Practical Issues of Online Partial Discharge Measurement for In-service Substation Transformer

被引:0
|
作者
Seo, Junhyuck [1 ]
Ma, Hui [1 ]
Saha, Tapan K. [1 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, St Lucia, Qld 4072, Australia
关键词
Insulation; Partial discharge (PD); peak detection; sampling rate; transformer; wavelet transform; INSULATION CONDITION;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) measurement provides a means for online monitoring and assessing the insulation condition of a substation transformer. However, the characteristics of PD pulses may vary depending on various factors such as geometry of insulation system, types of PD sources, properties of PD sensors and measurement systems, and sampling rate. Among these factors, sampling rate of PD measurement system has significant effect on the acquisition of PD waveform and the extraction of PD signals. This paper evaluated different sampling rates for online PD measurement of in-service substation transformers. The results of different sampling rates are compared in terms of the waveforms of the acquired PD signals, properties of the extracted PD signals, formation of PD patterns, and dataset sizes for proper PD evaluation, which will be presented in the paper. Other important issues such as online PD measurement system setup, filtration of power frequency harmonics, and PD signal extraction using wavelet transform are also discussed in this paper.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Online measurement of transformer partial discharge
    Wang Baobao
    Yang Yang
    CIS WORKSHOPS 2007: INTERNATIONAL CONFERENCE ON COMPUTATIONAL INTELLIGENCE AND SECURITY WORKSHOPS, 2007, : 906 - +
  • [2] Off-line Partial Discharge Measurement and Localization for a 33/6.9 kV In-Service Transformer
    Selva, A. M.
    Azis, N.
    Yousof, M. F. M.
    Sallehuddin, N.
    Tadam, A. B.
    Saliang, A. D.
    2022 9TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2022, : 505 - 508
  • [3] Partial discharge and the measurement in gas insulated substation
    Han, Xiaolian
    Feng, Yunping
    Qiu, Yuchang
    Chen, Jinqing
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 1995, 29 (03): : 30 - 38
  • [4] IN-SERVICE PARTIAL DISCHARGE TESTING OF GENERATOR INSULATION
    KURTZ, M
    STONE, GC
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1979, 14 (02): : 94 - 100
  • [5] Practical location method of transformer partial discharge
    Li, YQ
    Lu, FC
    Xie, HL
    Yin, M
    2004 International Conference on Power System Technology - POWERCON, Vols 1 and 2, 2004, : 1371 - 1374
  • [6] Practical Partial Discharge Measurement on Electrical Equipment
    Kularatna, Nihal
    IEEE ELECTRICAL INSULATION MAGAZINE, 2024, 40 (01) : 49 - 50
  • [7] Probabilistic Wavelet Transform for Partial Discharge Measurement of Transformer
    Seo, Junhyuck
    Ma, Hui
    Saha, Tapan
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (02) : 1105 - 1117
  • [8] Design and realization of measurement system of partial discharge in transformer
    Liu, Yunpeng
    Lu, Fangcheng
    Li, Yanqing
    Chen, Zhiye
    Gaodianya Jishu/High Voltage Engineering, 2002, 28 (01):
  • [9] Convenient Online Approach to Multisource Partial Discharge Localization in Transformer
    Cai, Junyi
    Zhou, Lijun
    Zhang, Yulin
    Wang, Dongyang
    Liao, Wei
    Zhang, Chenqingyu
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (09) : 9440 - 9450
  • [10] Study of propagation of transformer partial discharge pulses in the coupling network for a 500 kV substation
    Dong, XZ
    Zhu, DH
    Wang, CC
    Tan, KX
    Liu, YL
    IEEE POWER ENGINEERING SOCIETY - 1999 WINTER MEETING, VOLS 1 AND 2, 1999, : 1000 - 1005