A Fault Clearing Method in Converter-Dominated Microgrids With Conventional Protection Means

被引:158
作者
Oureilidis, Konstantinos O. [1 ]
Demoulias, Charis S. [1 ]
机构
[1] Aristotle Univ Thessaloniki, Dept Elect & Comp Engn, Elect Machines Lab, Thessaloniki 54124, PC, Greece
关键词
Distributed energy resources (DERs); droop control; microgrid protection; overcurrent devices; POWER CONVERTERS; STRATEGY; RELAY; PLL;
D O I
10.1109/TPEL.2015.2476702
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The integration of converter-interfaced distributed generation in microgrids has raised several technical issues, including the successful operation of protective devices during faults. The protection issue is associated with the lack of large current injection during a fault, due to limits imposed by the semiconductor switches. This paper proposes a fault-detection and clearing control strategy method for symmetrical and asymmetrical line faults in a looped microgrid. The protection devices are simple overcurrent devices with the same settings, due to the looped microgrid topology. The proposed method is applied without using any kind of physical communication. The fault is detected by measuring indirectly the microgrid impedance. After the fault identification, the distributed energy resources (DERs) adjust their control in order to inject a current proportional to the measured microgrid impedance, according to a droop curve. This means that the DER closer to the fault injects a relatively larger current, achieving by this way a selective coordination of the protection means. The effectiveness of the proposed control strategy is evaluated through detailed simulation and experimental tests.
引用
收藏
页码:4628 / 4640
页数:13
相关论文
共 35 条
[1]  
[Anonymous], 2011, SACE TMAX XT NEW LOW
[2]  
[Anonymous], IET J ENG
[3]  
[Anonymous], LOW VOLTAGE MOLDED C
[4]  
[Anonymous], 2009, IEEE INT C POW SYST
[5]  
[Anonymous], 501602004 EN
[6]  
[Anonymous], 1997, C371121996 IEEE
[7]  
[Anonymous], 2009, PROC CIRED
[8]  
Best R. J., 2012, P IEEE 44 INT U POW, P1
[9]   Development of adaptive protection scheme for distribution systems with high penetration of distributed generation [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :56-63
[10]   A new single-phase PLL structure based on second order generalized integrator [J].
Ciobotaru, Mihai ;
Teodorescu, Remus ;
Blaabjerg, Frede .
2006 IEEE POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-7, 2006, :361-+