Influence of Large Shed Structure on Contamination Accumulation Characteristics of Composite Insulator

被引:0
|
作者
Lyu Y. [1 ]
Wei Z. [1 ]
Wang J. [1 ]
机构
[1] School of Energy Power and Mechanical Engineering, North China Electric Power University, Hebei Province, Baoding
关键词
composite insulator; numerical simulation; pollution characteristics; super large umbrella skirt structure;
D O I
10.13334/j.0258-8013.pcsee.212996
中图分类号
学科分类号
摘要
In order to explore the influence of changing large sheds in different parts on the pollution accumulation characteristics of composite insulators, three kinds of large shed structural models are constructed based on the original model of FXBW4-110/100 composite insulators. COMSOL Multiphysic is used to numerically simulate the fouling characteristics of four insulator models, and the differences in the distribution of flow field and electric field near them are compared and analyzed to explore the fouling laws under different wind speeds, particle sizes and voltage types. The results show that the flow field distribution near the composite insulator can be changed by installing a large umbrella skirt at an appropriate position. When the size of the large shed is relatively small and the number of pieces is small, the DC field strength distribution near the composite insulator is almost unchanged. Under the same particle size, the amount of fouling increases with the increase of wind speed; under the action of DC voltage, the large umbrella skirt is installed at the beginning and end of the composite insulator, which is the first model. At low wind speed, the pollution amount is 75%~95% of the original model, and with the increase of wind speed, the difference of pollution amount increases first and then decreases. Under the action of AC voltage, the amount of pollution in model one fluctuates up and down based on the original model; while the amount of pollution in model two and model three at 1~3 m/s is about 50%~90% of the original model. ©2023 Chin.Soc.for Elec.Eng.
引用
收藏
页码:4046 / 4054
页数:8
相关论文
共 17 条
  • [11] DONG Haiyan, ZHANG Youpeng, LI Shaoyuan, Wind tunnel simulation on contamination distribution of canti-lever composite insulator with booster sheds[J], Journal of Zhejiang University (Engineering Edition), 53, 8, pp. 1563-1571, (2019)
  • [12] DONG Haiyan, ZHANG Youpeng, Numerical analysis of contamination characteristics of new type insulator for catenary cantilever[J], High Voltage Engineeering, 45, 7, pp. 2267-2275, (2019)
  • [13] WANG Liming, LIU Ting, MEI Hongwei, Research on contamination deposition characteristics of post insulator based on computational fluid dynamics[J], High Voltage Engineeering, 41, 8, pp. 2741-2749, (2015)
  • [14] WANG Guozhi, CHEN Qing, Simulation on contamination depositing characteristics of electrified railway catenary insulator[J], Insulators and Surge Arresters, 6, pp. 228-234, (2020)
  • [15] ELIMELECH M, GREGORY J, JIA X., Particle deposition and aggregation: measurement,modelling and simulation [M], (2013)
  • [16] WANG Jing, CHEN Linhua, LIU Yu, Effect of the electric field on the contamination accumulation characteristic of the insulator[J], High Voltage Engineeering, 37, 3, pp. 585-593, (2011)
  • [17] LYU Y, LI J, ZHAO W., Model optimization of pollution deposition criterion of insulators based on energy[J], IEEE Transactions on Dielectrics and Electrical Insulation, 24, 5, pp. 2920-2929, (2017)