Dynamic reconfiguration of an AC/DC hybrid distribution network considering battery energy storage aging and demand response

被引:0
|
作者
Liao X. [1 ]
Zhou Z. [1 ]
Le J. [2 ]
Li Z. [1 ]
Gong C. [3 ]
机构
[1] School of Electrical and Information Engineering, Wuhan Institute of Technology, Wuhan
[2] School of Electrical Engineering and Automation, Wuhan University, Wuhan
[3] State Grid Hebei Electric Power Research Institute, North China Electric Power Research Institute Co., Ltd., Beijing
基金
中国国家自然科学基金;
关键词
AC/DC hybrid distribution network; battery energy storage; dynamic reconfiguration; mixed integer second order cone programming; non-ideal linear model;
D O I
10.19783/j.cnki.pspc.221813
中图分类号
学科分类号
摘要
The existing battery energy storage model considers that the charging and discharging power and efficiency of the battery are fixed. On the other hand, the impact of the charging and discharging process on the cycle aging is not considered. This is contrary to the nonlinear equivalent circuit model of the battery cell body. Therefore, considering the cycle aging cost of the battery energy storage and demand response, this paper proposes a dynamic reconfiguration method of the AC/DC hybrid distribution network. By sampling the operational area of the actual battery energy storage charging and discharging power, a non-ideal battery energy storage model is reconstructed into a linear model in the convex envelope sampling point set. From this a cycle aging cost model based on the cumulative throughput and discharge depth is established, and the dynamic reconfiguration model of the AC/DC hybrid distribution network with minimum comprehensive cost is constructed. The mixed integer second-order cone programming method is used to solve the problem. The economics of the cycle aging cost model based on the depth of discharge proposed in this paper is verified by simulation on a modified 33-bus example, and the factors affecting the economics of the AC/DC hybrid distribution network reconfiguration method are analyzed. © 2023 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:43 / 54
页数:11
相关论文
共 25 条
  • [11] ZHANG Bo, LIU Shengyuan, LIN Zhenzhi, Et al., Reconfiguration of distribution network with high proportion of renewable energy considering demand response and soft open point, Automation of Electric Power Systems, 45, 8, pp. 86-94, (2021)
  • [12] HUANG Mingyu, ZHANG Qingping, ZHANG Shenxi, Et al., Distribution network reconfiguration considering demand-side response with high penetration of clean energy, Power System Protection and Control, 50, 1, pp. 116-123, (2022)
  • [13] HE Hongjie, ZHANG Ning, DU Ershun, Et al., Review on modeling method for operation efficiency and lifespan decay of large-scale electrochemical energy storage on power grid side, Automation of Electric Power Systems, 44, 12, pp. 193-207, (2020)
  • [14] GONZALEZ-CASTELLANOS A, POZO D, BISCHI A., Detailed li-ion battery characterization model for economic operation, International Journal of Electrical Power & Energy Systems, 116, pp. 105561-105561, (2020)
  • [15] GONZALEZ-CASTELLANOS A, POZO D, BISCHI A., Non-ideal linear operation model for li-ion batteries, IEEE Transactions on Power Systems, 35, 1, pp. 672-682, (2020)
  • [16] ANTONIADOU-PLYTARIA K, STEEN D, TUAN L, Et al., Market-based energy management model of a building microgrid considering battery degradation, IEEE Transactions on Smart Grid, 12, 2, pp. 1794-1804, (2021)
  • [17] ANTONIADOU-PLYTARIA K, STEEN D, TUAN L, Et al., Scenario-based stochastic optimization for energy and flexibility dispatch of a microgrid, IEEE Transactions on Smart Grid, 13, 5, pp. 3328-3341, (2022)
  • [18] LIU Chang, HUANG Yang, YANG Xinran, Et al., Flexible operation strategy of an urban transmission network considering energy storage systems and load transfer characteristics, Power System Protection and Control, 49, 6, pp. 56-66, (2021)
  • [19] ZHAO Zhipeng, LIU Jie, CHENG Chuntian, Et al., A MILP model for day-ahead peak operation of cascade hydropower stations considering backwater, Journal of Hydraulic Engineering, 50, 1, pp. 1-11, (2019)