Research and practice of novel architecture of supervision and control system in smart substation

被引:0
|
作者
Wang Y. [1 ]
Han S. [1 ]
Shang L. [1 ]
Geng X. [2 ]
Song W. [3 ]
Zhu C. [3 ]
机构
[1] State Grid Shandong Electric Power Company, Jinan
[2] State Grid Zibo Power Supply Company, Zibo
[3] Integrated Electronic Systems Lab Co., Ltd, Jinan
关键词
Bay level; IEC61850; Process level; Smart grid; Station level; Supervision and control system;
D O I
10.7667/PSPC180535
中图分类号
学科分类号
摘要
Supervision and control system of smart substation is usually configured by bays, which will lead to problems such as numerous facilities and a lack of alternative devices. To solve these problems, a novel architecture of supervision and control system for smart substation is proposed. This architecture enhances the degree of functional integration of station level. Because of allowing SV and GOOSE transferred within the same communication network, the communication network in smart substation is also optimized. The bay level adopts clustered measurement-control devices, which can integrate the measurement and control tasks into several physical devices. The bay level of proposed supervision and control system architecture can achieve hot standby at device level through the dynamic migration technology. In the meantime, visualization maintenance software has also been developed, which increase the efficiency of the reconstruction and expansion on smart substations. The crucial technology and implementation scheme of supervision and control system are elaborated. Through the trial operation of a new-built smart substation, this paper analyzes and predicts the application prospects of the novel supervision and control system. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:145 / 151
页数:6
相关论文
共 20 条
  • [11] Xiao Y., Design of information flow scheme for new smart substation, Proceedings of the CSEE, 36, 5, pp. 1245-1251, (2016)
  • [12] Liu J., Deng Z., Li Z., Et al., Automatic information verification technology of smart substation based plug and play, Power System Protection and Control, 46, 2, pp. 137-143, (2018)
  • [13] Hu S., Li L., Zhu X., Et al., Scheme and practice for improving engineering implementation efficiency of smart substation automation system, Automation of Electric Power Systems, 41, 11, pp. 173-180, (2017)
  • [14] Wang W., Cui J., Hu R., Et al., Discussion on related technologies of supervision and control terminal based on smart remote terminal unit, Automation of Electric Power Systems, 41, 16, pp. 187-191, (2017)
  • [15] Yang Z., Zhou B., Zhang H., Et al., Discussion on novel scheme of smart substation automation system, Automation of Electric Power Systems, 40, 14, pp. 1-7, (2016)
  • [16] Li F., Yi Y., Tao Y., Et al., Research on the programs of smart substation measurement and control technology, Electrical Measurement & Instrumentation, 50, 7, pp. 118-122, (2013)
  • [17] Yao Z., Wu Y., Xu X., Et al., Exploration of key technologies in integration of dispatching center and substation for smart grid, Automation of Electric Power Systems, 41, 8, pp. 179-185, (2017)
  • [18] Wang L., Quan X., Liu H., Et al., Research on integration technology of automation system in smart substation, Distribution & Utilization, 33, 7, pp. 61-65, (2016)
  • [19] Qin H., Wu F., Peng S., Et al., New technology research on secondary equipment operation maintenance for smart grid, Power System Protection and Control, 43, 22, pp. 35-40, (2015)
  • [20] Wang D., Liu X., A resource scheduling strategy for cloud computing platform of power system simulation based on dynamic migration of virtual machine, Automation of Electric Power Systems, 39, 12, pp. 97-105, (2015)