AN ADAPTIVE SCHEME FOR DIGITAL PROTECTION OF POWER TRANSFORMERS

被引:0
|
作者
GIRGIS, AA
HART, DG
BINCHANG, W
机构
关键词
DIGITAL TRANSFORMER PROTECTION; KALMAN FILTERING; ADAPTIVE RELAYING;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the development of an adaptive scheme for digital differential protection of power transformers. First, the transformer status is monitored to decide if the transformer is disconnected or is in normal operating condition. When the transformer is energized, a two-state Kalman filter model monitors the transformer during normal operating conditions. When a transient is detected, a three-state Kalman filter model is initiated to obtain the best estimate of the phasor quantities in the shortest period of time. These phasors are used to decide if a fault in the transformer exists. If the transformer was disconnected and switched on, the current waveform would include inrush current or a combination of inrush and fault currents. In this case a five-state Kalman filter model is initiated to obtain the best estimates of the dc offset, fundamental and second harmonic phasors. These phasors are used to decide if the switching occurs in the presence of an internal fault. Second, the current transformer ratios and tap values are included in the algorithm to obtain an adaptive percentage differential characteristic. This adaptive scheme was tested on data obtained in the laboratory and proved to be highly accurate and fast.
引用
收藏
页码:546 / 553
页数:8
相关论文
共 50 条
  • [1] DESIGN OF A DIGITAL PROTECTION SCHEME FOR POWER TRANSFORMERS USING OPTIMAL STATE OBSERVERS
    MURTY, YVVS
    SMOLINSKI, WJ
    SIVAKUMAR, S
    IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1988, 135 (03) : 224 - 230
  • [2] FAST ALGORITHM FOR DIGITAL PROTECTION OF POWER TRANSFORMERS
    RAHMAN, MA
    DASH, PK
    IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1982, 129 (02) : 79 - 85
  • [3] Protection of power plant transformers using digital technology
    Mozina, CJ
    1999 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE, VOLS 1 & 2, 1999, : 421 - 432
  • [4] A Novel Flux-Based Protection Scheme for Power Transformers
    Haghjoo, Farhad
    Mostafaei, Mohsen
    Mohammadzadeh, Mohsen
    9TH POWER SYSTEMS PROTECTION AND CONTROL CONFERENCE (PSPC2015), 2015, : 25 - 30
  • [5] Time domain differential protection scheme applied to power transformers
    Moravej, Z.
    Ebrahimi, A.
    Pazoki, M.
    Barati, M.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 154
  • [6] Differential protection scheme for power transformers using matched wavelets
    Roy, Arpita
    Singh, Devender
    Misra, Rakesh Kumar
    Singh, Amit
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (12) : 2423 - 2437
  • [7] A low voltage microgrid protection scheme using digital instrument transformers
    Sharma, Jigyesh
    Sidhu, Tarlochan S.
    IET RENEWABLE POWER GENERATION, 2024, 18 (06) : 1007 - 1018
  • [9] An adaptive protection scheme for shipboard power systems
    Amoda, Oluwaseun. A.
    Schulz, Noel. N.
    2007 IEEE ELECTRIC SHIP TECHNOLOGIES SYMPOSIUM, 2007, : 225 - +
  • [10] AC Microgrids Protection: A Digital Coordinated Adaptive Scheme
    Hussain, Noor
    Khayat, Yousef
    Golestan, Saeed
    Nasir, Mashood
    Vasquez, Juan C.
    Guerrero, Josep M.
    Kauhaniemi, Kimmo
    APPLIED SCIENCES-BASEL, 2021, 11 (15):