Influence of Electric Field Uniformity on Power Frequency Discharge Characteristics of Short Air Gap in Water Mist Condition

被引:0
|
作者
Chen B. [1 ]
Deng J. [2 ]
Sun Y. [1 ]
Liu Y. [1 ]
机构
[1] State Key Laboratory of Disaster Prevention & Reduction for Power Grid Transmission and Distribution Equipment, Hunan Electric Power Corporation Disaster Prevention and Reduction Center, Changsha
[2] College of Electrical and Information Engineering, Changsha University of Science & Technology, Changsha
来源
Chen, Baohui (bymountains@gmail.com) | 1734年 / China Machine Press卷 / 36期
关键词
Air gap; Ball-ball; Breakdown voltage; Power frequency; Rod-plate; Water mist;
D O I
10.19595/j.cnki.1000-6753.tces.200101
中图分类号
学科分类号
摘要
Water mist is a fire fighting technology with high insulation ability. The discharge characteristics of water mist under ball-ball gap and rod-plate gap were studied. For the ball-ball gap, the electrostatic field distortion caused by water mist droplets has greater influence than the charging of water mist particles in electrostatic field, and thus the breakdown voltage of water mist is always significantly lower than that of air gap. When the gap length is 2cm to 8cm, the breakdown voltage of water mist is 37.6% to 38.2% lower than that of air gap under ball-ball electrodes. For the rod-plate gap, the influence of electrostatic field distortion decreases with the increase of gap length. When the gap length is 3.5cm to 8cm, the effect of electrostatic field distortion is higher than that of charging of water mist particles in electrostatic field. Moreover, the breakdown voltage of water mist under rod-plate electrodes is 6.0% to 8.5% lower than that of air gap. When the gap length is longer than 12cm, the effect of charging of water mist particles in electrostatic field exceeds the effect of electrostatic field distortion caused by water mist, and the breakdown voltage of water mist under rod-plate electrodes is higher than the breakdown voltage of air gap by 3.6% to 4.4%. The results can provide guidance for the application of water mist in fire prevention of high voltage power equipment. © 2021, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:1734 / 1742
页数:8
相关论文
共 26 条
  • [11] Kang Jun, Li Pei, Wang Shengfu, Et al., Influence of salt spray on AC/DC breakdown voltage of rod-plane gap, High Voltage Engineering, 41, 6, pp. 1989-1994, (2015)
  • [12] Xia Yu, Li Weiguo, Chen Yan, DC discharge performance and voltage correction of air gaps under high altitude, Transactions of China Electro- technical Society, 33, 9, pp. 2115-2120, (2018)
  • [13] Yang Yaqi, Li Weiguo, Xia Yu, Et al., Research of AC and DC discharge characteristics of long gap under low pressure, Transactions of China Electro- technical Society, 33, 5, pp. 1143-1150, (2018)
  • [14] Jiang Xingliang, Zhou Longwu, Yuan Yao, Et al., Analysis on DC discharge performance of short air gap under rain conditions, High Voltage Engin- eering, 41, 7, pp. 2350-2355, (2015)
  • [15] (2013)
  • [16] (1963)
  • [17] Oladiran E O., The interaction of positive streamers with charged and uncharged water drops in vertical electric fields, Pure and Applied Geophysics, 119, 5, pp. 966-977, (1981)
  • [18] (2015)
  • [19] Grigor'ev A I, Shiry'aeva S O., The mechanism of corona discharge from a water droplet, Journal of Engineering Physics, 60, 4, pp. 481-488, (1991)
  • [20] Abdel-Salam M., Positive wire-to-plane coronas as influenced by atmospheric humidity, IEEE Transa- ctions on Industry Applications, 21, 1, pp. 35-40, (1985)