EVALUATION AND COMPARISON ON THE PERFORMANCE OF COOLING TOWERS WITH AIR DEFLECTORS

被引:0
|
作者
Sun, F. Zh. [1 ]
Dai, Zh. H. [1 ]
Wang, H. G.
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
来源
PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON POWER ENGINEERING 2009 (ICOPE-09), VOL 3 | 2009年
关键词
Air deflector; Cross-wind; engineering modification; INTAKE FLOW-RATE; HEAT-TRANSFER PERFORMANCE; WIND;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The performance of the cooling tower with engineering modification in a 300MW unit was analyzed. The operational data of two cooling towers that one used the air optimization technology and the other did not were investigated and compared. The results show that air deflectors that are fixed around the inlet of the cooling tower can reduce the adverse effect of cross-winds, have good influence on the uniformity of inlet air and then improve the performance of cooling tower. The relative variation of temperature difference as a new theoretical index was given to evaluate the performance of cooling towers under cross-wind conditions. Suggestions were proposed to evaluate the performance of cooling towers in actual operation.
引用
收藏
页码:243 / 246
页数:4
相关论文
共 50 条
  • [1] THERMAL PERFORMANCE EVALUATION OF SEAWATER COOLING TOWERS
    Sharqawy, Mostafa H.
    Husain, Iqbal S.
    Zubair, Syed M.
    Lienhard, John H.
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2011, VOL 1, 2012, : 371 - +
  • [2] Comparison and evaluation of air cooling and water cooling in resource consumption and economic performance
    Zhang, Haitian
    Feng, Xiao
    Wang, Yufei
    ENERGY, 2018, 154 : 157 - 167
  • [3] A review on the performance evaluation of natural draft dry cooling towers and possible improvements via inlet air spray cooling
    Sun, Yubiao
    Guan, Zhiqiang
    Hooman, Kamel
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 79 : 618 - 637
  • [4] Effect Mechanism of Ambient Air Parameters on the Thermal Performance for Cooling Towers
    Zhang, Lei
    Zhou, Jun
    Zuo, Simeng
    An, Guangyao
    Lang, Jinhua
    Yuan, Wei
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2024, 16 (01)
  • [5] Effect mechanism of air deflectors on the cooling performance of dry cooling tower with vertical delta radiators under crosswind
    Zhao, Yuanbin
    Long, Guoqing
    Sun, Fengzhong
    Li, Yan
    Zhang, Cuijiao
    Liu, Jiabin
    ENERGY CONVERSION AND MANAGEMENT, 2015, 93 : 321 - 331
  • [6] Evaluation of cooling towers.
    Geibel, C
    ZEITSCHRIFT DES VEREINES DEUTSCHER INGENIEURE, 1924, 68 : 152 - 153
  • [7] Effects of different wind deflectors on wind loads for extra-large cooling towers
    Ke, S. T.
    Zhu, P.
    Ge, Y. J.
    WIND AND STRUCTURES, 2019, 28 (05) : 299 - 313
  • [8] Hybrid Cooling Towers in Economic Comparison with Wet and Dry Cooling Towers.
    Alt, W.
    Maeule, R.
    VGB-Kraftwerkstechnik, 1987, 67 (08): : 763 - 768
  • [9] Influences of Lateral Double-Layered Deflectors on Cooling Performance of Air-Cooled Condenser
    HUANG Wenhui
    HUANG Xianwei
    YANG Lijun
    DU Xiaoze
    Journal of Thermal Science, 2021, 30 (06) : 2164 - 2177
  • [10] Influences of Lateral Double-Layered Deflectors on Cooling Performance of Air-Cooled Condenser
    Wenhui Huang
    Xianwei Huang
    Lijun Yang
    Xiaoze Du
    Journal of Thermal Science, 2021, 30 : 2164 - 2177