Improved DPC Strategy of Grid-connected Inverters under Unbalanced and Harmonic Grid Conditions

被引:0
|
作者
Shen, Yongbo [1 ]
Nian, Heng [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou, Zhejiang, Peoples R China
关键词
direct power control; grid-connected voltage source inverter; unbalanced and harmonic grid; vector PI controller; DIRECT POWER-CONTROL; CURRENT CONTROLLER; COMPENSATION; FILTERS;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an improved direct power control (DPC) strategy for grid-connected voltage source inverter (VSI) under unbalanced and harmonic grid voltage conditions. Based on the mathematic model of VSI with the negative sequence, 5th and 7th harmonic voltage components consideration, a PI controller is used in the proposed DPC strategy to achieve the average output power regulation. Furthermore, vector PI controller with the resonant frequency tuned at the two times and six times grid fundamental frequency is adopted to regulate both negative and harmonic components, and then two alternative targets of the balanced/sinusoidal current and smooth active/reactive output power can be achieved. Finally, simulation results based on Matlab validate the availability of the proposed DPC strategy.
引用
收藏
页码:1566 / 1570
页数:5
相关论文
共 50 条
  • [1] Grid Voltage Modulated Control of Grid-Connected Voltage Source Inverters under Unbalanced Grid Conditions
    Li, Mingshen
    Gui, Yonghao
    Vasquez, Juan C.
    Guerrero, Josep M.
    IECON 2017 - 43RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2017, : 2510 - 2515
  • [2] An Improved Voltage Support Strategy of Grid-Connected Inverter under Unbalanced Grid Condition
    Wang Wei
    Li Pengfei
    Li Fen
    Liu Guihua
    2017 IEEE TRANSPORTATION ELECTRIFICATION CONFERENCE AND EXPO, ASIA-PACIFIC (ITEC ASIA-PACIFIC), 2017, : 735 - 740
  • [3] Study on control strategy of grid-connected PV inverter under unbalanced grid conditions
    Liang, H. (lianghying@163.com), 1600, Science Press (34):
  • [4] Predictive current control for grid-connected inverters under unbalanced grid voltage
    Nian, H. (nianheng@zju.edu.cn), 2013, Power System Technology Press (37):
  • [5] Harmonic characteristics and control strategies of grid-connected photovoltaic inverters under weak grid conditions
    Zhao, Ensheng
    Han, Yang
    Lin, Xiangyang
    Liu, Enping
    Yang, Ping
    Zalhaf, Amr S.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 142
  • [6] Improved droop control strategy for grid-connected inverters
    Abusara, Mohammad A.
    Sharkh, Suleiman M.
    Guerrero, Josep M.
    SUSTAINABLE ENERGY GRIDS & NETWORKS, 2015, 1 : 10 - 19
  • [7] Improved virtual synchronous control for grid-connected VSCs under grid voltage unbalanced conditions
    Lei SHANG
    Jiabing HU
    Xiaoming YUAN
    Yunhui HUANG
    Journal of Modern Power Systems and Clean Energy, 2019, 7 (01) : 174 - 185
  • [8] Improved virtual synchronous control for grid-connected VSCs under grid voltage unbalanced conditions
    Shang, Lei
    Hu, Jiabing
    Yuan, Xiaoming
    Huang, Yunhui
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2019, 7 (01) : 174 - 185
  • [9] Blackbox Small-signal Modeling of Grid-Connected Inverters under Unbalanced Conditions
    Frances, Airan
    Ramirez, Dionisio
    Uceda, Javier
    2022 IEEE 13TH INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS (PEDG), 2022,
  • [10] Circulating Current Analysis and Suppression for Module Grid-Connected Inverters Under Unbalanced Conditions
    Chen, Hua
    Xing, Xiangyang
    IEEE ACCESS, 2018, 6 : 69120 - 69129