PLUMBING SYSTEM SHOCK-ABSORBERS AS A SOURCE OF LEGIONELLA-PNEUMOPHILA

被引:2
|
作者
MEMISH, ZA [1 ]
OXLEY, C [1 ]
CONTANT, J [1 ]
GARBER, GE [1 ]
机构
[1] OTTAWA GEN HOSP,DIV INFECT DIS,501 SMYTH RD,OTTAWA K1H 8L6,ONTARIO,CANADA
关键词
D O I
10.1016/S0196-6553(05)80234-2
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Background: Water distribution systems have been demonstrated to be a major source of nosocomial legionellosis. We describe an outbreak in our institution in which a novel source of Legionella pneumophila was identified in the plumbing system. Methods: After an outbreak of 10 cases of legionellosis in our hospital, recommended measures including superheating of the hot water to 80-degrees-C, hyperchlorination to 2 ppm, and flushing resulted in no new cases in the following 5 years. Recently, despite these control measures, three new cases occurred. Surveillance cultures of shower heads and water tanks were negative; cultures of tap water samples remained positive. This prompted a search for another reservoir. Shock absorbers installed within water pipes to decrease noise were suspected. Results: One hundred twenty-five shock absorbers were removed and cultured. A total of 13 (10%) yielded heavy growth of L. pneumophila (serogroup 1). Since their removal, no new cases have been found and the percentage of positive results of random tap water culture has dropped from 20% to 5%. Conclusions: This is the first report that identifies shock absorbers as a possible reservoir for L pneumophila. We recommend that institutions with endemic legionellosis assess the water system for possible removal of shock absorbers.
引用
收藏
页码:305 / 309
页数:5
相关论文
共 50 条
  • [11] A PLASMID IN LEGIONELLA-PNEUMOPHILA
    KNUDSON, GB
    MIKESELL, P
    INFECTION AND IMMUNITY, 1980, 29 (03) : 1092 - 1095
  • [12] EFFECTS OF METALS ON LEGIONELLA-PNEUMOPHILA GROWTH IN DRINKING-WATER PLUMBING SYSTEMS
    STATES, SJ
    CONLEY, LF
    CERASO, M
    STEPHENSON, TE
    WOLFORD, RS
    WADOWSKY, RM
    MCNAMARA, AM
    YEE, RB
    APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1985, 50 (05) : 1149 - 1154
  • [13] GENETICS OF LEGIONELLA-PNEUMOPHILA
    MINTZ, CS
    SHUMAN, HA
    MICROBIOLOGICAL SCIENCES, 1988, 5 (10): : 292 - 295
  • [14] SURVIVAL OF LEGIONELLA-PNEUMOPHILA
    BARKER, J
    TILL, DH
    MEDICAL LABORATORY SCIENCES, 1986, 43 (04): : 388 - 389
  • [15] PROTEINASES OF LEGIONELLA - PHENYLALANINEAMINOPEPTIDASE OF LEGIONELLA-PNEUMOPHILA
    GULNIK, SV
    YUSUPOVA, MP
    LAVRENOVA, GI
    TARTAKOVSKY, IS
    PROZOROVSKY, SV
    STEPANOV, VM
    JOURNAL OF GENERAL MICROBIOLOGY, 1986, 132 : 387 - 392
  • [16] LEGIONELLA-PNEUMOPHILA IN A WATER DISTRIBUTION-SYSTEM
    STICHTGROH, V
    EMMERLING, P
    DOLL, W
    EUROPEAN JOURNAL OF CLINICAL MICROBIOLOGY & INFECTIOUS DISEASES, 1985, 4 (06) : 591 - 592
  • [17] SHOCK-ABSORBERS CRITIQUED
    YEAPLE, F
    DESIGN ENGINEERING-LONDON, 1980, 51 (07): : 41 - 44
  • [18] FERRIC REDUCTASES OF LEGIONELLA-PNEUMOPHILA
    POCH, MT
    JOHNSON, W
    BIOMETALS, 1993, 6 (02) : 107 - 114
  • [19] SYSTEMATIC PROPAGATION OF LEGIONELLA-PNEUMOPHILA
    不详
    SOUTH AFRICAN MEDICAL JOURNAL, 1981, 59 (14): : 475 - 475
  • [20] AEROSOL INFECTIVITY OF LEGIONELLA-PNEUMOPHILA
    ZIMMERMAN, L
    NEW ENGLAND JOURNAL OF MEDICINE, 1979, 301 (18): : 1004 - 1004