Empirical Relationships Between Air-Load Break Switch Parameters and Interrupting Performance

被引:17
|
作者
Stoa-Aanensen, Nina Sasaki [1 ,2 ]
Runde, Magne [2 ]
Jonsson, Erik [2 ]
Teigset, Anders Dall'Osso [3 ]
机构
[1] Norwegian Univ Sci & Technol NTNU, Dept Elect Power Engn, N-7491 Trondheim, Norway
[2] SINTEF Energy Res, N-7465 Trondheim, Norway
[3] Sweco, N-0212 Oslo, Norway
关键词
Load break switch; logistic regression; medium voltage (MV); switchgear; thermal interruption;
D O I
10.1109/TPWRD.2015.2435804
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A simple gas-blow switch, consisting of an axisymmetric tulip/pin contact and a cylindrical polytetrafluoroethylene (PTFE) nozzle, has been used for empirical studies of medium-voltage load current interruption in air. Only the thermal phase of the interruption is considered. Based on the results of more than 3000 interruption tests, a logistic regression model has been developed to describe the relationships between the switch design and test circuit parameters, and the current interruption capability. The most important design recommendation is that the inner diameter of the nozzle should be only slightly larger than the pin contact. The upstream overpressure needed for successful interruption increases as a polynomial function of degree 0.5-1 with the rate of rise of recovery voltage and of degree 2-3 with increasing current.
引用
收藏
页码:278 / 285
页数:8
相关论文
共 50 条
  • [1] Current Interruption in Air for a Medium-Voltage Load Break Switch
    Jonsson, Erik
    Aanensen, Nina Sasaki
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) : 870 - 875
  • [2] Arcing Voltage for a Medium-Voltage Air Load Break Switch
    Stoa-Aanensen, Nina
    Runde, Magne
    Teigset, Anders Dall'Osso
    PROCEEDINGS OF THE 2015 SIXTY-FIRST IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS (HOLM), 2015, : 101 - 106
  • [3] Empirical relationships between thermoelastic parameters
    Vidyarthi, P. K.
    Singh, P. K.
    INDIAN JOURNAL OF PURE & APPLIED PHYSICS, 2016, 54 (07) : 449 - 452
  • [4] Air-Flow Investigation for a Medium-Voltage Load Break Switch
    Aanensen, Nina Sasaki
    Jonsson, Erik
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 299 - 306
  • [5] Comparison of Different Air Flow Concepts for a Medium Voltage Load Break Switch
    Stoa-Aanensen, Nina Sasaki
    Jonsson, Erik
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (02) : 508 - 513
  • [6] Empirical relationships between some manufacturing practices and performance
    Karim, M. A.
    Smith, A. J. R.
    Halgamuge, S.
    INTERNATIONAL JOURNAL OF PRODUCTION RESEARCH, 2008, 46 (13) : 3583 - 3613
  • [7] Effect of Magnetic Field Strength and Admixture Gas on Current Interrupting Capability of a CO2 Rotary-Arc Load-Break Switch
    Matsumura, Toshiro
    Yokomizu, Yasunobu
    Kanda, Daisuke
    Kumazawa, Takao
    Furuhata, Takashi
    Mitsukuchi, Kunio
    ELECTRICAL ENGINEERING IN JAPAN, 2009, 167 (02) : 21 - 27
  • [8] Effect of magnetic field strength and admixture gas on current interrupting capability of CO2 rotary-arc load-break switch
    Matsumura, Toshiro
    Yokomizu, Yasunobu
    Kanda, Daisuke
    Kumazawa, Takao
    Furuhata, Takashi
    Mitsukuchi, Kunio
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 2009, 167 (02): : 21 - 27
  • [9] Relationships between moment magnitude and fault parameters:theoretical and semi-empirical relationships
    王海云
    陶夏新
    EarthquakeEngineeringandEngineeringVibration, 2003, 2 (02) : 201 - 211
  • [10] Relationships between moment magnitude and fault parameters: theoretical and semi-empirical relationships
    Haiyun Wang
    Xiaxin Tao
    Earthquake Engineering and Engineering Vibration, 2003, 2 (2) : 201 - 211