FURTHER-STUDIES OF ANOMALOUS PHENOMENA IN DIELECTRIC-LOSS MEASUREMENTS - TRANSFORMER BUSHINGS MODEL

被引:6
|
作者
LEVI, R
MANIFASE, S
机构
[1] Doble Engineering Company, Watertown, MA
关键词
D O I
10.1109/61.400841
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The results of sc dielectric-loss measurements on bushings mounted in certain three-phase transformers, a not performed in accordance with the prescribed procedure, can deviate significantly from the correct values. An investigation of the incorrect procedure has shown that the capacitive coupling between adjacent windings and the lower portion of the bushings influenced the results such that dielectric losses were elevated to several times their normal values. Experience has shown that bushing test results on an three phases form a pattern hi cases where this phenomena is evident. Results of investigative field measurements showing this phenomena are presented, find an explanation of its origin is given.
引用
收藏
页码:889 / 895
页数:7