Research on detecting single-phase-to-ground faulted feeder in resonant grounded power distribution system

被引:0
|
作者
Chen, Kui [1 ]
Tang, Yi [1 ]
Liu, Changjiang [1 ]
Dong, Haibo [1 ]
机构
[1] China University of Mining and Technology, Xuzhou 221008, China
来源
关键词
D O I
暂无
中图分类号
学科分类号
摘要
In the resonant grounded power distribution system, the magnitude and direction of zero sequence measuring current in the faulty line is different from the current in the ungrounded power system when a single phase earth fault happens because of the compensation effect of the inductive current in arc suppression coil on the capacity ground current. Because the magnitude of zero sequence measuring current is connected with the compensation degree of arc suppression coil, the condition in resonant grounded power distribution system is more complicated than in ungrounded power system. Therefore the fault detection in a resonant grounded power distribution system is a tickler in indirectly earthed power system and the most existing methods used in field have the question which cannot find the faulty line accurately. On the basis of detailed analysis of the zero sequence measurement current distribution in resonant grounded power distribution system, a new detecting one-phase-to-ground fault feeder calculation method is proposed in this paper, which adds the arc suppressing coil compensation current to the zero sequence current of every feeders, is armed at the resonant grounded power distribution system and is based on the stable state analysis. EMPT simulation and analysis show that this calculation method has effectively raised the protecting abundant degree. The operation results of the power system indicated that the device which is developed in the calculation method has a high accuracy in the detecting fault feeder in the indirectly earthed power system regardless of running state including under compensation state, full compensation state and over compensation state.
引用
收藏
页码:61 / 65
相关论文
共 50 条
  • [31] New method for single-phase-to-ground fault feeder selection based on analysis of fault transient characteristics
    Key Laboratory of Power System Simulation and Control of Ministry of Education, Tianjin University, Tianjin 300072, China
    不详
    Dianli Xitong Zidonghue, 2009, 16 (76-80):
  • [32] Single-phase-to-ground fault section location in flexible resonant grounding distribution networks using soft open points
    Li, Zhengtian
    Ye, Yuqing
    Ma, Xiao
    Lin, Xiangning
    Xu, Feng
    Wang, Chaoliang
    Ni, Xiaojun
    Ding, Chao
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 122 (122)
  • [33] Faulty Phase Recognition Method for Single-Line-to-Ground Fault in Resonant Grounded Distribution Networks
    Ma, Mingwen
    Wang, Wen
    Wang, Faliang
    Ren, Xingqiang
    Wang, Zhen
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 351 - 357
  • [34] RESEARCH ON SINGLE-PHASE TO GROUND FAULT IN RESONANT GROUNDING SYSTEM
    Zhang Jian
    Duan Li-xiao
    Dou Zhan-liang
    2011 INTERNATIONAL CONFERENCE ON INSTRUMENTATION, MEASUREMENT, CIRCUITS AND SYSTEMS ( ICIMCS 2011), VOL 1: INSTRUMENTATION, MEASUREMENT, CIRCUITS AND SYSTEMS, 2011, : 459 - 463
  • [35] Artificial neural networks for single phase fault detection in resonant grounded power distribution systems
    Assef, Y
    Bastard, P
    Meunier, M
    1996 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE PROCEEDINGS, 1996, : 566 - 572
  • [36] Single-phase-to-ground Fault Detection with Distributed Parameters Analysis in Non-direct Grounded Systems
    Liu, Baowen
    Ma, Hongzhong
    Xu, Honghua
    Ju, Ping
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2019, 5 (01): : 139 - 147
  • [37] Faulted feeder identification and location for a single line-to-ground fault in ungrounded distribution system based on principal frequency component
    Liu, Ling
    ARCHIVES OF ELECTRICAL ENGINEERING, 2020, 69 (03) : 695 - 704
  • [38] Summary and Adaptability Analysis of Implementation Schemes about Single-Phase-to-Ground Fault Diagnosis in Distribution System
    Li, Yajie
    Song, Xiaohui
    Zhao, Shanshan
    Gao, Fei
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1311 - 1315
  • [39] Study of single-phase-to-ground fault branch identification algorithm in 10kV power distribution lines
    Li Na
    Yang Lingxiao
    Progress in Mining Science and Safety Technology, Pts A and B, 2007, : 889 - 893
  • [40] Principle and algorithm of traveling waves based single-phase-to-ground protection for distribution lines
    Dong, Xinzhou
    Wang, Jun
    Shi, Shenxing
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2013, 33 (10): : 154 - 160