An indicator based on Wavelet and PCA to study the relationship between saline contamination and partial discharge activity in ceramic insulators

被引:0
|
作者
Boya-Lara, Carlos [1 ]
Martinez, Doris Saavedra [1 ]
机构
[1] Univ Interamer Panama, Lab Ensayos Electr Alta Tens LEEAT, Ciudad De Panama, Panama
来源
PROCEEDINGS OF THE 2022 IEEE 40TH CENTRAL AMERICA AND PANAMA CONVENTION (CONCAPAN) | 2022年
关键词
Partial discharge; pollution; saline contamination; PCA; Wavelet Transform; POLLUTION;
D O I
10.1109/CONCAPAN48024.2022.9997594
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this study, we present an indicator that establishes a relationship between environmental contamination and partial discharge activity in ceramic insulators. To develop this indicator, a method based on the use of a fog chamber was developed in which the insulators were contaminated with a degree of salinity that allowed them to exhibit high flashover activity. Simultaneously, partial discharge activity was measured and processed using Wavelet Transform and Principal Component Analysis. For each partial discharge pulse, a representative value was obtained that indicates its relationship with contamination. These results reveal the evolution of the discharges, showing the flashovers as the salinity of the insulator increases, even several minutes after the application of the saline solution. In some cases, the use of the solution was found to reduce partial discharge activity and mitigate flashovers. In this case, it has a washing effect on the salt adhering to the surface. This indicator can serve as the starting point for the creation of devices that can be placed near the insulators in the distribution lines for long periods to alert when a flashover might occur based on the evolution of the partial discharge activity.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] Classification of partial discharge severities of ceramic insulators based on texture analysis of UV pulses
    Ma, Danrui
    Jin, Lijun
    He, Jianming
    Gao, Kai
    HIGH VOLTAGE, 2021, 6 (06): : 986 - 996
  • [2] Partial Discharge Diagnosis of Ceramic Pin Insulators Case Study in a Medium Voltage Feeder
    Mahmoudi, Javad
    Moussavi, Seyed Zeinolabedin
    Sharifian, Hamid
    2017 CONFERENCE ON ELECTRICAL POWER DISTRIBUTION NETWORKS CONFERENCE (EPDC), 2017, : 68 - 73
  • [3] Study on the Interface Partial Discharge between Silicone Rubber and Fiber Reinforced Plastic in Composite Insulators
    Bao Weining
    Liu Yingyan
    Gao Yanfeng
    Li Shaohua
    Liang Xidong
    Wang Jiafu
    2015 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2015, : 762 - 765
  • [4] Study of Partial Discharge Feature Based On Complex Wavelet For Large Power Transformer
    Chen Ruiguo
    Zhao Yisong
    Sun Yanhe
    2009 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY, VOLS 1-3, 2009, : 403 - 407
  • [5] Partial Discharge Diagnosis of Ceramic Pin Insulators Considering Cost-worth Analysis: Case Study in a Medium Voltage Feeder
    Mahmoudi, Javad
    Moussavi, Seyed Zeinolabedin
    Naderi, Peyman
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2493 - 2502
  • [6] An experiment study of partial discharge pattern recognition method based on wavelet neural networks
    Zheng, Dian-chun
    Zhang, Chun-xi
    Yang, Guo-qing
    Sun, Xue-yong
    CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 230 - +
  • [7] Study on the Relationship between Electrical Tree Development and Partial Discharge of XLPE Cables
    Gao, Chaofei
    Yu, Yanlong
    Wang, Zan
    Wang, Wei
    Zheng, Liwei
    Du, Jian
    JOURNAL OF NANOMATERIALS, 2019, 2019
  • [8] Study on the fractal characteristics of ultra-wideband partial discharge signals based on wavelet analysis
    Cheng, Yonghong
    Xie, Xiaojun
    Jiang, Yan
    Chen, Xiaolin
    Xie, Hengkun
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2002, 36 (06): : 551 - 554
  • [9] Study on the fault diagnosis of partial-discharge for the eletric power transformer based on wavelet transform
    An, WD
    Sun, CX
    Ji, Y
    Quan, Z
    Heng, L
    Lei, Z
    Liu, RG
    WAVELET ANALYSIS AND ITS APPLICATIONS, AND ACTIVE MEDIA TECHNOLOGY, VOLS 1 AND 2, 2004, : 389 - 397
  • [10] Study on time delay estimation algorithm in cable partial discharge location based on wavelet transform
    Du, Yan
    Liao, Rui-Jin
    Zhou, Quan
    Lu, Yun-Cai
    Gaoya Dianqi, 2007, 5 (389-393): : 389 - 393