PRACTICAL EXPERIENCE OF TECHNICAL SURVEY RELIABILITY OF OVERHEAD TRANSMISSION LINE STRUCTURES

被引:0
|
作者
Shaidulla, Mukhtar [1 ]
Abakanov, Tanatkan [1 ]
Abakanov, Askar [2 ]
Zaliyev, Felix [2 ]
Kenetbayev, Bolat [3 ]
机构
[1] Kazakh Leading Acad Architecture & Civil Engn, Int Educ Corp, Alma Ata, Kazakhstan
[2] Kazspetsremont LLP, Alma Ata, Kazakhstan
[3] D Serikbayev East Kazakhstan Tech Univ, Ust Kamenogorsk, Kazakhstan
来源
INTERNATIONAL JOURNAL OF GEOMATE | 2024年 / 27卷 / 119期
关键词
Transmission lines; Support structures; Steel structures; Technical survey;
D O I
10.21660/2024.119.4452
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Ensuring the reliability of the supporting structures of existing transmission lines is a key aspect of maintaining the stability and efficiency of the energy infrastructure. Various methods and technologies are used for this purpose. This study presents a methodology for comprehensively inspecting the load-bearing structures of overhead transmission lines located in the Aksu city of Pavlodar region of Kazakhstan. The survey included 2 main stages: visual and instrumental inspection up to the moment of line de-energization and inspection of all components of transmission line supports. During the design and construction, special reliability requirements were considered, such as the consideration of engineering-geological conditions when selecting a site for the construction of each support, considering the estimated climatic conditions of the region, wind speed, and the size of ice deposits. The results obtained from the inspection of all main and fastening elements of the supports' structures allowed us to assess the current state of the infrastructure and define a strategy for its maintenance and renewal. The results showed that deviations in metal profile thickness were minimal, averaging +/- 0.5 mm from design specifications, indicating minor structural failure. Grounding device resistance measurements varied within a narrow range of 5 to 7.45 Ohms, which met safety and operational standards, further confirming the reliability of the infrastructure. The strength of the concrete in the foundations, evaluated without failure, averaged 25 MPa, which meets Class B30 standards and indicates environmental resistance, which allowed us to conclude that further operation of transmission lines is possible.
引用
收藏
页码:92 / 99
页数:8
相关论文
共 50 条
  • [41] Technology and Application of Overhead Transmission Line Corridor Inspection
    Deng Yuanjing
    Ren Xichun
    Xia Kaiquan
    Zhang Hao
    PROCEEDINGS OF THE 2014 INTERNATIONAL CONFERENCE ON MECHATRONICS, ELECTRONIC, INDUSTRIAL AND CONTROL ENGINEERING, 2014, 5 : 1111 - +
  • [42] Development on Software of Overhead Transmission Line Foundation Design
    Cui, Qiang
    Liu, Sheng-kui
    Lu, Xian-long
    COMPUTER SCIENCE AND TECHNOLOGY (CST2016), 2017, : 973 - 979
  • [43] Modeling overhead transmission lines for line arrester studies
    Martinez, JA
    Castro-Aranda, F
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 1125 - 1130
  • [44] Seismic imaging of transmission overhead line structure foundations
    Vautrin, Denis
    Voorons, Matthieu
    Idier, Jerome
    Goussard, Yves
    Kerzale, Steven
    Paul, Nicolas
    COMPUTATIONAL IMAGING IX, 2011, 7873
  • [45] Analysis of Dicing Techniques and Methods of Overhead Transmission Line
    Lv, Xifeng
    He, Qing
    CEIS 2011, 2011, 15
  • [46] Fatigue failure of insulator string of overhead transmission line
    Gopalan, Thazhath Veettil
    Journal of Engineering Mechanics, 1991, 117 (01) : 88 - 99
  • [47] Analytical and experimental investigation of overhead transmission line vibration
    Barry, O.
    Zu, J. W.
    Oguamanam, D. C. D.
    JOURNAL OF VIBRATION AND CONTROL, 2015, 21 (14) : 2825 - 2837
  • [48] Numerical Noise Analysis for Insulator of Overhead Transmission Line
    Zhang, Yulin
    Chen, Yuwen
    Huang, Yu
    ADVANCES IN MATERIALS, MACHINERY, ELECTRONICS II, 2018, 1955
  • [49] Overhead transmission line shunt conductance from measurements
    Fernandes, AB
    Neves, WLA
    Costa, EG
    Cavalcanti, MN
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 479 - 479
  • [50] SENSITIVITY STUDY OF AN UNTRANSPOSED OVERHEAD TRANSMISSION-LINE
    INDULKAR, CS
    KUMAR, P
    KOTHARI, DP
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1982, 4 (04) : 265 - 269