Experimental study on stability and heat transfer characteristics of separated heat pipe with a compressible volume condenser

被引:0
|
作者
Zhao, Jinle [1 ]
Bi, Qincheng [1 ]
Wang, Teng [2 ]
Zhang, Tao [1 ]
Feng, Fan [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, 28 Xianning West Rd, Xian 710049, Peoples R China
[2] North China Elect Power Univ, Dept Power Engn, Baoding 071003, Peoples R China
关键词
Separated heat pipe; Condenser structure; Operating parameters; Heat transfer characteristics; Stability; PASSIVE COOLING SYSTEM; 2-PHASE CLOSED THERMOSIPHON; LOOP THERMOSIPHON; FILLING RATIO; PERFORMANCE; INSTABILITY;
D O I
10.1016/j.csite.2024.105511
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel Separated Heat Pipe (SHP) system incorporating two magnetic spheres (SHPMS) was proposed for power generation (US Patent 11365653B2, 2022) using low-grade thermal energy, or offering both reliable emergency power and efficient heat transfer for spent fuel pools. This paper reports the experimental investigation on flow and heat transfer characteristics of the SHP, providing a foundation for the R&D of SHPMS. The SHP system features a unique shell-and-tube condenser structure, where the tube side serves as the cooling coil, while the shell side functions as the condenser chamber, with the dual roles of liquid storage and surge tank. The study researched the stability and heat transfer performance of the SHP under various parameters, including filling ratios ranging from 17 % to 98 %, cooling temperatures between 14 degrees C and 22 degrees C, and system pressures from 630 to 830 kPa. Analysis of instantaneous temperature, pressure, and flow patterns reveals the absence of high-frequency oscillations or alternating flow patterns, indicating that the condenser's condensing chamber may eliminate the instability in the SHP. Comparative analysis of the heat transfer coefficient and thermal resistance indicates that higher filling ratios and system pressures impair heat transfer performance, with optimal results at lower filling ratios (17 %-55 %) and pressure (630 kPa), where the higher heat transfer coefficient and lower thermal resistance were observed. Cooling temperatures showed little impact on heat transfer, allowing it to be chosen based on safety and energy efficiency needs. This study provides a new perspective on SHP systems with compressible volume condenser, offering a potential solution to address the instability challenges of SHP and the selection of operation parameters.
引用
收藏
页数:22
相关论文
共 50 条
  • [11] Heat transfer characteristics of micro-channel condenser and copper pipe condenser in heat pump water heater
    Wu, Jiang-Hong
    Li, Hui-Xi
    You, Shao-Fang
    Binggong Xuebao/Acta Armamentarii, 2015, 36 (06): : 1147 - 1152
  • [12] EXPERIMENTAL RESEARCH ON HEAT TRANSFER CHARACTERISTICS OF PUSULATING HEAT PIPE
    Jia, Li
    Li, Yan
    HT2008: PROCEEDINGS OF THE ASME SUMMER HEAT TRANSFER CONFERENCE - 2008, VOL 2, 2009, : 375 - 379
  • [13] Experimental investigation of transient heat transfer characteristics of a heat pipe
    Sundaram, A. Shanmuga
    Velraj, R.
    Suganya, G.
    International Journal of Heat and Technology, 2009, 27 (01) : 29 - 35
  • [14] Flow and heat transfer in a rotating heat pipe with a conical condenser
    Lian, Wenlei
    Han, Taoyi
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2019, 101 : 70 - 75
  • [15] Experimental study on the ash deposition and heat transfer characteristics of a heat pipe air preheater
    Zhang, Jiajie
    Guo, Yang
    Hu, Zhou
    Li, Rui
    Ma, Suxia
    APPLIED THERMAL ENGINEERING, 2023, 234
  • [16] Experimental investigation on the heat transfer performance of flat heat pipe embedded with internally cooled condenser
    Rakshith, Bairi Levi
    Asirvatham, Lazarus Godson
    Angeline, Appadurai Anitha
    Raj, J. Perinba Selvin
    Bose, Jefferson Raja
    Wongwises, Somchai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2024, 230
  • [17] Experimental study on heat transfer characteristics of pulsating heat pipe under vibration environment
    Yao, Feng
    Chen, Xi
    Liu, Xiangdong
    Zhou, Hua
    Chen, Yongping
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2025, 208
  • [18] Effect of condenser location on heat transfer characteristics of miniature loop heat pipe with flat evaporator
    Huo, Jie-Peng
    Wang, Shuang-Feng
    Zhang, Xian-Feng
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2013, 34 (02): : 360 - 363
  • [19] Experimental study on heat transfer characteristics of naphthalene gravity heat pipe in molten salt
    Peng D.
    Guo Y.
    Lu Y.
    Wu Y.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2021, 42 (05): : 317 - 322
  • [20] Visualization experiment on boiling heat transfer and flow characteristics in separated heat pipe system
    Ding, Tao
    Cao, Han Wen
    He, Zhi Guang
    Li, Zhen