PLUMBING SYSTEM SHOCK-ABSORBERS AS A SOURCE OF LEGIONELLA-PNEUMOPHILA

被引:2
|
作者
MEMISH, ZA [1 ]
OXLEY, C [1 ]
CONTANT, J [1 ]
GARBER, GE [1 ]
机构
[1] OTTAWA GEN HOSP,DIV INFECT DIS,501 SMYTH RD,OTTAWA K1H 8L6,ONTARIO,CANADA
关键词
D O I
10.1016/S0196-6553(05)80234-2
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Background: Water distribution systems have been demonstrated to be a major source of nosocomial legionellosis. We describe an outbreak in our institution in which a novel source of Legionella pneumophila was identified in the plumbing system. Methods: After an outbreak of 10 cases of legionellosis in our hospital, recommended measures including superheating of the hot water to 80-degrees-C, hyperchlorination to 2 ppm, and flushing resulted in no new cases in the following 5 years. Recently, despite these control measures, three new cases occurred. Surveillance cultures of shower heads and water tanks were negative; cultures of tap water samples remained positive. This prompted a search for another reservoir. Shock absorbers installed within water pipes to decrease noise were suspected. Results: One hundred twenty-five shock absorbers were removed and cultured. A total of 13 (10%) yielded heavy growth of L. pneumophila (serogroup 1). Since their removal, no new cases have been found and the percentage of positive results of random tap water culture has dropped from 20% to 5%. Conclusions: This is the first report that identifies shock absorbers as a possible reservoir for L pneumophila. We recommend that institutions with endemic legionellosis assess the water system for possible removal of shock absorbers.
引用
收藏
页码:305 / 309
页数:5
相关论文
共 50 条
  • [1] LEGIONELLA-PNEUMOPHILA
    KURTZ, JB
    ANNALS OF OCCUPATIONAL HYGIENE, 1988, 32 (01): : 59 - 61
  • [2] HEAT-SHOCK RESPONSE IN LEGIONELLA-PNEUMOPHILA
    LEMA, MW
    BROWN, A
    BUTLER, CA
    HOFFMAN, PS
    CANADIAN JOURNAL OF MICROBIOLOGY, 1988, 34 (10) : 1148 - 1153
  • [3] EFFICACY OF OZONE IN ERADICATION OF LEGIONELLA-PNEUMOPHILA FROM HOSPITAL PLUMBING FIXTURES
    EDELSTEIN, PH
    WHITTAKER, RE
    KREILING, RL
    HOWELL, CL
    APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1982, 44 (06) : 1330 - 1334
  • [4] THE INTRACELLULAR MULTIPLICATION OF LEGIONELLA-PNEUMOPHILA IN PROTOZOA FROM HOSPITAL PLUMBING SYSTEMS
    NAHAPETIAN, K
    CHALLEMEL, O
    BEURTIN, D
    DUBROU, S
    GOUNON, P
    SQUINAZI, F
    RESEARCH IN MICROBIOLOGY, 1991, 142 (06) : 677 - 685
  • [5] ULTRASTRUCTURE OF LEGIONELLA-PNEUMOPHILA
    RODGERS, FG
    JOURNAL OF CLINICAL PATHOLOGY, 1979, 32 (12) : 1195 - 1202
  • [6] PLEOMORPHISM OF LEGIONELLA-PNEUMOPHILA
    KATZ, SM
    HASHEMI, S
    BROWN, KR
    HABIB, WA
    HAMMEL, JM
    ULTRASTRUCTURAL PATHOLOGY, 1984, 6 (2-3) : 117 - 129
  • [7] LEGIONELLA-PNEUMOPHILA PERITONITIS
    DOURNON, E
    BURE, A
    KEMENY, JL
    POURRIAT, JL
    VALEYRE, D
    LANCET, 1982, 1 (8285): : 1363 - 1363
  • [8] PHAGOCYTOSIS OF LEGIONELLA-PNEUMOPHILA
    HALABLAB, MA
    RICHARDS, L
    BAZIN, MJ
    JOURNAL OF MEDICAL MICROBIOLOGY, 1990, 33 (02) : 75 - 83
  • [9] LEGIONELLA-PNEUMOPHILA SEROTYPES
    EDELSTEIN, P
    LANCET, 1979, 1 (8110): : 271 - 271
  • [10] LEGIONELLA-PNEUMOPHILA IN TOURISTS
    COSSAR, JH
    DEWAR, RD
    FALLON, RJ
    GRIST, NR
    REID, D
    PRACTITIONER, 1982, 226 (1371) : 1543 - &