Experimental investigation on the influence of EEV opening on the performance of transcritical CO2 refrigeration system

被引:22
|
作者
Hou, Yu [1 ,2 ]
Ma, Juanli [2 ]
Liu, Changhai [2 ]
Cao, Jing [2 ]
Liu, Xiufang [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, Xian 710049, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
关键词
Transcritical CO2 refrigeration system; EEV opening; Cooling capacity; COP; CONDENSATION HEAT-TRANSFER; PRESSURE-DROP; TRANSFER COEFFICIENT; LOW-TEMPERATURES; CARBON-DIOXIDE; CYCLES; SPEED;
D O I
10.1016/j.applthermaleng.2013.12.054
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to investigate the influence of electronic expansion valve (EEV) opening on the performance of the transcritical CO2 refrigeration system, an experimental test rig of the transcritical CO2 system was built up. The system operation parameters such as temperature, pressure were measured with different EEV opening, when the inlet temperatures of the gas-cooler water and the evaporator water were set to 30 degrees C and 15 degrees C, respectively. The effects of EEV opening on the pressure, temperature and the performance of the system were studied in detail. The results demonstrate that the EEV opening has great effects on the discharge pressure of the compressor, gas-cooler outlet pressure, and the discharge temperature of the compressor. The compressor input power decreases with the increasing of EEV opening. The cooling capacity and the coefficient of performance (COP) of the system peaks at the EEV opening of 40% and 60%, respectively. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:51 / 56
页数:6
相关论文
共 50 条
  • [1] Experimental Investigation on Transcritical CO2 Refrigeration System
    Liu, Yingfu
    Shen, Pengyu
    Jin, Guangya
    ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 1156 - +
  • [2] Influence of Refrigerant Charge Amount and EEV Opening on the Performance of a Transcritical CO2 Heat Pump Water Heater
    Zhang, Ze
    Dong, Xiaojun
    Ren, Zheng
    Lai, Tianwei
    Hou, Yu
    ENERGIES, 2017, 10 (10):
  • [3] Investigation on the adaptivity of the transcritical CO2 refrigeration system with a capillary
    Song, Yulong
    Wang, Jing
    Cao, Feng
    Shu, Pengcheng
    Wang, Xiaolin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 79 : 183 - 195
  • [4] Experimental investigation of solar assisted transcritical CO2 heat pump and refrigeration system
    Key Laboratory for Thermal Science and Power Engineering, Department of Thermal Engineering, Tsinghua University, Beijing 100084, China
    Kung Cheng Je Wu Li Hsueh Pao, 2008, 3 (381-384):
  • [5] PERFORMANCE ANALYSIS OF TRANSCRITICAL CO2 REFRIGERATION SYSTEM FOR SUPERMARKET APPLICATION
    Santosa, IDewa M. C.
    Sudirman
    Ing, Suta Waisnawa
    INTERNATIONAL JOURNAL OF GEOMATE, 2018, 15 (50): : 70 - 75
  • [6] Experimental investigation of a transcritical CO2 system for simultaneous heating and cooling performance
    Peng, Xu
    Yang, Yushen
    Liu, Xinxin
    Wang, Dingbiao
    Wang, Guanghui
    Xiang, Sa
    APPLIED THERMAL ENGINEERING, 2021, 187
  • [7] Experimental investigation on a transcritical CO2 ejector expansion refrigeration system with two-stage evaporation
    Zheng, Lixing
    Deng, Jianqiang
    APPLIED THERMAL ENGINEERING, 2017, 125 : 919 - 927
  • [8] A CO2 transcritical refrigeration system with ejector and economizer
    Li M.
    Zhan H.
    Wang P.
    Liu X.
    Li Y.
    Ma Y.
    Huagong Xuebao/CIESC Journal, 2021, 72 : 146 - 152
  • [9] Experimental Study on Performance of Double-Throttling Device Transcritical CO2 Ejector Refrigeration System
    Huai, Yanshuang
    Guo, Xianmin
    Shi, Yaoguang
    8TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY (ICAE2016), 2017, 105 : 5106 - 5113
  • [10] Performance optimization of a transcritical CO2 refrigeration system using a controlled ejector
    He, Yang
    Deng, Jianqiang
    Zheng, Lixing
    Zhang, Zaoxiao
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 75 : 250 - 261