Effect of fill layout and water flow rate distribution on the performance for cooling tower

被引:0
|
作者
Wang M. [1 ]
Wang J. [1 ]
Zhang C. [2 ]
机构
[1] School of Civil Engineering, Beijing Jiaotong University, Beijing
[2] Department of Power Engineering and Water Conservancy, GuoHua Ninghai Power Plant, Ningbo, 315000, Zhejiang
来源
Wang, Jin (14115313@bjtu.edu.cn) | 2018年 / Harbin Institute of Technology卷 / 50期
关键词
Cooling performance; Fill non-uniform layout; Non-uniform water flow rate distribution; Super-large cooling tower; Three dimensional numerical simulation;
D O I
10.11918/j.issn.0367-6234.201803100
中图分类号
学科分类号
摘要
In order to identify the effect of fill layout and water flow rate distribution on the cooling performance of cooling tower, a three-dimensional numerical model was established based on prototype of No.6 Cooling Tower in the Second Phase of Guohua Ninghai Power Plant in Zhejiang Province. Loading the mass, momentum, energy equation was computed by using user defined function. The comparision with the field measurement data proves the accuracy of the numerical calculation result. The effects of three kinds of fills and five kinds of fills layouts on cooling performance of super-large cooling tower weve compared and analyzed. It is found that compared with biphasic wave and double oblique wave, the cooling efficiency of S wave is optimal. For S wave, based on the dimensionless radius ř≤0.39 (inner zone), 0.39< ř≤0.70 (middle zone) and 0.70<ř≤1 (outer zone), the outlet water temperature of non-uniform layout 1.25-1.5-1.25 m is 0.66 K lower than the outlet water temperature of the uniform fill layout pattern 1.5 m. It is shown that the decreased fill height in inner and outer zones results in a higher air velocity and more uniform distribution of air velocity. In addition, increasing the salinity of cooling water made the outlet water temperature of three kinds of fills improve by about 2 K. It is indicated that the rise of outlet water temperature is related to the nature of seawater itself, and fill types has little impact on outlet water temperature. © 2018, Editorial Board of Journal of Harbin Institute of Technology. All right reserved.
引用
收藏
页码:124 / 131
页数:7
相关论文
共 25 条
  • [11] Williamson N., Armfield S., Behnia M., Numerical simulation of flow in a natural draft wet cooling tower-the effect of radial thermos fluid fields, Applied Thermal Engineering, 28, 2-3, (2008)
  • [12] Kroger D., Air-cooled Heat Exchangers and Cooling Towers, (2004)
  • [13] Kloppers J., A critical evaluation and refinement of the performance of wet-cooling towers, (2003)
  • [14] Alkhedhair A., Gurgenci H., Jahn I., Et al., Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers, Applied Thermal Engineering, 61, (2013)
  • [15] Alkhedhair A., Jahn I., Gurgenci H., Et al., Numerical simulation of water spray in natural draft dry cooling towers with a new nozzle representation approach, Applied Thermal Engineering, 98, (2016)
  • [16] Alwaked R., Behnia M., Enhancing performance of wet cooling tower, Energy Conversion and Management, 48, 10, (2007)
  • [17] Mortensen M., Minet R.G., A two-stage cyclic fluidized bed process for converting hydrogen chloride to chlorine, Chemical Engineering Science, 51, 10, (1996)
  • [18] Nomura S., Behavior of coalchlorine in coke making process, International Journal of Coal Geology, 83, 4, (2010)
  • [19] Sliger T., Kramlich J., Marinov N., Towards the development of a chemical kinetic model for the homogeneous oxidation of mercury by chlorine species, Fuel Processing Technology, 65-66, (2000)
  • [20] Fluent user's guide, (2003)