Development of a Dynamic Model of the Egyptian Power Grid for AGC Studies Using Real Data

被引:0
|
作者
Soliman, Radwa I. [1 ]
Abdalla, Omar H. [2 ]
Emary, Adel A. [1 ]
Talat, Laila A. [2 ]
机构
[1] Egyptian Elect Transmiss Co, Natl Energy Control Ctr, Cairo, Egypt
[2] Helwan Univ, Dept Elect Power & Machines Engn, Cairo, Egypt
来源
2024 14TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING, ICEENG 2024 | 2024年
关键词
Automatic Generation Control (AGC); Primary Frequency Control; Load Frequency Control (LFC); Egyptian Grid; Dead Band; Ramp Rate;
D O I
10.1109/ICEENG58856.2024.10566425
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents the development of a dynamic model of the Egyptian power system for Automatic Generation Control (AGC) studies. Each category of turbine and its speed-governor system is lumped in an equivalent model. Parameters of each equivalent model are derived based on weighted-average real data. The Egyptian power grid is briefly described and the MATLAB/Simulink software is used to perform AGC studies. Governor dead-band and ramp rate are considered. Two operating conditions are studied: peak summer demand and minimum winter demand. An integral controller is designed and applied to the generating units under AGC control through a secondary loop. The primary loop is the conventional speed droop proportional control. Various scenarios of the frequency control are considered including AGC on different generating units. The simulation results have shown that the parameters of the proposed model are insensitive to variations in the system operating point, thus implying the validity of the model over a wide range of operating conditions.
引用
收藏
页码:1 / 6
页数:6
相关论文
共 50 条
  • [21] USING OF POWER FLOW OPTIMIZATION IN POWER GRID DEVELOPMENT PROBLEM
    Przygrodzki, Maksymilian
    RYNEK ENERGII, 2011, (05): : 9 - 13
  • [22] Reference model for a data grid approach to address data in a dynamic SDI
    Serena Coetzee
    GeoInformatica, 2012, 16 : 111 - 129
  • [23] Analysis of grid code requirements for wind power dynamic model
    Kim, Mi-Young (fssp@koreatech.ac.kr), 1600, Science and Engineering Research Support Society (09):
  • [24] Real time data analytics platform for power grid smart applications
    Akram, Nihla
    De Silva, Sanjaya
    Foti, Magda
    Jayasinghe, Malith
    Dayarathna, Miyuru
    Vavalis, Manolis
    Perera, Srinath
    2017 14TH INTERNATIONAL CONFERENCE ON THE EUROPEAN ENERGY MARKET (EEM 17), 2017,
  • [25] Ocean Wave Power Data Generation for Grid Integration Studies
    McArthur, Shaun
    Brekken, Ted K. A.
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [26] Development of a Dynamic Photovoltaic Inverter Model with Grid-Support Capabilities for Power System Integration Analysis
    Darbali-Zamora, Rachid
    2023 IEEE 50TH PHOTOVOLTAIC SPECIALISTS CONFERENCE, PVSC, 2023,
  • [27] Research and Application of Grid AGC Collaborative Real-time Control Method Based on Wind Power Forecast Deviation
    Li, Jun
    Wang, Yong
    Liao, DaPeng
    Ding, XingWu
    Wang, Tao
    2018 FIRST INTERNATIONAL CONFERENCE ON ENVIRONMENT PREVENTION AND POLLUTION CONTROL TECHNOLOGY (EPPCT 2018), 2018, 199
  • [28] Enhancement of the Dynamic Model of Abu-Sultan Steam Power Plant in the Egyptian Power System
    Nassar, Ibrahim A.
    Abdella, Mahmoud M.
    2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 1339 - 1345
  • [29] Two-level Hierarchical Model Predictive Control for AGC of AC/DC Interconnected Power Grid with Wind Power Integration
    Liao X.
    Liu K.
    Wang N.
    Ma Y.
    Chen Z.
    Ding K.
    Zhou Q.
    Qin L.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2018, 42 (08): : 45 - 50and73
  • [30] Voltage Stability Assessment of a Real Power System Using a Detailed Dynamic Load Model
    Al Dessi, S. A.
    Osman, A. H.
    Ibrahim, A. I.
    2013 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER AND ENERGY CONVERSION SYSTEMS (EPECS), 2013,