Analysis of indoor set-point temperature of split-type ACs on thermal comfort and energy savings for office buildings in hot-humid climates

被引:0
|
作者
Amoabeng K.O. [1 ,2 ]
Opoku R. [1 ,2 ,3 ]
Boahen S. [1 ]
Obeng G.Y. [1 ]
机构
[1] Department of Mechanical Engineering, Kwame Nkrumah University of Science & Technology (KNUST), Kumasi
[2] Sustainable Energy Service Centre, College of Engineering, KNUST, Kumasi
[3] Technology Consultancy Centre, College of Engineering, KNUST, Kumasi
来源
Energy and Built Environment | 2023年 / 4卷 / 03期
关键词
Air-conditioners; Energy savings; Hot-humid climate; Indoor thermal comfort; Set-point temperatures;
D O I
10.1016/j.enbenv.2022.02.006
中图分类号
学科分类号
摘要
In hot-humid climates, particularly in sub-Saharan Africa (SSA), ambient temperatures and relative humidity are as high as 35 °C and 84%, respectively, requiring the use of mechanical cooling systems for indoor thermal comfort. Split-type vapor-compression air-conditioners (SVAC) are mainly used for space cooling in SSA and consume 60–80% of total energy consumption in commercial and public buildings. Appropriate control strategy of the indoor set-point temperature of SVAC can result in significant energy savings in these buildings. In this study, modeling and dynamic simulation have been conducted using EnergyPlus to predict the energy saving potential and indoor thermal comfort of buildings in hot-humid climates by controlling set-point temperature of the SVAC. In a case study, climatic data for Ghana, was used to predict the energy saving potential and indoor thermal comfort. The study results revealed that, to ensure indoor thermal comfort at high outdoor temperature condition of 35 °C, the least and optimum set-point temperatures of the SVAC should be 21 °C and 25 °C, respectively. On the other hand, for low outdoor temperature condition, the least and optimum set-point temperatures were 22 °C and 26 °C, respectively. Considering 1-star and 2-star rated SVACs which are dominantly used in Ghana, operating at 21–25 °C in the case of high outdoor conditions, and 22–26 °C for low outdoor conditions relative to the least temperatures resulted in energy savings of 8–33% and 12-44%, respectively. © 2022
引用
收藏
页码:368 / 376
页数:8
相关论文
共 6 条
  • [1] Effect of the Set-Point Temperature on Indoor Thermal Comfort and Energy Demand in Office Building
    Park, Taeju
    Song, Doosam
    Kang, Kinam
    Kang, Gyumin
    Kim, Brain S.
    Cho, Hyejung
    Song, Sunggeun
    ASHRAE TRANSACTIONS 2014, VOL 120, PT 2, 2014, 120
  • [2] The effects of passive design on indoor thermal comfort and energy savings for residential buildings in hot climates: A systematic review
    Hu, Ming
    Zhang, Kai
    Nguyen, Quynh
    Tasdizen, Tolga
    URBAN CLIMATE, 2023, 49
  • [3] An enthalpy-based energy savings estimation method targeting thermal comfort level in naturally ventilated buildings in hot-humid summer zones
    He, Yueer
    Liu, Meng
    Kvan, Thomas
    Peng, Shini
    APPLIED ENERGY, 2017, 187 : 717 - 731
  • [4] Predicted Medium Vote Thermal Comfort Analysis Applying Energy Simulations with Phase Change Materials for Very Hot-Humid Climates in Social Housing in Ecuador
    Godoy-Vaca, Luis
    Vallejo-Coral, E. Catalina
    Martinez-Gomez, Javier
    Orozco, Marco
    Villacreses, Geovanna
    SUSTAINABILITY, 2021, 13 (03) : 1 - 31
  • [5] Optimizing active chilled beam systems in the South Korean Climate: Comparative analysis of cooling energy and thermal comfort by set-point temperature
    Park, Jun Kyu
    Yeon, Sang Hun
    Kim, Chul Ho
    Yoon, Yeobeom
    Moon, Jin Woo
    Lee, Kwang Ho
    ENERGY AND BUILDINGS, 2024, 325
  • [6] Thermal adaptation of different set point temperature modes and energy saving potential in split air-conditioned office buildings during summer
    Yan, Haiyan
    Shi, Fangning
    Sun, Zhen
    Yuan, Guodong
    Wang, Minli
    Dong, Mengru
    BUILDING AND ENVIRONMENT, 2022, 225