Effects of Repetitive Fast Transients on Aging of Transformer Insulation

被引:0
|
作者
Devadiga, Anurag A. [1 ]
Jayaram, Shesha H. [1 ]
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Insulation; Oils; Transient analysis; Oil insulation; Power transformer insulation; Aging; Partial discharges; mineral oil; paper-oil insulation; power electronics converters; repetitive transient; rise time; switching frequency; OIL-PAPER INSULATION; BREAKDOWN CHARACTERISTICS; VOLTAGES;
D O I
10.1109/TDEI.2024.3387411
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The wind-turbine step-up transformers are subjected to high-frequency high dV/dt transient voltages due to the operation of power electronic converters and vacuum circuit breakers. These high-frequency transients are harmful to the transformer turn-to-turn and layer-to-layer paper-oil insulation. The current research work addresses the effect of the transient voltage parameters on the degradation of the transformer paper-oil insulation. Two-level, two-factor design of experiments were used to obtain the effect of transient voltage parameters on the aging of the paper-oil insulation. Rise time and switching frequency were the two factors (parameters) selected for the aging experiments. The two values of rise time were 220 and 650 ns, and two values of the switching frequency were 1 and 3 kHz. The faster rise time (220 ns) and higher switching frequency (3 kHz) of the voltage led to a higher degradation for the paper-oil insulation. In addition, the transient voltage aging of paper-oil insulation is investigated and compared for two types of mineral oils: Luminol TRi oil and Voltesso 35 oil, which have differences in their electrical and chemical properties.
引用
收藏
页码:2189 / 2197
页数:9
相关论文
共 50 条
  • [31] Determining Water in Transformer Paper Insulation: Analyzing Aging Transformers
    Martin, Daniel
    Saha, Tapan
    Dee, Richard
    Buckley, Gary
    Chinnarajan, Srinivasan
    Caldwell, Greg
    Bin Zhou, Jian
    Russell, Gary
    IEEE ELECTRICAL INSULATION MAGAZINE, 2015, 31 (05) : 23 - 32
  • [32] Study on the Aging Characteristics of Insulation Oil of UHVDC Converter Transformer
    Liu C.
    Shao S.
    Liao R.
    Yang L.
    Cheng L.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (03): : 730 - 736
  • [33] Comprehensive diagnostic and aging assessment method of solid insulation in transformer
    Dong, M
    Yan, Z
    Zhang, GJ
    2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 137 - 140
  • [34] Temperature aging of the selected synthetic and mineral transformer insulation systems
    Trnka, P.
    Pihera, J.
    Prosr, P.
    Polansky, R.
    ANNALS OF DAAAM FOR 2007 & PROCEEDINGS OF THE 18TH INTERNATIONAL DAAAM SYMPOSIUM: INTELLIGENT MANUFACTURING & AUTOMATION: FOCUS ON CREATIVITY, RESPONSIBILITY, AND ETHICS OF ENGINEERS, 2007, : 777 - 778
  • [35] Novel Sensor for Determining the Aging Condition of Insulation Paper in a Transformer
    Muenster, T.
    Kinkeldey, T.
    Werle, P.
    Haemel, K.
    Preusel, J.
    2020 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (2020 IEEE CEIDP), 2020, : 520 - 523
  • [36] Insulation Performance of Aging Transformer Winding under Transient Impulse
    Li, Yabo
    Wu, Zhen
    Ma, Guoming
    Li, Chengrong
    Ye, Haifeng
    Wu, Hao
    Luo, Yingting
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [37] Transfer function based analysis of fast transients impact on winding insulation
    Florkowski, Marek
    Furgal, Jakub
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (04): : 162 - 165
  • [38] Effects of Accelerated Repetitive Impulse Voltage Aging on Performance of Model Stator Insulation of Wind Turbine Generator
    Liu, Xuezhong
    Zhang, Tianlong
    Bai, Yonggang
    Ding, Xiaoxia
    Wang, Ying
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (04) : 1606 - 1615
  • [39] MEASUREMENT OF SWITCHING TRANSIENTS IN 735-KV SUBSTATIONS AND ASSESSMENT OF THEIR SEVERITY FOR TRANSFORMER INSULATION
    MALEWSKI, R
    DOUVILLE, J
    LAVALLEE, L
    IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) : 1380 - 1390
  • [40] Simulation on variation of electrical insulation parameters in predictive test caused by insulation aging of power transformer
    Wei, Jian-Lin
    Wang, Shi-Qiang
    Wu, Feng-Jiao
    Dong, Ming
    Huang, Xin-Bo
    Zhang, Guan-Jun
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (07): : 1618 - 1623