Theoretical analysis of the optimal ejector operation and design within an ejector-based refrigeration system

被引:1
|
作者
Metsue, Antoine [1 ,2 ]
Nesreddine, Hakim [3 ]
Bartosiewicz, Yann [2 ]
Poncet, Sebastien [1 ]
机构
[1] Univ Sherbrooke, Mech Engn Dept, Sherbrooke, PQ, Canada
[2] Catholic Univ Louvain, Inst Mech Mat & Civil Engn iMMC, Louvain La Neuve, Belgium
[3] Hydro Quebec, Lab Technol Energie, Shawinigan, PQ, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Carbon dioxide; Refrigeration cycle; Transcritical ejector; Coefficient of performance; Design; PERFORMANCE IMPROVEMENT; WORK RECOVERY; CYCLE; MODEL;
D O I
10.1016/j.ijrefrig.2024.09.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
Optimal operation and design of ejectors are the subject of recent concerns, especially for the enhancement of refrigeration and heat pump cycles based on natural refrigerants like carbon dioxide. In this study, a thermodynamic analysis of an ejector-based refrigeration cycle is performed to determine both what operating pressures lead to the highest physically possible performance depending on the ambient conditions, and what are the main dimensions of the ejector leading to the best performance at a given ambient temperature. A state-of-the-art thermodynamic model for the prediction of the ejector performance is for the first time utilized to generate reliable operation and performance maps of the ejector cycle. Most notably, it is found that the optimal coefficient of performance is not necessarily found when the ejector operates at critical conditions but mostly when the device is under off-design regime, depending on the ejector internal efficiency and the hot side temperature. In addition, the analysis reveals that the performance of the cycle is not highly sensitive to the throat area ratio of the ejector given that the latter lies within an acceptable range. Those findings contribute to getting a better understanding of how the cycle benefits from the ejector and define design and control strategies for the cycle.
引用
收藏
页码:334 / 344
页数:11
相关论文
共 50 条
  • [31] Numerical assessment of ejector operation for refrigeration applications based on CFD
    Bartosiewicz, Y
    Aidoun, Z
    Mercadier, Y
    APPLIED THERMAL ENGINEERING, 2006, 26 (5-6) : 604 - 612
  • [32] Performance characteristics of the ejector refrigeration system based on the constant area ejector flow model
    Yapici, R
    Ersoy, HK
    ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (18-19) : 3117 - 3135
  • [33] Design of steam ejector in a refrigeration application based on thermodynamic performance analysis
    Ruangtrakoon, Natthawut
    Aphornratana, Satha
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2019, 31 : 369 - 382
  • [34] Optimal design of two-stage ejector for subzero refrigeration system on fishing vessel
    Wang, Xinli
    Wang, Lei
    Song, Yajie
    Deng, Jie
    Zhan, Youjie
    APPLIED THERMAL ENGINEERING, 2021, 187
  • [35] Experimental and economic analysis with a novel ejector-based detection system for thermodynamic measurement of compressors
    Li, Xiaoqiong
    Wang, Xiaoyan
    Zhang, Yufeng
    Fang, Lei
    Deng, Na
    Zhang, Yan
    Jin, Zhendong
    Yu, Xiaohui
    Yao, Sheng
    APPLIED ENERGY, 2020, 261 (261)
  • [36] System COP of Ejector-Based Ground-Source Heat Pumps
    El Hassan, Mouhammad
    ENERGIES, 2022, 15 (22)
  • [37] Influence of geometric parameters on ejector acoustics and efficiency in ejector refrigeration system
    Li, Wenliang
    Han, Qingyang
    Wang, Cheng
    Zhang, Hailun
    Jia, Lei
    Wang, Lei
    Sun, Wenxu
    Xue, Haoyuan
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2025, 169 : 429 - 443
  • [38] Thermally activated mobile ejector refrigeration system analysis
    Salim, M
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART D-JOURNAL OF AUTOMOBILE ENGINEERING, 2004, 218 (D9) : 1055 - 1061
  • [39] The Influence of Ejector's Structure Parameters on the Performance of Ejector Refrigeration System
    Hu, Wenju
    Wang, Meng-yuan
    Nie, Jin-zhe
    Gao, Yan
    Zhang, Qun-li
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2683 - 2690
  • [40] Calculation and analysis for an ejector refrigeration system with various refrigerants
    Wang, Fei
    Shen, Shengqiang
    Huagong Xuebao/CIESC Journal, 2010, 61 (02): : 275 - 280