analyzed had different chemical compositions. Experiments were performed in the laboratory with the test oils at three different moisture levels (low, medium and high). The purpose was to see the effect of moisture content and oil composition on the quantities of fault gases dissolved in the different oil types. The overheating tests were performed by heating the oils in an oven at 150 °C. Discharges were generated using a flat plate-plate electrode arrangement immersed in oil. Five key dissolved hydrocarbon gases - hydrogen (H2), methane (CH4), ethane (C2H6), ethylene (C2H4) and acetylene (C2H2) ¿ generated by the two fault types in NEIFs were analyzed and compared with mineral oil (MIO) fault gases. The classic Duval triangle 1, modified Duval triangle 3, Roger's ratio, Dornenburg and IEC 60599 methods were applied to predict the fault type. The findings confirmed that the direct application of classic DGA fault interpretation methods, developed for mineral oils, to non-mineral oils needs some modifications. IR and RMN spectroscopy analyses were performed to observe differences in triacylglycerol group compositions before and after heating tests. © 1994-2012 IEEE.
引用
收藏
相关论文
共 50 条
  • [41] Reducing Environmental Impact and Improving Safety and Performance of Power Transformers With Natural Ester Dielectric Insulating Fluids
    Asano, Roberto, Jr.
    Page, Stephane A.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2014, 50 (01) : 134 - 141
  • [42] Data-driven Fault Diagnosis of Power Transformers using Dissolved Gas Analysis (DGA)
    Dhini, Arian
    Faqih, Akhmad
    Kusumoputro, Benyamin
    Surjandari, Isti
    Kusiak, Andrew
    INTERNATIONAL JOURNAL OF TECHNOLOGY, 2020, 11 (02) : 388 - 399
  • [43] An Application of Dissolved Gas Analysis (DGA) in the Assessment of Transformer Failures: A Focus on Geomagnetic Disturbances (GMDs)
    Jerry, Robard
    Gope, Gideon
    2018 IEEE PES/IAS POWERAFRICA CONFERENCE, 2018, : 775 - 780
  • [44] Comparative Performance Study of Dissolved Gas Analysis (DGA) Methods for Identification of Faults in Power Transformer
    Wajid, Abdul
    Rehman, Atiq Ur
    Iqbal, Sheeraz
    Pushkarna, Mukesh
    Hussain, Syed Mudassir
    Kotb, Hossam
    Alharbi, Mohammed
    Zaitsev, Ievgen
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2023, 2023
  • [45] Extraction and Analysis of Chemical Compositions of Natural Products and Plants
    Zhang, Mengjie
    Zhao, Jinhua
    Dai, Xiaofeng
    Li, Xiumei
    SEPARATIONS, 2023, 10 (12)
  • [46] Dissolved Gas Analysis in Camellia Insulating Oil during Thermal Ageing Test
    Gu, Lingyun
    Han, Qiuhuang
    Wang, Feipeng
    Wang, Kaizheng
    Xiang, Chenmeng
    Shi, Changkai
    Wu, Yan
    Bai, Xuefeng
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 495 - 498
  • [47] Statistical Analysis of Natural Ester based Insulating Liquid using Hypothesis Testing
    Baruah, Niharika
    Sangineni, Rohith
    Chakraborty, Manas
    Nayak, Sisir Kumar
    PROCEEDINGS OF 2020 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2020), 2020, : 347 - 350
  • [48] Dissolved gas analysis (DGA) of epartial discharge fault in bio-degradable transformer insulation oil
    Muhamad, N. A.
    Phung, B. T.
    Blackburn, T. R.
    2007 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING, VOLS 1-2, 2007, : 336 - +
  • [49] DISSOLVED GAS ANALYSIS (DGA) STUDY OF ARCING FAULT IN BIO-DEGRADABLE OIL INSULATION SYSTEMS
    Muhamad, N. A.
    Phung, B. T.
    Blackburn, T. R.
    Lai, K. X.
    ISEIM 2008: PROCEEDINGS OF 2008 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING, 2008, : 19 - 19
  • [50] Failure Analysis of Leakage for Insulating Joint at Natural Gas Pipeline
    Wang, G. F.
    Deng, B.
    Zhang, H. B.
    Yang, F. P.
    Zhang, L.
    Ren, G. Q.
    JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2022, 22 (01) : 292 - 297