Performance analysis and improvement of air-to-water chiller for application in wide ambient temperature range

被引:11
|
作者
Ding, GL [1 ]
Fu, L [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Power & Energy Engn, Inst Refrigerat & Cryogen, Shanghai 200030, Peoples R China
关键词
air-to-water chiller; auxiliary parallel capillary tube; variable condenser air flow; control strategy;
D O I
10.1016/j.applthermaleng.2004.03.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
Some air-to-water chillers can work well in summer but meet problems in low temperature ambience. When the ambient temperature decreases into a certain level, the cooling capacity of the chiller drops rapidly or in severe situation the compressor stops running. In order to expand the applicable condition, performance variation of an air-to-water chiller in a wide range of ambient temperature is analyzed based on simulation, and a new type air-to-water chiller is presented, in which an auxiliary capillary tube is installed parallel to the thermostatic expansion valve (TEV) as well as variable number condenser fans are used. A suitable control strategy of the chiller is proposed, and the performance of the chiller across an assorted range of ambient temperature range is also predicted. The operation of the capillary tube and the cooling fans are found to be a function of the coolant temperatures and the unique chiller operation has been tested for a period of more than a year. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:135 / 145
页数:11
相关论文
共 50 条
  • [1] Performance analysis and optimisation of the chiller-air handling units system with a wide range of ambient temperature
    Zulkafli, Nur I.
    Sukri, Mohamad F.
    Tahir, Musthafah Mohd
    Muhajir, Asjufri
    Hanak, Dawid P.
    CLEANER ENGINEERING AND TECHNOLOGY, 2023, 14
  • [2] AIR-TO-WATER HEAT-PUMP CHILLER SYSTEM - AN ANALYSIS OF VARIANCE IN ANNUAL ELECTRICITY CONSUMPTION
    AGAWA, M
    KOMATSU, M
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (12): : 70 - 70
  • [3] AN OPTICAL SPATIAL FILTER FOR ACHIEVING WIDE DYNAMIC RANGE IN AIR-TO-WATER OPTICAL TRANSMISSION
    SWARNER, WG
    APPLIED OPTICS, 1970, 9 (02): : 507 - &
  • [4] Performance Analysis of Air-to-Water Optical Wireless Communication Using SPADs
    Nabavi, Pooya
    Yuksel, Murat
    2019 IEEE GLOBAL COMMUNICATIONS CONFERENCE (GLOBECOM), 2019,
  • [5] Performance Analysis of Air-to-Water Heat Pump in Latvian Climate Conditions
    Kazjonovs, Janis
    Sipkevics, Andrejs
    Jakovics, Andris
    Dancigs, Andris
    Bajare, Diana
    Dancigs, Leonards
    ENVIRONMENTAL AND CLIMATE TECHNOLOGIES, 2014, 14 (01) : 18 - 22
  • [6] Heating Performance Analysis of an Air-to-Water Heat Pump Using Underground Air for Greenhouse Farming
    Lim, Taesub
    Baik, Yong-Kyu
    Kim, Daeung Danny
    ENERGIES, 2020, 13 (15)
  • [7] PART-LOAD PERFORMANCE ANALYSIS OF AIR-TO-WATER HEAT-PUMP SYSTEMS
    TASSOU, SA
    MARQUAND, CJ
    WILSON, DR
    JOURNAL OF THE INSTITUTE OF ENERGY, 1984, 57 (432): : 364 - 367
  • [8] Experimental analysis on air-to-water sound transmission loss in shallow water
    ZHANG Lingshan
    PENG Zhaohui
    WANG Guangxu
    LUO Wenyu
    ChineseJournalofAcoustics, 2017, 36 (02) : 217 - 230
  • [9] Experimental analysis on air-to-water sound transmission loss in shallow water
    Peng, Zhaohui
    Zhang, Lingshan
    Wang, Guangxu
    2ND FRANCO-CHINESE ACOUSTIC CONFERENCE (FCAC 2018), 2019, 283
  • [10] Influence of water-side fouling on air-to-water heat exchanger performance
    Bowman, CF
    PROCEEDINGS OF THE AMERICAN POWER CONFERENCE, VOL. 60, PTS I & II, 1998, : 969 - 974