Applying power quality characteristics of wind turbines for assessing impact on voltage quality

被引:1
|
作者
Tande, John Olav Giæver [1 ]
机构
[1] SINTEF Energy Research, NOR, Trondheim,N-7465, Norway
关键词
Copyrights - Electric power system interconnection - Electric power transmission networks - Electric utilities - Power quality - Quality control - System stability - Wind farm;
D O I
10.1002/we.59
中图分类号
学科分类号
摘要
Injection of wind power into an electric grid affects the voltage quality. As the voltage quality must be within certain limits to comply with utility requirements, the effect should be assessed prior to installation. To assess the effect, knowledge about the electrical characteristics of the wind turbines is needed or else the result could easily be an inappropriate design of the grid connection. The electrical characteristics of wind turbines are manufacturer-specific but not site-specific. This means that, having the actual parameter values for a specific wind turbine, the expected impact of the wind turbine type on voltage quality when deployed at a specific site, possibly as a group of wind turbines, can be calculated. The methodology for this is explained and illustrated by case studies considering a 5 × 750 kW wind farm on a 22 kV distribution feeder. The detailed analysis suggests that the wind farm capacity can be operated at the grid without causing unacceptable voltage quality. For comparison, a simplified design criterion is considered assuming that the wind farm is only allowed to cause a voltage increment of 1%. According to this criterion, only a very limited wind power capacity would be allowed. Measurements confirm, however, the suggestion of the detailed analysis, and it is concluded that a simplified design criterion such as the ‘1% rule’ should not be used for dimensioning the grid connection of wind farms. Rather, this article suggests a systematic approach including assessment of slow voltage variations, flicker, voltage dips and harmonics, possibly supported by more detailed analyses, e.g. system stability if the wind farm is large or the grid is very weak, and impact on grid frequency in systems where wind power covers a high fraction of the load, i.e. most relevant for isolated systems. Copyright © 2002 John Wiley & Sons, Ltd. Copyright © 2002 John Wiley & Sons, Ltd.
引用
收藏
页码:37 / 52
相关论文
共 50 条
  • [21] Assessment of power quality characteristics of wind farms
    Estanqueiro, A. I.
    Tande, J. O.
    Lopes, J. A. Pecas
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 3203 - 3206
  • [22] Voltage quality assessment considering low voltage ride-through requirement for wind turbines
    Park, Chang-Hyun
    Jang, Gilsoo
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (16) : 4205 - 4212
  • [23] Comparison of Power Quality in Different Grid-Integrated Wind Turbines
    Duong, M. Q.
    Le, K. H.
    Grimaccia, F.
    Leva, S.
    Mussetta, M.
    Zich, R. E.
    2014 IEEE 16TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2014, : 448 - 452
  • [24] The wind farm aggregation impact on power quality
    Bialasiewicz, Jan T.
    Muljadi, Eduard
    IECON 2006 - 32ND ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS, VOLS 1-11, 2006, : 1953 - +
  • [25] Impact of Wind Power Plant Operation on Voltage Quality Parameters-Example from Poland
    Skibko, Zbigniew
    Holdynski, Grzegorz
    Borusiewicz, Andrzej
    ENERGIES, 2022, 15 (15)
  • [26] Impact of the Power Quality of the Wind Farm and the Effects on the Power System
    Chura Acero, Julio Fredy
    Limachi Viamonte, Wilhem Rogger
    Chayna Velasquez, Omar
    Alvarez Lupaca, Wilbert D.
    2021 IEEE PES/IAS POWERAFRICA CONFERENCE, 2021, : 805 - 809
  • [27] Impact of Wind Power Plants on Distribution Systems Power Quality
    Spacil, Daniel
    Santarius, Pavel
    11TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2010, PROCEEDINGS, 2010, : 261 - 265
  • [28] An implementation of real-time measurement and assessment system for power quality characteristics of grid connected wind turbines
    Lee, Jong-Joo
    Kim, Dong-Joon
    Moon, Young-Hwan
    Transactions of the Korean Institute of Electrical Engineers, 2010, 59 (09): : 1560 - 1565
  • [29] Power quality solutions for voltage dip compensation at wind farms
    Amarfs, H.
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 512 - +
  • [30] Voltage Quality in the Medium Voltage Distribution Grid with Connected Wind Power Plants
    Kaspirek, Martin
    2016 17TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2016, : 294 - 298