Impact of Power Transformer Oil-Temperature on the Measurement Uncertainty of All-Acoustic Non-Iterative Partial Discharge Location

被引:10
|
作者
Poluzanski, Vladimir [1 ,2 ]
Kartalovic, Nenad [2 ]
Nikolic, Bosko [1 ]
机构
[1] Univ Belgrade, Sch Elect Engn, 73 Kralja Aleksandra Blvd, Belgrade 11120, Serbia
[2] Univ Belgrade, Elect Engn Inst Nikola Tesla, 8a Koste Glavinica St, Belgrade 11040, Serbia
关键词
partial discharge; acoustic emission; power transformer; transformer oil temperature; measurement uncertainty; nonlinearity; monte carlo filtering; metrology; software;
D O I
10.3390/ma14061385
中图分类号
O64 [物理化学(理论化学)、化学物理学];
学科分类号
070304 ; 081704 ;
摘要
In this paper, the influence of the variation in transformer oil temperature on the accuracy of the all-acoustic non-iterative method for partial discharge location in a power transformer is researched. The research can improve power transformers' testing and monitoring, particularly given the large transformer oil temperature variations during real-time monitoring. The research is based on quantifying the contribution of oil temperature to the standard combined measurement uncertainty of the non-iterative algorithm by using analytical, statistical, and Monte Carlo methods. The contribution can be quantified and controlled. The contribution varied significantly with different mutual placements of partial discharge and acoustic sensors. The correlation between the contribution and the mean distance between partial discharge and acoustic sensors was observed. Based on these findings, the procedure to quantify and control the contribution in practice was proposed. The procedure considers the specificity of the method's mathematical model (the assumption that the oil temperature is constant), the non-iterative algorithm's nonlinearity, and the large variations in transformer oil temperature. Existing studies did not consider the significant effect of the oil temperature on the combined measurement uncertainty of partial discharge location influenced by those phenomena. The research is limited to partial discharge located in the transformer oil.
引用
收藏
页码:1 / 18
页数:18
相关论文
共 17 条
  • [1] Algorithm for Calculating Influence of Power Transformer Oil Temperature Change on the Accuracy of All-Acoustic Non-Iterative Partial Discharge Localization
    Poluzanski, Vladimir S.
    Kovacevic, Uros D.
    Nikolic, Bosko D.
    FME TRANSACTIONS, 2018, 46 (02): : 183 - 193
  • [2] A non-iterative partial discharge source location method for transformers employing acoustic emission techniques
    Kundu, Prasanta
    Kishore, N. K.
    Sinha, A. K.
    APPLIED ACOUSTICS, 2009, 70 (11-12) : 1378 - 1383
  • [3] Comparative Examination of Iterative and Non-Iterative Algorithms for Partial Discharge Location Approximation in High Voltage Equipment
    Szirtes, Mate
    Cselko, Richard
    2019 16TH WORKSHOP ON POSITIONING, NAVIGATION AND COMMUNICATIONS (WPNC 2019), 2019,
  • [4] Transformer partial discharge location technology based on gradient oil temperature
    Yu, Ruidong
    Zhang, Zhousheng
    FRONTIERS IN ENERGY RESEARCH, 2024, 12
  • [5] Analysis of partial discharge in oil filled power transformer with electro-acoustic method
    Gacek, Zbigniew
    Szadkowski, Marek
    Malitowski, Grzegorz
    Witos, Franciszek
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 287 - 290
  • [6] Location and recognition of partial discharge sources in a power transformer using advanced acoustic emission method
    Ziomek, Waldemar
    Kuffelz, Edmund
    Sikorski, Wojciech
    Staniek, Pawel
    Siodla, Krzysztof
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 20 - 23
  • [7] Effects of Transformer-Oil Temperature on Amplitude and Peak Frequency of Partial Discharge Acoustic Signals
    Shanker, Tangella Bhavani
    Nagamani, Hebbale Narasimhaiah
    Antony, Deepthi
    Punekar, Gururaj S.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3227 - 3229
  • [8] The Impact of Temperature on the Partial Discharge Characteristics of Moving Charged Metal Particles in Transformer Oil
    Li, Xingxing
    Tang, Ju
    Ma, Shouxiao
    Yao, Qiang
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [9] Development of partial discharge location system in oil-filled transformer considering acoustic wave propagation properties
    Murayama, Hiroki
    Katayama, Tomohiko
    Yamada, Kyohei
    Kozako, Masahiro
    Hikita, Masayuki
    Kashine, Kenji
    Nakamura, Itaru
    Koide, Hidenobu
    Proceedings of the International Symposium on Electrical Insulating Materials, 2011, : 273 - 276
  • [10] Development of Partial Discharge Location System in Oil-Filled Transformer Considering Acoustic Wave Propagation Properties
    Murayama, Hiroki
    Katayama, Tomohiko
    Yamada, Kyohei
    Kozako, Masahiro
    Hikita, Masayuki
    Kashine, Kenji
    Nakamura, Itaru
    Koide, Hidenobu
    PROCEEDINGS OF 2011 INTERNATIONAL CONFERENCE ON ELECTRICAL INSULATING MATERIALS (ISEIM), 2011, : 273 - 276