Treeing modeling and the effect of rejuvenation fluid in aged XLPE power cables based on the finite element method

被引:1
|
作者
Fadakar, Farzad [1 ]
Hosseini, Seyed Mohammad Hassan [1 ]
Shirazi, Amir Hossein Merati [1 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, South Tehran Branch, Tehran, Iran
关键词
Cable rejuvenation; Electrical tree; Finite element simulation; Power cable; Water tree; XLPE insulation; WATER; PERFORMANCE;
D O I
10.1007/s00202-024-02490-w
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article examines vented-type water tree and electrical tree in an XLPE-insulated cable, as well as the effect of rejuvenation fluid on the medium-voltage 20 kV XLPE cable insulation. Initially, laboratory specimens are placed under a scanning electron microscope and imaged to determine the dimensions and characteristics of water treeing and electrical treeing. Then, these specimens are immersed in the rejuvenation fluid, and their dielectric properties are evaluated over a 1-month period. The obtained results are analyzed using COMSOL Multiphysics software, and the outputs are discussed and examined. The initiation of vented-type water tree and its growth from a water filled cavity near an impurity was studied by building electric field simulation model and finite element analysis. The moisture in environment is gathered at the impurities or defects of cable insulation and the water filled cavities are formed under the action of alternating Maxwell stress. Although the field around the water tree is relatively low, if the cable is subjected to high stress (such as lightning strikes), the field at the ends of the cavities can intensify even further. In such cases, it can lead to the formation of electrical tree that can cause the XLPE breakdown. Therefore, stopping the growth of water trees and controlling them can be crucial for improving the electrical performance of water tree aged cables. One way to control water trees is by injecting a rejuvenation fluid into the cable (rejuvenation technique). The main components of the rejuvenating fluid include siloxanes and catalysts that react with water molecules and form oligomers, filling the water tree areas. This chemical reaction decomposes water molecules, leading to improved insulation performance. The objective of this article is to study the initiation of water tree and investigate the intensified electric field around vented-type water tree and how it can lead to electrical tree, as well as the role of the rejuvenation material in improving cable performance.
引用
收藏
页码:7769 / 7781
页数:13
相关论文
共 50 条
  • [1] Enhancing Inhibition of Electrical Treeing in XLPE Cables Based on the Targeted Movement of Rejuvenation Fluid Induced by Electric Field
    Wu, Yaping
    Zhou, Kai
    Lin, Siyan
    Wang, Zikang
    Chen, Yidong
    Zhu, Guangya
    Fu, Yao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1048 - 1055
  • [2] The Mechanism of Water Tree Growth in XLPE Cables based on the Finite Element Method
    Tao, Wenbiao
    Ma, Zhenguo
    Wang, Wenquan
    Liu, Jie
    Zhou, Kai
    Li, Tianhua
    Huang, Ming
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [3] A Finite Element Method based Approach for Modeling of Partial Discharges in HVDC Cables
    Anagha, E. R.
    Joseph, Jineeth
    Sindhu, T. K.
    2018 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2018, : 533 - 537
  • [4] Thermal analysis for determination of current carrying capacity of PE and XLPE insulated power cables using finite element method
    Kocar, I
    Ertas, A
    MELECON 2004: PROCEEDINGS OF THE 12TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE, VOLS 1-3, 2004, : 905 - 908
  • [5] Modeling propagation characteristics of power cables with finite element techniques and ATP
    O, Hio Nam
    Blackburn, T. R.
    Phung, B. T.
    2007 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING, VOLS 1-2, 2007, : 419 - 423
  • [6] Finite-Element Modeling of Power Cables Using Coordinate Transformations
    Piwonski, Albert
    Dular, Julien
    Rezende, Rodrigo Silva
    Schuhmann, Rolf
    IEEE TRANSACTIONS ON MAGNETICS, 2024, 60 (03) : 1 - 4
  • [7] A New Rejuvenation Method Based on Nano-filler for Water Tree Aged Cables
    Yang, Mingliang
    Zhou, Kai
    Yang, Di
    Tao, Wenbiao
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014, : 1398 - 1403
  • [8] Digital image processing for physical basis analysis of electrical failure forecasting in XLPE power cables based on field simulation using finite-element method
    Talaat, M.
    Tayseer, M.
    El-Zein, A.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (26) : 6703 - 6714
  • [9] Risk Assessment of XLPE Power Cables Based on Fuzzy Comprehensive Evalution Method
    Huan, Jia-jia
    Wang, Gang
    Li, Hai-feng
    Sun, Zhi-bin
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [10] A new rejuvenation technology based on formation of nano-SiO2 composite fillers for water tree aged XLPE cables
    Yang, Mingliang
    Zhou, Kai
    Wu, Ke
    Tao, Wenbiao
    Yang, Di
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (14): : 481 - 487