Ensemble learning-based HVDC systems fault diagnosis

被引:0
|
作者
Li Q. [1 ]
Chen Q. [1 ]
Wu J. [1 ]
Peng G. [1 ]
Huang X. [1 ]
Li Z. [2 ]
Yang B. [2 ]
机构
[1] China Southern Power Grid EHV Transmission Company, Guangzhou
[2] China Southern Power Grid EHV Transmission Company Dali Bureau, Dali
基金
中国国家自然科学基金;
关键词
classifier; ensemble learning; fault diagnosis; HVDC transmission system;
D O I
10.19783/j.cnki.pspc.221653
中图分类号
学科分类号
摘要
In this paper, the measured data of four kinds of faults in a substation of the Southwest power grid are used as the data set. A method based on ensemble learning (EM) is designed for the fault diagnosis of a high voltage direct-current (HVDC) system, one which can significantly improve the speed, accuracy, and robustness of fault diagnosis. First, data preprocessing for the four types of fault data is conducted. At the same time, the feature of fault data is extracted and trained. The fault data label is used to average the weight of the fault data set. Then the classification error of the current weak classifier for the weighted data set is calculated, as well as the weight of the current classifier in the strong classifier. Finally, the distribution of the weights of the training samples is updated to obtain a strong classifier. From the trained model, the fault types are identified in the different data sets. Compared with a back propagation neural network fault diagnosis model, the proposed method can achieve more than 89% diagnostic accuracy in multiple tests, with a low error rate and strong robustness. It is conducive to fault identification and rapid diagnosis in an HVDC system in operation. © 2023 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:168 / 178
页数:10
相关论文
共 26 条
  • [21] SHAO Yao, TANG Yong, Research survey on multiinfeed AC/DC hybrid power systems, Power System Technology, 33, 17, pp. 24-30, (2009)
  • [22] MIRSAEIDI S, DONG X., An enhanced strategy to inhibit commutation failure in line-commutated converters, IEEE Transactions on Industrial Electronics, 67, 1, pp. 340-349, (2020)
  • [23] LIU Zhanlei, ZENG Xiangjun, YU Kun, Et al., A new method of single-phase grounding fault protection for a resonant grounding distribution network based on unbalanced overvoltage dynamic suppression, Power System Protection and Control, 49, 8, pp. 41-49, (2021)
  • [24] WANG Kaike, XIONG Xiaofu, XIAO Yang, Et al., Single-phase break fault protection method for an active distribution network based on negative sequence current, Power System Protection and Control, 49, 6, pp. 10-18, (2021)
  • [25] CHEN Shuyong, LI Xinnian, YU Jun, Et al., A method based on the sin-cos components detection mitigates commutation failure in HVDC, Proceedings of the CSEE, 25, 14, pp. 1-6, (2005)
  • [26] GUO C, LIU Y, ZHAO C, Et al., Power component fault detection method and improved current order limiter control for commutation failure mitigation in HVDC, IEEE Transactions on Power Delivery, 30, 3, pp. 1585-1593, (2015)