Partial Discharge Initiated by Free Moving Metallic Particles on GIS Insulator Surface: Severity Diagnosis and Assessment

被引:52
|
作者
Qi, Bo [1 ]
Li, Chengrong [1 ]
Xing, Zhaoliang [1 ]
Wei, Zhen [1 ]
机构
[1] North China Elect Power Univ, Beijing Key Lab High Voltage & EMC, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
关键词
Gas insulated substation; partial discharge; free moving metallic particles; insulator; severity; diagnosis and assessment; GAS;
D O I
10.1109/TDEI.2013.003585
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Free moving metallic particles are one of the most common defects leading to insulation failures in gas insulated substation (GIS) equipment. The present research is designed to diagnose and assess the severity levels of partial discharge (PD) initiated by free moving metallic particles on GIS insulator surface. On a well-established 252 kV GIS experiment platform, long term tests were conducted to observe the entire development process of partial discharge from its very initiation stage till eventual flashover as the applied voltage gradually boosted. Real time measurement was undertaken during the tests to capture the trend curve of partial discharge as a result of test time, scatter plot, histogram, grey-scale map, and time-frequency map of partial discharge. The experimental results indicate that 1) partial discharge provoked by free moving metallic particles in GIS goes through three severity levels, namely, minor discharge, moderate discharge, and threatening discharge; 2) as partial discharge develops, the phase distribution is widening and corresponding shape changes occur in the scatter plot, histogram, grey-scale map, and time-frequency map. It is recommended that the features of phase distribution and the corresponding spectra could be used as important criteria in diagnosing and assessing the severity levels of partial discharge initiated by free moving metallic particles on GIS insulator surface.
引用
收藏
页码:766 / 774
页数:9
相关论文
共 23 条
  • [1] Severity Diagnosis and Assessment of the Partial Discharge Provoked by High-Voltage Electrode Protrusion on GIS Insulator Surface
    Qi, Bo
    Li, Chengrong
    Geng, Bibo
    Hao, Zhen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2363 - 2369
  • [2] Risk assessment of free moving particles in GIS using spectral and partial discharge analysis
    Meijer, S
    Zoetmulder, RGA
    Smit, JJ
    Girodet, A
    CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 403 - 406
  • [3] Severity Diagnosis and Assessment of the Partial Discharge Provoked by Protrusion in GIS
    Li Yuan
    Liu Zehui
    Qu Quanlei
    Yu Xinlong
    Peng Jie
    Li Junhao
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 690 - 692
  • [4] Severity diagnosis and assessment on defects in GIS based on partial discharge detection
    Xie Yaoheng
    Zhou Weihua
    Ye Huisheng
    Liu Yun
    Tang Zhiguo
    Wang Caixiong
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 928 - 931
  • [5] Discharge characteristic investigation on surface discharge initiated by metallic particles attached to gas-insulated substation insulator
    Yao, Rui
    Si, Gangquan
    Zhang, Yanbin
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2016, 11 (02) : 162 - 167
  • [6] Evolution phenomena and features of surface partial discharge initiated by immobilized metal particles on GIS insulators
    Qi, Bo
    Li, Chengrong
    Hao, Zhen
    Geng, Bibo
    Xu, Dangguo
    Liu, Shaoyu
    Deng, Chun
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2011, 31 (01): : 101 - 108
  • [7] Risk assessment basis of Acoustic Signal from Free Moving Metallic Particles in GIS
    Li, Dajian
    Yu, Zhangting
    Chen, Liangyuan
    Zhang, Yubo
    PROCEEDINGS OF THE 2019 14TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2019), 2019, : 1413 - 1418
  • [8] An Assessment Method of Partial Discharge Severity for GIS in Service
    Song H.
    Dai J.
    Li Z.
    Luo L.
    Sheng G.
    Jiang X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (04): : 1231 - 1240
  • [9] Characteristics of the Partial Discharge in the Development of Conductive Particle-Initiated Flashover of a GIS Insulator
    Zhao, Junping
    An, Zhengjie
    Lv, Bin
    Wu, Zhicheng
    Zhang, Qiaogen
    ENERGIES, 2020, 13 (10)
  • [10] GIS Partial Discharge Severity Assessment: A Digital Image Approach
    Jin, Zhiyang
    Qi, Bo
    Li, Chengrong
    Yu, Le
    Xing, Zhaoliang
    Xu, Dangguo
    Liu, Shaoyu
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 690 - 693