A novel adaptive differential line protection principle

被引:0
|
作者
Liu K. [1 ]
Li Y. [2 ]
Brncic I. [3 ]
Shi Z. [3 ]
Wang J. [2 ]
机构
[1] ABB Corporate Research China, Chaoyang District, Beijing
[2] ABB Corporate Research Sweden, Vasteras
[3] ABB Substation Automation Products, Vasteras
来源
| 1600年 / Chinese Society for Electrical Engineering卷 / 36期
关键词
Adaptive protection; CT saturation; Differential protection; Fault component; Phase angle difference; Transmission line;
D O I
10.13334/j.0258-8013.pcsee.151054
中图分类号
学科分类号
摘要
Differential current protection has been widely used for the line as main protection. Conventional differential current protection has relatively lower sensitivity because of charging current and heavy load; and may mal-trip for external faults with CT saturation, and the additional methods to avoid mal-operation from CT saturation may slow down the operation speed and sensitivity. Adaptive line differential protection enhanced by phase angle was proposed, which achieves good balance among high sensitivity, fast operation speed and high security. Proposed protection principle is immune to charging current and CT saturation, and has fast operation speed with small value of the operate time dispersion. PSCAD/Matlab simulation verifies the validity of proposed principle. © 2016 Chin. Soc. for Elec. Eng.
引用
收藏
页码:3440 / 3450
页数:10
相关论文
共 27 条
  • [11] Suonan J., Liu K., Zhang Y., Et al., New principle of differential protection based on the resistance component of differential current, Automation of Electric Power Systems, 31, 16, pp. 45-49, (2007)
  • [12] Suonan J., Liu K., Su X., Et al., A novel transmission line pilot protection based on fault component integrated impedance, Proceedings of the CSEE, 28, 31, pp. 54-61, (2008)
  • [13] Suonan J., Liu K., Su X., Et al., Novel transmission line pilot protection based on integrated impedance, Automation of Electric Power Systems, 32, 3, pp. 36-41, (2008)
  • [14] Zhang W., He B., Shen B., Et al., Traveling- wave differential protection on UHV transmission line with shunt reactor, Proceedings of the CSEE, 27, 10, pp. 56-61, (2007)
  • [15] Chen F., Qian G., Song G., Study on traveling-wave differential protection for series compensated line, Proceedings of the CSEE, 29, 28, pp. 89-94, (2009)
  • [16] Wang L., Wang X., Differential protection based on calculated power for UHV transmission lines, Proceedingss of the CSEE, 33, 19, pp. 174-183, (2013)
  • [17] Suonan J., Ma C., Kang X., Et al., A novel transmission line pilot protection principle based on current model recognition, Proceedings of the CSEE, 32, 19, pp. 109-117, (2012)
  • [18] Zhao Y., Lu Y., Transformer adaptive elliptical restraint differential protection based on phaselet algorithm, Proceedingss of the CSEE, 28, 7, pp. 72-78, (2008)
  • [19] Liu H., Zhou Z., Zhou C., Et al., Current differential relay of transmission lines based on incremental quantity, Proceedings of the CSEE, 33, 1, pp. 146-152, (2013)
  • [20] Wen M., Chen D., Yin X., Et al., Long transmission line current differential protection by using instantaneous value after equal transfer processes, Proceedingss of the CSEE, 27, 28, pp. 59-65, (2007)