Overvoltage and insulation coordination for ±1100 kV UHVDC converter station

被引:0
|
作者
机构
[1] Zhou, Hao
[2] Deng, Xu
[3] Wang, Dongju
[4] Shen, Yang
[5] Chen, Xilei
[6] Sun, Ke
来源
Zhou, H. (zhouhao_ee@zju.edu.cn) | 2013年 / Science Press卷 / 39期
关键词
Power transmission - Electric insulation coordination - Busbars - Electrolysis - Surge protection - Insulation - Transformer protection - Overvoltage protection;
D O I
10.3969/j.issn.1003-6520.2013.10.022
中图分类号
学科分类号
摘要
In order to specify the overvoltage and insulation level of equipments in ±1100 kV UHVDC converter stations, the arrester configuration scheme and some basic parameters for ±1100 kV Zhundong converter station are proposed. Overvoltage of equipments in AC system, valve hall, DC busbar, and neutral busbar are also calculated in accordance with the fundamental principles of arrester configuration for UHV converter stations and the existing experiences in insulation coordination of ±800 kV UHVDC converter stations. The work is done also for specifing insulation levels for ±1100 kV UHVDC converter stations of the ±1100 kV UHVDC power transmission project from Zhundong to Sichuan in China. Thus, the recommended insulation margins that determine the insulation levels of converter station equipments are proposed: the insulation margins for thyristor valves are 10%/10%/15% for switching impulse/lightning impulse/steer front impulse; the insulation levels of lighting and swtiching impulses are recommended as 2600 kV and 2150 kV respectively for 1100 kV DC buses, and as 2250 kV and 2100 kV respectively for equipments at the valve side of high-voltage Y/Y converter transformers.
引用
收藏
相关论文
共 50 条
  • [1] Switching Overvoltage Characteristics of ±1100-kV UHVDC Converter Station
    Wang, Dongju
    Zhou, Hao
    Deng, Xu
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) : 1205 - 1212
  • [2] The insulation and coordination of ± 1 000 kV UHVDC converter station
    Lu, Yuxin
    Han, Yongxia
    Zhu, Zhifang
    Liu, Gang
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2014, 29 : 516 - 523
  • [3] 750 kV AC filter insulation coordination in UHVDC converter station
    Nie, Dingzhen
    Zhang, Tao
    Yu, Shifeng
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (06): : 1802 - 1808
  • [4] Research on key issues of insulation coordination for ±1 100 kV UHVDC converter station
    Cixi Power Supply Bureau, Cixi 315300, China
    不详
    不详
    Chen, X. (xilei_chen@163.com), 1600, Science Press (39):
  • [5] Development and application of insulation coordination software for UHVDC converter station
    Pan, Wenxia
    Liu, Xun
    Nie, Dingzhen
    Chen, Jie
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2011, 31 (03): : 109 - 112
  • [6] Insulation coordination for ±800kV UHVDC converter stations
    Beijing Wanglian HVDC Engineering Technology Co., Ltd, Beijing 100005, China
    Gaodianya Jishu, 2006, 9 (75-79):
  • [7] Comparison of Insulation Coordination Between ±800kV and ±1100kV UHVDC Systems
    Wang, Dong-ju
    Zhou, Hao
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2015, 10 (04) : 1773 - 1779
  • [8] Comparison of insulation coordination between ±800kV and ±1100kV UHVDC systems
    College of Electrical Engineering, Zhejiang University, China
    J. Electr. Eng. Technol., 4 (1774-1780):
  • [9] Study on Overvoltage and Insulation Coordination of Grounding Pole Line for ±800kV UHVDC System
    Xia Chao
    Chen Xiujuan
    Shi Weidong
    Liu Fan
    Xie Shijun
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2433 - 2439
  • [10] Protective characteristics of MOA configured in ±1 100 kV UHVDC converter station under internal overvoltage
    Chen, Xiujuan
    Zhang, Cuixia
    Zhang, Boyu
    Su, Ning
    Wu, Yani
    Yang, Peng
    Dianwang Jishu/Power System Technology, 2015, 39 (02): : 362 - 366