Adaptive concept of controlled islanding in power systems for wide-area out-of-step prediction of synchronous generators based on adaptive tripping index

被引:21
|
作者
Zare, Hassan [1 ]
Yaghobi, Hamid [1 ]
Alinejad-Beromi, Yousef [1 ]
机构
[1] Semnan Univ, Fac Elect & Comp Engn, Semnan, Iran
关键词
power system measurement; distributed power generation; synchronous generators; power system transient stability; rotors; time-domain analysis; correlation methods; machine protection; controlled islanding; power systems; wide-area out-of-step prediction; adaptive tripping index; tripping signal online prediction; wide-area measurement systems; WAMS; WAOOS protection; unstable inter-area oscillations; sinusoidal line; WAOOS transient instability; coherent generator online identification; correlation coefficient evaluation; global tripping signals; GTS; inter-area rotor angle oscillation; inertia frame; critical inter-area angle; IEEE 39-bus test system; time-domain simulations; sampling time; PROTECTION; IDENTIFICATION; STRATEGY;
D O I
10.1049/iet-gtd.2018.0319
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Here, based on wide-area measurement systems (WAMS), an adaptive tripping index (TI) is proposed for online prediction of tripping signals with respect to wide-area out-of-step (WAOOS) protection of synchronous generators. The proposed TI included two different equations consisting of a straight line for unstable inter-area oscillations and a sinusoidal line for WAOOS transient instability. For online identification of coherent generators with respect to inter-area oscillations, based on evaluating the correlation coefficients between generator behaviours, an index is proposed from which the global tripping signals (GTS) are calculated. The GTS consist of the rate of change of inter-area rotor angle oscillation between two oscillating areas in the centre of inertia frame. Actually, the proposed scheme is an adaptive and online index from which the critical inter-area angle is adjusted individually by evaluating GTS at each sampling time gathered from the WAMS data. The proposed strategy is implemented on an IEEE 39-bus test system and its performance is investigated by simulating typical scenarios during time-domain simulations. The results show the effectiveness of the proposed scheme for fast prediction of WAOOS protection in real-time environment.
引用
收藏
页码:3829 / 3836
页数:8
相关论文
共 37 条
  • [1] A Wide-Area Measurement Systems-Based Adaptive Strategy for Controlled Islanding in Bulk Power Systems
    Song, Honglei
    Wu, Junyong
    Wu, Kui
    ENERGIES, 2014, 7 (04): : 2631 - 2657
  • [2] A criterion for out-of-step islanding control based on wide-area disturbed trajectory measurements
    Liu, Fusuo
    Fang, Yongjie
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2008, 32 (17): : 22 - 25
  • [3] Out-of-step prediction logic for wide-area protection based on an autoregressive model
    Yamashita, K
    Kameda, H
    2004 IEEE PES POWER SYSTEMS CONFERENCE & EXPOSITION, VOLS 1 - 3, 2004, : 307 - 312
  • [4] Wide-Area Measurements-Based Out-of-Step Protection System
    Sauhats, Antans
    Utans, Andrejs
    Biela-Dailidovicha, Edite
    2015 56TH INTERNATIONAL SCIENTIFIC CONFERENCE ON POWER AND ELECTRICAL ENGINEERING OF RIGA TECHNICAL UNIVERSITY (RTUCON), 2015,
  • [5] Review of Transient Out-of-step Criterion for Power Systems Based on Wide Area Response
    Zhu C.
    Ma S.
    Zheng C.
    Li P.
    Chen C.
    Dianwang Jishu/Power System Technology, 2022, 46 (07): : 2677 - 2689
  • [6] Neural network based adaptive out-of-step protection strategy for electrical power systems
    Abdelaziz, AY
    Irving, MR
    Mansour, MM
    ElArabaty, AM
    Nosseir, AI
    ENGINEERING INTELLIGENT SYSTEMS FOR ELECTRICAL ENGINEERING AND COMMUNICATIONS, 1997, 5 (01): : 35 - 42
  • [7] Neural network-based adaptive out-of-step protection strategy for electrical power systems
    Abdelaziz, A.Y.
    Irving, M.R.
    Mansour, M.M.
    El-Arabaty, A.M.
    Nosseir, A.I.
    International Journal of Engineering Intelligent Systems for Electrical Engineering and Communications, 1997, 5 (01): : 35 - 42
  • [8] A Predictive Out-of-Step Identification Method Based on Wide-Area Velocity-Acceleration Trajectory
    Zhu, Cunhao
    Mei, Shengwei
    Zhang, Xuemin
    Ma, Shiying
    Liu, Feng
    Li, Penghua
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2024, 39 (01) : 1196 - 1208
  • [9] Comparison of adaptive critic-based and classical wide-area controllers for power systems
    Ray, Swakshar
    Venayagamoorthy, Ganesh Kumar
    Chaudhuri, Balarko
    Majumder, Rajat
    IEEE TRANSACTIONS ON SYSTEMS MAN AND CYBERNETICS PART B-CYBERNETICS, 2008, 38 (04): : 1002 - 1007
  • [10] A summarization of research on wide-area measurement information based power system controlled islanding
    Song, H. (10117346@bjtu.edu.cn), 1600, Power System Technology Press (37):