Accurate Time-Domain Fault Location Method on Practically Transposed Transmission Lines

被引:0
|
作者
Lu, Dayou [1 ]
Liu, Yu [1 ]
Wang, Binglin [1 ]
Yi, Lihui [1 ]
Zheng, Xiaodong [2 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Shanghai Jiao Tong Univ, Dept Elect Power Engn, Shanghai 200240, Peoples R China
关键词
fault location; practically transposed transmission line; time domain; Bergeron model; ALGORITHM; SCHEME;
D O I
10.1109/PESGM46819.2021.9638003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Accurate fault location reduces time searching for the fault and the power system operational cost. This paper proposes a time domain fault location method for practically transposed transmission lines. Unlike the ideally transposed lines which assumed to be transposed infinite number of times, the transposed lines in practice is transposed for very limited times. First, the practically transposed line is modeled as a non-homogenous line, consisting of several untransposed line sections. Afterwards, the eigenvalue decomposition is applied to decouple each untransposed line section and the Bergeron model is applied to solve the voltage distribution through the entire non-homogeneous line. Finally, the voltage method is applied to locate the fault using the calculated voltage distribution. Extensive numerical experiments verify that the proposed fault location method presents higher fault location accuracy compared to the existing method that simply assumes ideal transposition for practically transposed transmission lines.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] An accurate unsynchronized fault location method on practically transposed transmission lines with closed-form solutions
    Lu, Dian
    Liu, Yu
    Xie, Yuhao
    Zhu, Yuxuan
    Fan, Rui
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 155
  • [2] Noniterative Parameter-Free Fault Location for Practically Transposed Transmission Lines With Synchronized/Unsynchronized Measurements
    Lu, Dian
    Wan, Jun
    Duan, Mengzhao
    Xie, Yuhao
    Fan, Rui
    Liu, Yu
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2025, 74
  • [3] Novel Method of Time-domain Fault Location for Wind Farm Double-circuit Transmission Lines
    Shu H.
    Deng Y.
    Cao P.
    Zhu M.
    Ma Y.
    An N.
    Dianwang Jishu/Power System Technology, 2023, 47 (04): : 1450 - 1459
  • [4] Time-domain fault location algorithm for parallel transmission lines using unsynchronized currents
    Jiale, S
    Song, GB
    Xu, QQ
    Chao, Q
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2006, 28 (04) : 253 - 260
  • [5] Time-domain based fault location for series compensated transmission lines without requiring fault type
    Ghazizadeh-Ahsaee, Mahdi
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 181
  • [6] Accurate Fault Location for Untransposed/Transposed Transmission Lines Using Sparse Wide-Area Measurements
    Jiao, Xiangqing
    Liao, Yuan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (04) : 1797 - 1805
  • [7] Time-domain fault location algorithm based on one-terminal current of parallel transmission lines
    School of Electric Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    Zhongguo Dianji Gongcheng Xuebao, 2007, 7 (52-57):
  • [8] A novel time-domain method for fault detection and classification in VSC-HVDC transmission lines
    Imani, Amir
    Moravej, Zahra
    Pazoki, Mohammad
    International Journal of Electrical Power and Energy Systems, 2022, 140
  • [9] A novel time-domain method for fault detection and classification in VSC-HVDC transmission lines
    Imani, Amir
    Moravej, Zahra
    Pazoki, Mohammad
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 140
  • [10] Simple and Accurate Time-Domain Method for Internal Fault Location in Layer-type Transformer Windings
    Alzekri, Samir
    Gomez, Pablo
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,